Technical Procedure CP-206,rev 4,PCR 98-034, Specifications & Surveillance Component Cooling/Service Waster System
ML20198A291
Person / Time
Site: Calvert Cliffs  
Issue date: 02/23/1998
From: Earls C
BALTIMORE GAS & ELECTRIC CO.
To:
Shared Package
ML20198A279 List:
References
CP-206, NUDOCS 9812160219
Download: ML20198A291 (8)


Text

...

s CALVERT CLIFFS NUCLEAR POWER PLANT TECHNICAL PROCEDURE CP-206 SPECIFICATIONS AND SURVEILLANCE l

COMPONENT COOLING / SERVICE WATER SYSTEM REVISION 4 PCR 97-103 i

Safety Related __

Non-Safety Related V REFERRAL USE - PERIODICALLY REFER TO PROCEDURE DURING USE Approval Authority Effective Date 02 'O 3 --f Og-REFERRAL USE W4ysetere procedure during use 9812160219 981210 PDR ADOCK 05000317 P

PDR l

l

Specifications end Surv illance Component Cooling /Scrvice Water Syst3m CP-206 Revision 4 Page 2 of 8 l

RECORD OF REVISIONS AND CHANGES Revision PCR Number Number Summary Of Revision Or Change i

t 4

97-103 Procedure reformatted. Changed micro symbol to the word " micro", per Writer's Manual. Attachment 1 P' Squency reduced to 1/W. Changed hydrazine Action Level to <1. AodE; ammonia to the table at a frequency of 1/W. Changed Action Level notification from

  • Notify SS" to " Notify SS as i

directed by SPC."

l 4

98-032 Changed the word " micro" to micron where applicable.

a i

f i

f

\\

t i

1 l

l

e Specifications cnd Survrillince Component Co$ ling /S:rvice Wat:r Syst:m CP.206 RcVision 4 Page 3 of 8 1

t 1

TABLE OF CONTENTS I.0 PURPOSE.

5 2.0 APPLICABILITY / SCOPE

.............5

3.0 REFERENCES

AND DEFINITIONS

........5

A. PROCEDURE

DEVELOPMENT 5

B. PROCEDURE

PERFORMANCE

.5 C. DEFINITIONS x

.5 4.0 PREREQUISITES -

....6 A. RESPONSIBILITIES--

.6 5.0 PRFCAUTIONS

...... 6 i

6.0 PERFORMANCE.

.. 7

{

A. SURVEILIANCE.

.7 B. SPECIFICATIONS.

7 C. GENERIC CORRECTIVE ACTIONS -

7 7.0 POST. PERFORMANCE ACTIVITIES 7

8.0 BASIS

....... 7 9.0 RECORDS

.... 7 Attaciunent 1, Component Cooling Water System and Service Water Syter"..

.... 8 J

u 8

4 I

I r

l

Specifications end Surv:ill nce Compon:nt Cooling /Scrvice Wat r System CP-206 Revision 4 Y

Page 4 of 8 LIST OF EFFECTIVE PAGES Page No.

Change Nc.

Page No Change No.

Page No Change No.

1 2

3 4

5 EC-1 6

7 8

i l

l l

a Specifications end Survrillance Compon:nt Cooling /S:rvice Wat:r Syst m CP-206 Revision 4 l 4 Page 5 of 8 1.0 PURPOSE This procedure defines a sampling and analysis program for monitoring the water chemistry of the Component Cooling and Service Water Systems.

l 2.0 APPLICABILITY / SCOPE 1

l This procedure is applicable to the Plant Chemistry Unit.

This sampling and analysis program is applicable to the Component Cooling and Service Water System.

The procedure stipulates the s,.aillance frequencies, specifications, and corrective actions for each chemical parameter monitored. The radiochemical parameter surveillance frequencies, specifications, and corrective actions are provided in CP-224, Monitoring Radioactivity in Systems Normally Uncontaminated.

3.0 REFERENCES

AND DEFINITIONS A.

Procedure Development 1.

CP-102, General Information Records B.

Procedure Performance 1.

CP-102, GeneralInformation Records 2.

CP-224, Monitoring Radioactivity In Systems Normally Uncontaminated C.

Definitions 1.

Action Level 1:

A value or range of values for a chemical or radiochemical parameter which:

a) is inconsistent with the goals of the Chemistry Section, b) indicates an adverse trend has developed, or c) indicates long-term impacts should be anticipated or expected.

2.

Dissolved Copper:

The copper remaining in the filtrate after filtering through a 0.45 micron filter.

3.

Dissolved Iron:

EC-1 The iron remaining in the filtrate after filtering through a 0.45 micron filter.

Specifications end Surv:illance Compon:nt Cooling /S:rvice Wat:r Syst:m CP-206 Revision 4 4

Page 6 of 8 3.0.

References and Definitions (Continued) 4.

Target:

The value or range of values for a chemical or radiochemical parameter which is a goal or a predetermined warning limit. A Target is not a specification.

4.0 PREREQUISITES A.

Responsibilities 1.

The Chemistry Technicians are responsible for; a)

Sampling, analyzing, and documenting the results of the surveillance.

b)

Performing corrective actions as required.

c)

Notifying the Supervisor - Plant Chemistry, SPC, of any abnormal chemistry results or equipment conditions.

d)

Performing and documenting the initial notifications of ACTION LEVEL 1 conditions.

2.

The SPC is responsible for; a)

Ensuring the surveillance frequencies and corrective actions are performed.

b)

Ensuring that the General Supervisor - Chemistry, GSC, is notified of any ACTION LEVEL 1 condition.

c)

Ensuring that the Shift Supervisor - Operations, SS, is notified of any ACTION LEVEL 1 condition.

5.0 PRECAUTIONS None

.- _ ~-.-

Specifications end Survrillance Componsnt Cooling /S:rvice Wat r Syst:m CP-206 R: vision 4

v l

Page 7 of 8 l

l 6.0 PERFORMANCE A.

Surveillance 1.

SAMPLE the Component Cooling Water System and the Service Water System AND ANALYZE for the parameters at the frequency specified on Attachment 1.

B.

Specifications 1.

COMPARE the surveillance results to the TARGET, and ACTION LEVEL 1 values.

C.

Generic Corrective Actions 1.

VERIFY all results and pertinent information is documented.

I 2.

IF a TARGETis exceeded, THEN:

a)

NOTIFY the SPC.

b)

DOCUMENT notifications, as directed by the SPC, in the appropriate record.

c)

IMPLEMENT corrective actions as directed by the SPC.

i 3.

IF an ACTION LEVEL 1 is exceeded, THEN:

a)

RECORD the date and time the sample was collected as the " ACTION LEVEL 1 TIME OF INITIATION"in the appropriate record.

b)

NOTIFY the SPC.

c)

NOTIFY the SS, as directed by the SPC.

d)

DOCUMENT notifications in the appropriate record.

e)

RESAMPLE and ANALYZE the affected parameter as soon as practical, or as directed by the SPC, to verify entry into the ACTION LEVEL 1 condition.

f)

INCREASE surveillance frequency as directed by the SPC.

i t

g)

PERFORM corrective actions as directed by the SPC.

7.0 POST-PERFORMANCE ACTIVITIES None 8.0 BASIS l

None l

(

9.0 RECORDS None

).-

Specifications cnd Surveillanca Compon:nt Cooling /S:rvics Wat:r Syst m CP-206 t

i Rsvision 4 Page 8 of 8 COMPONENT COOLING WATER SYSTEM l

1 l

AND SERVICE WATER SYSTEM ATTACHMENT 1 PARAMETER UNITS FREQUENCY TARGET ACTION LEVEL 1 Ammonia ppm 1/W pH @ 25'C (1) 1/W 9.0 - 9.8

< 9.0

> 9.8 Hydrazine ppm 3/W 5-25

<1 Chloride ppb 1/M S 25 Dissolved ppb 1/W 55 Oxygen Dissolved ppb 1/M S 50 Copper Dissolved Iron ppb 1/M 5100 Suspended (2) ppb 1/M S1000 Solids Gamma Activity See CP-See CP-224 See CP-224 See CP-224 224 Tritium Activity See CP-See CP-224 See CP-224 See CP-224 224 1.

Sample and analyze for dissolved iron and copper if a pH change of > 2 pH units occurs over a 2-day period.

2.

Suspended solids should be sampled and analyzed at the same time as dissolved iron and copper-