r June 7,1988 Docket Nos.:
50-295 ana 50-304 DISTRIBUTION m Docket File D OGC-Rockville NRC/ Local ~~PDRi EJordan PDIII-2 Rdg.
JPartlow TMurley/JSniezek T8arnhart(8)
Mr. Henry Bliss FMiraglia ACRS (10)
Nuclear Licensing Manager DCrutchfield GPA/PA Commonwealth Edison Company GHnlahan ARM /LFMB Post Office Box 767 LLuther PDIII-2 Plant File Chicago, Illinois 60690 JNorris
Dear Mr. Bliss:
SUBJECT:
ZION NUCLEAR POWER STATION, UNITS 1 AND 2 - FIRE PROTECTION APPENDIX R TO 10 CFR PART 50 (TAC N0s. 55582 AND 55583)
By letter dated July 27, 1984, Comonwealth Edison Company (CECO) submitted reassessment of the safe shutdown capability and revised _ proposed modifications to meet the requirements of Appendix R to 10 CFR Part 50, including Section III.G.3 and III.L. By the same letter of July 27, 1984, Ceco requested several exemptions from Section III.G.2 and III.G.3 of Appendix R.
The July 27, 1984 submittal has been supplemented by letters datad August 31, 1984, January 24, 1985, February 18, 1986, February 9,1987, January 21 and February 23, 1988.
i The staff has reviewed all of the above suomittals and granted six exemptions.
The staff has also concluded that one of the exemptions requested was not j
necessary.
The details of the staff's review are contained in the Safety Evaluation attached to the exemption.
The approval of the interim measures safe shutdown capability, and modifications to meet Appendix R are the subject of other licensing action.
Sincerely, 7s Jan A. Norris, Project Manager Project Directorate III-2 Division of Reactor Projects - III, IV, V and Special Projects
Enclosure:
As stated cc w/ enclosure:
See ne t page
- See Previous Concurrence s
PDIII-4:PM PDIII-2:LA OGC-Rock.
PDI L : 0
- JNorrfs:bj
- LLuther
- RFonner LN olm 11 7
11/19/87 11/23/87 g'/gD/88 a n tc d
f /'s /88
(,/7/88
$%P2gggg $%8%p F
t
Docket Hos.:
50-295 Distribution and 50-304 Docket File 0GC-Bethesda NRC & Local PDRs Edordan PDIII-2 Rdg JPartlow Mr. L. D. Butterfield, Jr.
TMurley/JSniezek TBarnhart(8)
Nuclear Licensing Manager FMiraglia ACRS(10)
Comonwealth Edison Company CRossi 1
GPA/PA Post Office Box 767 GHolahan
(
ARM /LFMB PDIII-2 Piant File Chicago, Illinois 60690 LLuther JNorris
Dear Mr. Butterfield:
SUBJECT:
ZION NUCLEAR POWER STATION, UNITS 1 AND 2 - FIRE PROTECTION -
APPENDIX R TO 10 CFR PART 50 (TAC NOS. 55582 AND 55583)
By letter dated July 27, 1984, Comonwealth Edison Company (CECO) submitted reassessment of the safe shutdown capability and revised proposed modifications to meet the requirements of Appendix R to 10 CFR Part 50, i
including Section III.G.3 and III.L.
By the same letter of July 27, 1984, CECO requested several exemptions from Section III.G.2 and III.G.3 of Appendix R.
The July 27, 1984 submittal has been supplemented by letters dated August 31, 1984, January 24,1985, February 18, 1986 and February 9, 1987.
The staff has reviewed all of the above submittals and granted six exemptions.
The staff has also concluded that one of the exemptions requested was not necessa ry. The details of the staff's review are contained in the Safety Evaluation attached to the exemption.
The approval of the interim measures safe shutdown capability, and modifications to meet Appendix R are the subject of other licensing action.
Daniel R. Muller, Director Project Directorate III-2 Division of Reactor Projects - III, IV, V and Special Projects
Enclosure:
As stated cc w/ enclosure:
See next page LA:PD32:DR PM:P 2: RSP O
BETHESDA LLUTHER JNORRIS
- // //87
/// fy/87 ll/Jy/87 D:PD32:DRSP AD/DRSP D:DRSP DRMULLER GMHOLAHAN DMCRUTCHFIELD
/ /87
/ /87
/ /87 t
j
' one il o
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 l;
- y June 7,1988 Docket Nos.
50-295 and 50-304 Mr. Henry Bliss Nuclear Licensing Manager Comonwealth Edison Company Post Office Box 767 Chicago, Illinois 60690
Dear Mr. Bliss:
SUBJECT:
ZION NUCLEAR POWER STATION, UNITS 1 AND 2 - FIRE PROTECTION APPENDIX R TO 10 CFR PART 50 (TAC N0s. 55582 AND 55583)
By letter date.1 July 27,1984, C;inonwealth Edison Company (CECO) submitted ret.sessment of the safe shutdown capability and revised proposed modifications to meet the requirements of Appendix R to 10 CFR Part 50, including Section III.G.3 and III.L.
By the same letter of July 27, 1984, CECO requested several exemptions from Section III.G.? and III.G 3 of Appendix R.
The July 27, 1984 submittal has been supplemented by letters dated August 31, 1984 January 24, 1985. February 18, 1986, February 9,1987, January 21 and February 23, 1988.
The staff has reviewed all of the above submittals and granted six exemptions.
The staff has also concluded that one of the exemptions requested was not necessary. The details of the staff's review are contained in the Safety Evaluation attached to the exemption.
The approval of the interim measures safe shutdown capability, and modifications to ercet Appendix R are the subject of other licensing at Hon.
Sincerely, bk Jaln A. Norris, Project Manager Project Directorate III-2 Division of Reactor Projects - III, IV, Y and Special Projects
Enclosure:
As stated cc w/ enclosure:
See next page
..,-..--....Y..-..-,,.__.-..-..-,-.-,,
Mr. Henry Bliss Commonwealth Edison Company Zion Station ec:
Robert J. Vollen, Esquire Mr. Michael C. Parker, Chief 109 North Dearborn Street Division of Engineering Chicago, Illinois 60602 Illinois Department of Nuclear Safety Dr. Cecil Lue-Hing 1035 Outer Park Drive, 5th Floor Director of Research and Development Springfield, Illinois 62704 Metropolitan Sanitary District of Greater Chicago 100 East Erie Street Chicago, Illinois 60611 1
Phillip Steptoe, Esq.
l Sidley and Austin One First National Plaza Chicago, Illinois 60603 l
Mayor of Zion Zion, Illinois 60099 Illinois Department of Nuclear Safety ATTN: Manager, Nuclear Facility Safety 1035 Outer Park Drive, 5th Floor Springfield, Illinois 62704 U.S. Nuclear Regulatory Commission Resident Inspectors Office 105 Shiloh Blvd.
Zion, Illinois 60099 Regional Administrator, Region III U.S. Nuclear Regulatory Connission 799 Roosevelt Road Glen Ellyn, Illinois 60137 e
i
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _