Mr. William T. Cottia October 15,1998 RE-ISSUED Prasid:nt and Chisf Executive Officer INTERNAL ONLY STP Nucl:ar Operating Company 10/27/98 South Texas Project Electric Generating Station P. O. Box 289 Wadsworth, TX 77483
SUBJECT:
10 CFR PART 50, APPENDIX R, DEVIATION REQUEST FOR FIRE AREA 07, SOUTH TEXAS PROJECT, UNITS 1 AND 2 (STP)(TAC NOS. M92177 AND M92178)
Dear Mr. Cottle:
By letter dated September 14,1995 (superseding a letter dated April 13,1995),
supplemented by letters dated November 6,1996, May 22, and August 4,1997, Houston Lighting and Power submitted a request for deviation from its approved fire protection program as it incorporates Section Ill.G.2.c of Appendix R to 10 CFR Part 50 for fire area 07 to the extent that it specifies that an automatic fire suppression system be provided in the area. The request has been adopted by STP Nuclear Operating Company. The Nuclear Regulatory Commission (NRC) staff has reviewed the request and has concluded that the change to the approved fire protection program does not adversely affect the abilty to achieve and maintain safe shutdown in the event ofa fire and, therefore, does not require prior approval of the Commission under Paragraph 2.E of the licenses. Our safety evaluation is enclosed.
[
Sincerely, ORIGINAL SIGNED BY:
Thomas W. Alexion, Project Manager Project Directorate IV-1 Division of Reactor Projects Ill/lV 1
Office of Nuclear Reactor Regulation Docket Nos. 50-498 and 50-499 gI g gg ISTEvd g: Tpy
Enclosure:
As stated cc w/enci: See next page J
i-
' DISTRIBUTION:
Docket Filel PUBLIC PD4-1 r/f TGwynn, RIV OGC SWest
- EAdensam (EGA1)
JHannon CHawes TAlexion ACRS pbl O l Document Name: STP92177.LTR
- SEE PREVIOUS CONCURRENCE OFC PM/PD4-1 LA/PD4-1 OGC*
SL/SPLB*
D/PD4-1
]
NAME TAlexion/vw CHawes Shorn SWest JHannon l
DATE
/
/98
/
/98 10/05/98 10/05/98
/
/98 COPY YES/NO YES/NO YES/NO YES/NO YES/NO OFFICIAL RECORD COPY 9810300053 981027 7
PDR ADOCK 05000498 l
F PDR i
r, __
e.
, _. ~
Mr. William T. Cottle Octcber 15, 1998
- \\ohh?
President cnd Chl:f Extcutiva Officer STP Nuclear Oper; ting Company 1-lhili?
South Texas Proj:ct Electric h,
Generating Station NI
/,
P. O. Box 289 Wadsworth,TX 77483 i
SUBJECT:
10 CFR PART 50, APPENDIX R, DEVIATION REQUEST FOR FIRE AREA 07, SOUTH TEXAS PROJECT, UNITS 1 AND 2 (STP)(TAC NOS. M92177 AND M92178)
Dear Mr. Cottle:
By letter dated September 14,1995 (superseding a letter dated April 13,1995),
supplemented by letters dated November 6,1996, May 22, and August 4,1997, Houston Lighting and Power submitted a request for reviation from its approved fire protection program I
as it incorporates Section Ill.G.2.c of Appendix R to 10 CFR Part 50 for fire area 07 to the extent that it specifies that an automatic fire suppression system be provided in the area. The request has been adopted by STP Nuclear Operating Company. The Nuclear Regulatory Commission (NRC) staff has reviewed the request and has concieded that the change to the approved fire protection program does not adversely affect the ability to achieve and main safe shutdown in the event of a fire and, therefore/r%uire prior approval of the Commission under Paragraph 2.E of the licenses. Our safety evaluation is enclosed.
Sincerely, ORIGINAL SIGNED BY:
Thomas W. Alexion, Project Manager Project Directorate IV-1 Division of Reactor Projects Ill/lV Office of Nuclear Reactor Regulation 7
' Docket Nos. 50-498 and 50-499
Enclosure:
As stated cc w/enci: See next page DISTRIBUTION: