1 DISTRIBUTION Docket;Fjle J F NRC PDR Local PDR June 8, 1988 PD21 r/f S.Varga(14E4)
G. Lainas E.'Adensam Docket No. 50-416 P. Anderson L. Kintner OGC Hr. Oliver D. Kingsley, Jr.
E. Jordan (NNBB 3302)
Vice President, Nuclear Operations J. Partlow (9A2)
System Energy Resources, Inc.
ACRS~(10)
P.O. Box 23054 Jackson, Mississiopi 39205
Dear Mr. Kingsley:
SUBJECT:
GRAND GULF NUCLEAR STATION (GGNS), UNIT 1 - PROPOSED TECHNICAL SPECIFICATION CHANGE REGARDING CONTROL R0D SCRAM ACCUMULATOR ALARM OPERABILITY (TAC N0. 67976)
By letter dated April 22, 1988, System Energy Resources, Inc. (the licensee) requested a change to Technical Specification 3/4.1.3.3, which requires all control rod scram accumulators to be operable.
The proposed change would provide for alternate sarveillance tests in Section 4.1.3.3 when the accumu-lator pressure and leakage alarm circuit is inoperable.
The NRC staff is reviewing your submittal and finds that additional information is needed to complete its review.
The alternate surveillance tests should be i
made action statements, and the present surveillance requirements should not be changed to be consistent with the format of the GGNS Technical Specifications.
The analysis of the issue of no significant hazards consideration should be changed to consider the following factors:
1.
The magnitude of expected accumulator pressure decay and leakage for the proposed surveillance intervals based on operating experience, 2.
The accident or transient which the accumulators are designed to mitigate, 3.
Whether the accident or transient caused by failure of accumulators to l
function is a new or different kind from any previously evaluated, and 4.
The margin of safety involved in the function of accumulators (e.g.,
minimum pressure and maximum leakage) and the effect of the change on this margin.
4 In order to complete our review as scheduled, you are requested to provide the i
above information by July 8, 1938.
l gRo6170108 880609
~
p ADOCK 05000416 VDR i
.v.
i l-Mr. Oliver D. Kingsley, Jr.- The reporting and/or recordkeeping requirements contained'in this letter. affect-
~
fewer than ten respondents;-therefore, OMB clearance.is not required under P. L.96-511.
2 -
1 Sincerely, t
Lester L. Kintner, Sr. Project: Manager-Project Directorate 11-1
~
Division'.of Reactor Projects'I/II
~
cc: See next page 1
1 l
0FC
- LA:Rb2 DRPR:D:P fgRPR:
_____:. p._ DRPR:PM:
_(___.__
.g.___...__________.__,,,,,_____,,,____,,,,,,,,,,,,,,,,,,,
NAME : Pang on
- LK ner:ch nsam
_____: ____J._____:____________.____...____,..____________.,____,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
6/f/88 6/f/88 DATE : ^6/S/88 0FFICIAL RECORD COPY
x
'Q s
Mr. Oliver D. Kingsley, Jr.
System Energy Resources, Inc.
Grand Gulf Nuclear Station (GGNS) cc:
Mr. Ted H. Cloninger Mr. C. R. Hutchinson Vice President, Nuclear Engineering GGNS General Manager and Support System Energy Resources, Inc.
System Energy Rasources, Inc.
Post Office Box 756 Post Office Box 23054 Port Gibson, Mississippi 39150 Jackson, Mississippi 39205 Robert B. McGehee, Esquire The Honorable William J. Guste, Jr.
Wise, Carter, Child, Steen and Caraway Attorney General P.O. Box 651 Department of Justice i
Jackson, Mississippi 39205 5 tate of Louisiana Baton Rouge, Louisiana 70804 Nicholas S. Reynolds, Esquire Bishop, Liberman, Cook, Purcell Office of the Governor 1
and Reynolcs State of Mississippi 1400 L Street, N.W.
Jackson, Mississippi 39201 Washington, D. C.
20005-3502 Attorney General Mr. Ralph T. Lally Gartin Building Nanager of Quality Assurance Jackson, Mississippi 39205 Middle South Utilities System Services, Inc.
i 639 Loyola Avenue, 3rd Floor Mr. Jack McMillan, Director New Orleans, Louisiana 70113 Division of Solid Waste Management Mississippi Department of Natural Mr. John G. Cesare Resources Director, Nuclear Licensing Post Office Box 10385 Syster Energy Resources, Inc.
Jackson, Mississippi 39209 P.O. Box 23054 Jackson, Mississippi 39205 Alton B. Cobb, M.D.
State Health,0fficer Mr. C. B. Hogg, Project Manager State Board of Health Bechtel Power Corporation P.O. Box 1700 P. O. Box 2166 Jackson, Mississippi 39205 Houston, Texas 77252-2166 President Mr. Ross C. Butcher Claiborne County Board of Supervisors Senior Resident Inspector Port Gibson, Mississippi 39150 U. S. Nuclear Regulatory Commission 101 Marietta Street, N.W., Suite 3100 Atlanta, Georgia 30323 Mr. James E. Cross GGNS site Director Systems Energy Resources, Inc.
P.O. Box 756 Port Gibson, Mississippi 39150
--