ELECTRICAL EQUIPMENT PROTECTIVE DEVICES SAFETY-RELATED MOTOR-OPERATED VALVES THERMAL OVERLOAO PROTECTION AND BYPASS DEVICES LIMITING CONDITION FOR OPERATION 3.8.4.2 The thermal overload protection bypass devices of each safety related motor-operated valve given in Table 3.8-1 shall be OPERABLE.

APPLICABILITY: Whenever the motor operated valve is required to be OPERABLE.

ACTION:

With the thermal overload protection bypass devices for any one or more safety-related motor-operated valves inoperable, declare the affected valve (s) inoper-able and apply the appropriate ACTION Statement (s) of the affected valve (s).

SURVEILLANCE REQUIREMENTS 4.8.4.2 The above required thermal overload protection bypass devices shall be verified to be OPERABLE. ,

a. Following maintenance on the valve motor starter, and
b. Following any periodic testing during which the, thermal overload device was temporarily placed in force.  ?
c. At least once per 18 months, j