___-. _

I

\\

ATTACHMENT B NPF 88 PROPOSED 4

i 4

8809290215 980921 PDR ADOCK 05000302 P

PDC NS20760

1 I

PRO'OSi3 IiiSTRUMENTATION CHEMICAL DETECTION SYSTEMS AMMONIA DETECTION SYSTEM

  1. 64cre LIMITING CONDITION FOR OPERATION

=-

~

_ - ~

~-~~~w

___~

_ ~

3.3.3.7.2 Two independent ammonia detection systems, with their alarm / trip setpoints adjusted to actuate at an ammonia concentration of less than or equal to 50 ppm, shall be OPERABLE.

APPLICA8ILIITY:

All MODES.

ACTION:

a.

With one ammonia detection system inoperable, restore the inoperable detection system to OPERABLE status within 7 days or within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> initiate and maintain operation of the control room ventilation system in the recirculation mode of operation.

b.

With no ammonia detection system OPERABLE, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> initiate and maintain operation of the control room ventilation system in tne recirculation mode of operation.

c.

The provisions of Specification 3.0.4 are not applicable.

SURVEILLANCE REQUIREllENTS I

4.3.3.7.2 Each ammonia detection system shall be demonstrated OPERABLE by I

performance of a CHANNEL CHECK at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, a CHANNEL FUNCTIONAL TEST at least once per 31 days and a CHANNEL CALIBRATION at least once per 18 months.

D El. ET E!L

[ TilI S PAGE I!1TEt1TIOt1 ALLY BLA!1K ]

l t

I i

l 1

l WATERFORD - UNIT 3 3/4 3-a8 PRCPOSED

INSTRt[ MENTATION PRO 30SD 8ASES 3/4.3.3.6 ACCIDENT HONITORING INSTRUMENTATION The OPERABILITY of the accident monitoring instrumentation ensures that sufficient information is available on selected plant parameters to monitor and assess these variables following an accident.

This capability is consistent with the recommendations of Regulatory Guide 1.97, "Instrumentation for Light-Water-Cooled Nuclear Plants to Assess Plant Conditions Ouring and Following an Accident," December 1980 and NUREG-0578, "TMI-2 Lessons Learned Task Force Status Report and Short-Term Recommendations." Table 3.3-10 includes Regulatory Guide 1.97 Category I key variables.

The remaining Category I variables are included in their respective specifications.

The Subcooled Margin Monitor (S M ), the Heated Junction Thermocouple (HJTC), and the Core Exit Thermocouples (CET) comprise the Inadequate Core Cooling (ICC) instrumentation required by Item II.F.2 NUREG-0737, the Post THI-2 Action Plan.

The function of the ICC instrumentation is to enhance the ability of the plant operator to diagnose the approach to existence of, and recovery from ICC.

Additionally, they aid in tracking reactor coolant inventory.

These instruments are included in the Technical Spe:ifications at the request of NRC Generic Letter 83-37.

These are not required by the accident analysis, nor to bring the plant to Cold Shutdown.

In the event more than four sensors in a Reactor Vessel Level channel are inoperable, repairs may only be possible during the next refueling outage.

This is because the sensors are accessible only after the missile shield and reactor vessel head are removed.

It is not feasible to repair a channel except during a refueling outage when the missile shield and reactor vessel head are removed to refuel the core.

If only one channel is inoperable, it should be restored to OPERABLE status in a refueling outage as soon as reasonably possible.

If both channels are inoperable, at least one channel shall be restored to OPERABLE status in the nearest refueling outage.

3/4.3.3.7 CHEMICAL DETECTION SYSTEMS bur 5 The chemical detection systems are the chlorine, and broad range toxic gas detection systems.

The OPERABILITY of the chemical detection systems ensures that sufficient capability is available to promptly detect and initiate protective action in the event of an accidental chemical release.

~

The chemical detection systems provide prompt detection of toxic gas re-leases which could pose an actual threat to safety of the nuclear power plant or significantly hamper site personnel in performance of duties necmssary for the safe operation of the plant.

The broad range toxic gas detection system operates on the principle of gas photoionization, and therefore, the system is sensitive to a broad range of gases.

The system is therefore sensitive to both atmospheric and chemical composition normal fluctuations affecting the Waterford 3 site.

The setpoint WATERFORD - UNIT 3 B 3/4 3-3 AMENDMENT NO. I A, 20 PROPOSEJ