. -. -. _. ~. -. - - -.. - - - -.

. ~..

i NOTICE OF VIOLATION New York Power Authority Docket No. 50-333 James A. FitzPatrick Nuclear Power Plant License No. DPR 59 in accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," (60 FR 34381; June 30,1995), the following violation was identified:

10 CFR 50, Appendix B, Criterion ill, " Design Control", requires that applicable regulatory requirements and the design basis for safety-related systems and components are correctly translated into the plant's design.

Contrary to the above, NYPA did not correctly translate the applicable design basis for safety-related systems and components into the plant's design in that the effects of a short circuit on the protection scheme for certain containment penetrations were not analyzed, per the design bases for the conditions of a loss of coolant accident coincident with a loss of offsite power.

This is a Severity Level IV Violation (Supplement I).

The NRC has concluded that information regarding the reason for the violation, the corrective actions taken and planned to correct the violation and prevent recurrence and the date when full compliance was achieved is already adequately addressed on the docket in Inspection Report 50-333/98-05, dated September 28,1998. However, you are required to submit a written statement or explanation pursuant to 10 CFR 2.201 if the i

description therein does not accurately reflect your corrective actions or your position. In that case, or if you choose to respond, clearly mark your response as a " Reply to a Notice of Violation," and send it to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555 with a copy to the Regional Administrator, Region I, and a copy to the NRC Resident inspector at the facility that is the subject of this notice, within 30 days of the date of the letter transmitting this Notice of Violation (Notice).

4 If you contest this enforcement action, you should also provide a copy of your response to the Director, Office of Enforcement, United States Nuclear Regulatory Commission, Washington, DC 20555-0001.

Because your response will be placed in the NRC Public Document Room (PDR), to the extent possible, it should not include any personal privacy, proprietary, or safeguards information so that it can be placed in the PDR without redaction. If personal privacy or proprietary information is necessary to provide an acceptable response, then please provide a bracketed copy of your response that identifies the information that should be protected and a redacted copy of your response that deletes such information. If you request withholding of such material, you M9.11 specifically identify the portions of your response that you seek to have withheld and provide in detail the bases for your claim of withhold-ing (e.g., explain why the disclosure of information will create an unwarranted invasion of personal privacy or provide the information required by 10 CFR 2.790(b) to support a 9810060024 980928 PDR ADOCK 05000333 G

1 2

l

' request for withholding confidential commercial or financiat information). If safeguards l

information is necessary to provide an acceptable response, please provide the level of protection described in 10 CFR 73.21.

l Dated at King of Prussia, Pennsylvania

. this 28th day of September,1998 l

i i.

l l-