Proposed Tech Specs,Replacing Instrument Tag Number TS-CR-863 w/TS-CIT-863-3 for Chloride Intrusion Monitor
ML20196K238
Person / Time
Site: Brunswick 
Issue date: 06/27/1988
From:
CAROLINA POWER & LIGHT CO.
To:
Shared Package
ML20196K218 List:
References
NUDOCS 8807060548
Download: ML20196K238 (4)


Text

.

e ENCLOSURE 5 BRUNSWICK STEAM ELECTRIC PIANT, UNIT 1 NRC DOCKET NO. 50 325 OPERATING LICENSE NO. DPR-71 REQUEST FOR LICENSE AMENDMENT CHLORIDE INTRUSION MONITOR TECHNICAL SPECIFICATION PACES 8807060548 880627 PDR ADOCK 05000325 p

PNU

snacr 4 ta41

. :R TABLE 3.3.5.6-1 E

E CHLORIDE INTRUSION MONITORS ci MINIMUM NUMBER 8

FUNCTIONAL UNIT AND INSTRUMENT NUMBER OPERABLE CHANNELS (a)

CZy 1.

Chloride leak detectors in the condenser 4

hotwell outlet headers (CO-CR24) 2.

Chloride leak dbtector in the condensate 1

pump discharge (CO-CIS-3075-1 or TS-CIT-863-3) 3.

Chloride leak detector in the inlet to the 1

condensate filter demineralizer (CFD-CIT-1) 4.

Chloride leak detector in the inlet to the 1

deep bed demineralizer (CDD-CIT-1)

Y*

a.

Chloride intrusion can be detected if any of the functional units have their required minimum number of channels OPERABLE.

i

}

h a

a n

i f

t a

T

. MSE61-1R)'-

' TABLE 3.3.5.6-2

~

E E

CHLORIDE INTRUSION MONITORS SETPOINTS M*

FUNCTIONAL UNIT AND INSTRUMENT NUMBER ALARM SETPOINT ALLOWABLE LIMIT' E

1.

Chloride leak detectors in the condenser

~ $ 1.0 pahos/cm 5 2.0.pahos/cm-y hotwell outlet headers (CO-CR24) t 2.

Chloride leak detector in the condensate 3

pump discharge Wide range monitor (CO-CIS-3075-1)

$ 2.0 pahos/cm 5 10 pahos/cm a.

b.

Narrow range monitor (TS-CIT-863-3)

$ 0.3 pahos/cm 5 0.5 pahos/cm f

3.

Chloride leak detector in the inlet to the

$ 0.3 pahos/cm 5 0.5 pahos/cm filter demineralizer (CFD-CIT-1) i t'

4.

Chicride leak detector in the inlet to 5 0.3 pahos/cm 5 0.5 pahos/cm the deep bed demineralizer (CDb-CIT-1)

Y 5

4 e

a i

a n

Z t

Y b

D

suacr 4 rats ~

-,.J TABLE'4.3.5.6-1 E

y CHLORIDE INTRUSION MONITORS SURVEILLANCE REQUIREMENTS M"

' CHANNEL CHANNEL FUNCTIONAL CHANNEL FUNCTIONAL UNIT AND INSTRUMENT NUMBER CHECK TEST CALIBRATION 3

1.

Chloride leak detector in the condenser D

H R

hotwell outlet headers (CO-CR24) 2.

Chloride leak detector in the D

M SA condensate pump discharge (CO-CIS-3075-1 or TS-CIT-863-3) l 3.

Chloride leak detector in the inlet to D

M

~ SA the condensate filter demineralizer ti (CFD-CIT-1) n y

4.

Chloride leak detector in the inlet to D

M SA g

the deep bed demineralizer (CDD-CIT-1)

Y 6

a 8n

_