ML20198C091

From kanterella
Jump to navigation Jump to search
Industrial Pretreatment Quarterly Self-Monitoring Results for Oct 1998, for PNPP
ML20198C091
Person / Time
Site: Perry 
Issue date: 10/31/1998
From: Myers L, Ryder S
CENTERIOR ENERGY
To:
Shared Package
ML20198C085 List:
References
NUDOCS 9812210302
Download: ML20198C091 (1)


Text

-

INDUSTRIAL PRETREATMENT

' QUARTERLY SELF-MONITORING RESULTS

' Perry Nuclet-Power Plant Permit No.: 1004911 10 Center Rd.

Report Date: 10/22/98 Perry, Ohio 44081 Laboratory: Electro Analytical Date of Sample:.10/7 to 10/8/98 Time of sample: 1400 Sample Location: Sewage Pump Station Name of Sampler: S. Ryder Laboratory Address: 7118 Industrial Park Blvd.

Mentor, Ohio 44060-5314 Date of Analysis: 10/8 to 10/16/98 Flow: 42,800 gpd PARAMETER SAMPLE EPA-ANALYSIS DISCHARGE ANALYSIS TYPE METHOD DATE LIMIT RESULT COD Composite 410.4 10/13/98 n/a 280 mg/l BOD Composite 405.1 10/14/98 n/a 130 mg/l TSS Composite 160.2 10/16/98 n/a 140 mg/l Silver

- Composite 200.7 10/15/98 n/a

<.050 mg/l l

Mercury Composite 245.2 10/14/98 2 ug/l

<.53 ug/l pH Composite 150.1 10/8/98 5.5 to 12 s.u.

8.1s.u.

Oil / Grease Grab 1664 10/13/98 50 mg/l 180 mg/l Oil / Grease' Grab 1664 10/22/98 50 mg/l 15 mg/l

  • Oil / Grease sampled on 10/22 as a foii~'w up to the Oil / Grease results on 10/13/98.

o I certify under penalty of law that I have personally examined and I am familiar with the information in this report and that, based on my inquiry of those persons immediately responsible for obtaining the information contained in this report, I believe that the information is true, accurate, and complete. I am aware that there are significant penalties for submitting false information including the possibility of fine and imprisonment.

((Mw

////f/f8 Vice President - Nuclear

/

signature 7:

IJate'~

Title l

l.-

l

~

9812210302 981209 PDR ADOCK 05000440 R.

PDR w

>