10 CFR 50.36 georgina o,etne a c., company gn4.g.g.o am g

g;n,sge SC 29065 Nuclear Operations SCE&G

=

November 18, 1988 Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555

Subject:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Technical Specifications 3/4.8.1 A. C. Sources Gentlemen:

Please find attached the subject Technical Specification with the corrections as identified in the conference call between Mr. J. J. Hayes of the NRC and Mr.

W. R. Higgins of my staff that took plat.e on September 14, 1988. There have also been some minor editorial changes which, along with the above, will be 3

denoted with marginal revision indicators. Also included in this submittal is a "No Significant Hazards" determination.

In the above referenced conference call, the NRC reviewer stated that loading of the Diesel Generator was part of the ten tests identified in the note ori Table 4.8-1.

This requirement was added by identifying surveillance requirement 4.8.1.1.2.A.4 in the note. The NRC reviewer also commented that loading the Diesel Generator in surveillance requirement 4.8.1.2 was not required.

Therefore, the "(with the exception of 4.8.1.1.2.a.4)" was added.

The reviewer also indicated that Diesel Generator failure reporting requirements were also applicable in 4.8.1.2.

Therefore, 4.8.1.1.3 was added i

to surveillance requirement 4.8.1.2.

I declare that the statements and matters set forth herein are true and correct to the best of my knowledge, information and belief. Should you have any questions, please contact us at your convenience.

Very truly yours, W An A

0. S. Bradham WRH/OSB: led Attachments l

cc: See Page 3 8811300448 881118 i

PDR ADOCK 05000375 P

PNU

l

\\

Document Control Desk November 18, 1988 Page 2 c:

D. A. Nauman/J. G. Connelly, Jr./0. W. Dixon, Jr./T. C. Nichols, Jr.

E. C. Roberts W. A. Williams, Jr.

M. L. Ernst J. J. Hayes, Jr.

General Managers C. A. Price /R. M. Campbell, Jr.

R. B. Clary K. E. Nodland J. C. Srelson G. O. Percival R. L. Prevatte J. B. Knotts, Jr.

H. G. Shealy NSRC HPCF RTS TSP 5E0)

File 813.20)

(