TABLE 2

.

U S NUCLEAR REGULATORY COMMISSION

OFFICE OF INSPECTION AND ENFORCEMENT

CONFIRMATORY MEASUREMENTS PROGRAM

FACILITY: POINT BEACH

FOR THE 2 QUARTER OF 1936

=

=-NRC

LICENSEE----

---LICENSEE:NRC----

SAMPLE

ISOTOPE RESULT

ERROR

RESULT

ERROR

RATIO

RES

T

L WASTE

G BETA

9.7E-07

4.0E-08

6.0E-07

0.0E-01

6.2E-01

2.4E 01

D

H-3

2.0E-02

3.0E-04

2.0E-02

0.0E-01

1.0E 00

6.5E 01

A

SR-89

5.0E-08

9.0E-09

2.0E-08

0.OE-01

4.0E-01

5.6E 00

D

2 COUNT

SR-89

5.0E-08

9.0E-09

5.7E-08

0.0E-01

1.1E 00

5.6E 00

A

T TEST RESULTS:

A= AGREEMENT

D= DISAGREEMENT.

  • = CRITERIA RELAXED
N=NO COMPARISON

1

<

i

.

T

I

8611070039 861031

PDR

ADOCK 05000266

3

j

G

PDR

I

.

- - _ - . .-.

-

-

,__

,-.

__.

- . . -

. . . . .

- _ . . - .

- -

-

-

._ _ _ _ _ _ _ _ _ _ _ _ _ _

'

.

.

ATTACHMENT 1

CRITERIA FOR COMPARING ANALYTICAL MEASUREMENTS

This attachment provides criteria for comparing results of capability tests

and verification measurements.

The criteria are based on an empirical

relationship which combines prior experience and the accuracy needs of this

program.

.

In these criteria, the judgment limits are variable in relation to the comparison

of the NRC's value to its associated one sigma uncertainty.

As that ratio,

referred to in this prograra as " Resolution", increases, the acceptability of a

licensee's measurement should be more selective.

Conversely, poorer agreement

should be considered acceptable as the resolution decreases.

The values in the

ratio criteria may be rounded to fewer significant figures reported by the NRC

Reference Laboratory, unless such rounding will result in a narrowed category of

acceptance.

RESOLUTION

RATIO = LICENSEE VALUE/NRC REFERENCE VALUE

Agreement

<4

0.4 - 2.5

4-

7

0.5 - 2.0

8-

15

0.6 - 1.66

16 - 50

0.75 - 1.33

51 - 200

0.80 - 1.25

200 -

0.85 - 1.18

Some discrepancies may result from the use of different equipment, techniques,

and for some specific nuclides.

These may be factored into the acceptance

criteria and identified on the data sheet.

.