Forwards Insp Repts 50-277/98-08 & 50-278/98-08 on 980811-0921 & Nov.First Violation Occurred When Inadequate Sys Restoration Instructions in Rwcs Operating Procedures Did Not Detect Valves That Were Mispositioned
ML20155D384
Person / Time
Site: Peach Bottom  Constellation icon.png
Issue date: 10/28/1998
From: Anderson C
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Rainey G
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
Shared Package
ML20155D387 List:
References
RTR-REGGD-01.033, RTR-REGGD-1.033 50-277-98-01, 50-277-98-08, 50-277-98-1, 50-277-98-8, 50-278-98-01, 50-278-98-08, 50-278-98-1, 50-278-98-8, EA-98-410, NUDOCS 9811030208
Download: ML20155D384 (4)


See also: IR 05000277/1998008

Text

.

. . -

-- .

. .

.

_.

- . -

.

. . . ~

~

-.

- . .

- . - ..

.

t'r'

t

-

October 28, 1998

EA 98-410 '

Mr. G. Hainey, President

PECO Nuclear

Nuclear Group Headquarters

Correspondence Control Desk

P.O. Box 195

Wayne, Pennsylvania 19087-0195

SUBJECT:

NRC INTEGRATED INSPECTION REPORT 50-277/98-08,50-278/98-08

Dear Mr. Ralaey:

I

On September 21,1998, the NRC completed an inspection at the Peach Bottom Atomic

Power Station. The enclosed report presents the results of that inspection.

During the six-week period covered by this inspection period, your staff continued to

operate both units at the Peach Bottum Atomic Power Station safely. Operators in the

control room demonstrated very good communication practices during this inspection.

1

Operators also showed very good questioning attitude while pursing a breaker problem and

i

during the review of a surveillance procedure.

,

Based on the results of this inspection, the NRC has determined that two violations of NRC

requirements occurred. These violations are cited in the enclosed Notice of Violation

"

- (Notice) and the circumstances surrounding them are described in detail in the subject

inspection report.

The first violation occurred when inadequate system restoration instructions in the reactor

water cleanup system operating procedure did not detect, on two occasions, valves that

were mispositioned in maintenance activities. The first occasion of mispositioned valves

caused a steam leak into a room outside of containment and an unplanned entry into

emergency operating procedures. The second occasion caused an unexpected engineered

i

safety feature actuation (i.e. automatic system isolation). We determined that this

\\

violation was repetitive since the corrective actions for a prior plant status / configuration

control violation cited in NRC Inspection Report 50-277(278)/98-01 were not sufficient in

order to preclude this violation, in your response to this violation, please provide your

assessment as to why your corrective actions for the prior plant status / configuration

control violation were not effective to prevent this violation.

The cecond violation was identified by an NRC inspector and involved the failure of

radiation protection technicians to fully comply with a procedure associated with source

checking of instruments used to survey incoming shipments of radioactive material.

"'

9811030208 981028

PDR

ADOCK 05000277

G

PDR

3

0FFICIAL. RECORD COPY

IE:01

!

  • J

l

G. Rainey

2

The NRC has concluded that information regarding the reason for the second violation, and

the actions taken or planned to correct this violation and prevent recurrence is already

adequately addressed in this inspection report. Therefore, you are not required to respond

to this violation unless the descriptions in the referenced report do not accurately reflect

your corrective actions or your position, in that case, or if you choose to provide

additional information, you should follow the instructions specified in the enclosed Notice.

The radwaste processing, handling, storage, and radioactive material transportation

programs, limited senior reactor operator requalification program, and construction of the

independent spent fuel storage installation (ISFSI) were also inspected by Region I

specialists during this inspection period. We noted that radwaste processing, handling,

storage, and radioactive material transportation programs were effective. We concluded

that the limited senior reactor operator requalification program was good overall. We also

determined that construction activities on the east retaining wall of the ISFSI were

acceptable.

In accordance with 10 CFR 2.790 of the NRC's " Rules of Practice," a copy of this letter

and its enclosures will be placed in the NRC Public Document Room (PDR).

We appreciate your cooperation.

Sincerely,

Original Signed by:

Clifford J. Anderson, Chief

Projects Branch 4

Division of Reactor Projects

Docket Nos.: 50-277,50-278

License Nos.: DPR-44, DPR-56

Enclosures:

1. Notice of Violation

2. Inspection Report No. 50-277/98-08 and 50-278/98-08

.

_

_

_

_ . . _

._

. _ . - _

_ _ - - .

.

.

..

N

$

G. Rainey

3

cc w/encls:

J. Hagan, Vice President, Nuclear Station Support

J. Doering, Vice President, Peach Bottom Atomic Power Station

M. Warner, Plant Manager, Peach Bottom Atomic Power Station

G. D. Edwards, Chairman, Nuclear Review Board

R. Boyce, Director, Nuclear Quality Assurance

A. F. Kirby,111, External Operations - Delmarva Power & Light Co.

G. J. Lengyel, Manager, Experience Assessment

J. W. Durham, Sr., Senior Vice President and General Counsel

T. M. Messick, Manager, Joint Generation, Atlantic Electric

W. T. Henrick, Manager, External Affairs, Public Service Electric & Gas

R. McLean, Power Plant Siting, Nuclear Evaluations

D. Levin, Acting Secretary of Harford County Council

R. Ochs, Maryland Safe Energy Coalition

J. H. Walter, Chief Engineer, Public Service Commission of Maryland

Mr. & Mrs. Dennis Hiebert, Peach Bottom Alliance

Mr. & Mrs. Kip Adams

Commonwealth of Pennsylvania

State of Maryland

TMI- Alert (TMIA)

b

l

- -

-

-

. . -

- .

.

.

-

.

. . -

. .-

-

.

. -_

j

,

G. Rainey:

4

,

Distribution w/encls:

Region I Docket Room (with concurrences)

H. Miller, RA/W. Axelson, DRA (1)

B. Boger, ADPR. NRR

J. Goldberg, OGC

J. Lieberman, OE (OEMAIL)

D Holody, ORA

}

T. Walker, ORA

L. Manning, ORA

C. Anderson, DRP

D. Florek, DRP

S. Barr, DRP

R. Junod, DRP

Nuclear Safety Information Center (NSIC)

NRC Resident inspector

PUBLIC

Distribution w/encis: (Via E-Mail)

3

B. McCabe, OEDO

R. Capra, PDI 2, NRR

inspection Program Branch, NRR (IPAS)

,

,'

M. Thadani, NRR

B. Buckley, NRR

R. Correia, NRR

W. Kane, NMSS/SFPO

S. Shankman, NMSS/SFPO

E. Leeds, NMSS/SFPO

M. Ross-Lee, NMSS/SFPO

P. Eng, NMSS/SFPO

M. Campion, ORA

DOCDESK

DOCUMENT NAME: G:\\ BRANCH 4\\PB\\PB980808. INS

To receive a copy of this document, indicate in the box: "C" = Copy without

attachment /enci s

s

"E" = Copy with attachment / enclosure

"N" = No copy

OFFICE

Rl/g7)

l

Rl/DRP

,

NAME

DFJppfek

/

CAnderson cfi

DATE

1DTf)/98

10/M /98

OFFICIAL RECORD COPY

- -