ELECTRICAL EQUIPMENT PROTECTIVE DEVICES SAFETY-RELATED MOTOR-OPERATED VALVES THERMAL OVERLOAO PROTECTION AND BYPASS DEVICES LIMITING CONDITION FOR OPERATION 3.8.4.2 The thermal overload protection bypass devices of each safety related motor-operated valve given in Table 3.8-1 shall be OPERABLE.
APPLICABILITY:
Whenever the motor operated valve is required to be OPERABLE.
ACTION:
With the thermal overload protection bypass devices for any one or more safety-related motor-operated valves inoperable, declare the affected valve (s) inoper-able and apply the appropriate ACTION Statement (s) of the affected valve (s).
SURVEILLANCE REQUIREMENTS 4.8.4.2 The above required thermal overload protection bypass devices shall be verified to be OPERABLE.
Following maintenance on the valve motor starter, and a.
b.
Following any periodic testing during which the, thermal overload device was temporarily placed in force.
?
c.
At least once per 18 months, j