ML20151P809
| ML20151P809 | |
| Person / Time | |
|---|---|
| Site: | Vogtle (NPF-068) |
| Issue date: | 08/02/1988 |
| From: | Matthews D Office of Nuclear Reactor Regulation |
| To: | City of Dalton, GA, Georgia Power Co, Municipal Electric Authority of Georgia, Oglethorpe Power Corp |
| Shared Package | |
| ML20151P814 | List: |
| References | |
| NPF-68-A-007 NUDOCS 8808100193 | |
| Download: ML20151P809 (7) | |
Text
'
cha 1 +f
- m*),,
UNITED STATES
[
j; NUCLEAR REGULATORY COMMISSION g
j WASHING TO N, D. C. 20555
%.... /
GEORGIA POWER COMPANY OGLETHORPE POWER CORPORATION MUNICIPAL ELECTIC AUTHORITY OF GEORGIA CITY OF DALTON, GEORGIA V0GTLE ELECTRIC GENERATING PLANT, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 7 License No. NPF-68 1.
The Nuclear Regulatory Commission (the Comission) has found that:
A.
The application for amendment to the Vogtle Electric Generating Plant, Unit 1 (the facility) Facility Operating License No. NPF-68 filed by the Georgia Power Company acting for itself, Oglethorpe Power Corpo-ration, Municipal Electric Authority of Georgia, and City of Dalton, Georgia, (the licensees) dated February 4, 1988, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, as amended, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be condJCted in compliance with the Comission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this license amendment will not be inimical to the comon defense and security or to the health and safety nf the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
8808100193 880802 PDR ADOCK 05000424 P
PDC Y
. 2.
Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachments to this license amendment and paragraph 2.C.(2) of Facility Operating License No. NPF-68 is hereby amended to read as follows:
(2) Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No.
7, and the Environmental Protection Plan contained in Appendix B, both of which are attached hereto, are hereby incorporated into this license. GPC shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
3.
This license amendment is effective as of its date of issuance and shall be implemented witain 30 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION ORIGINAL SIGNED BY:
David B. Matthews, Direc*or Project Directorate 11-3 Division of Reactor Projects
Attachment:
Technical Specification Changes Date of Issuance:
August 2, 1988 0FFICIAL RECORD COPY 3\\b LA:gQ(I-3 (JM:PDII-3 OGC-WF,
- P011-3 MRood J JHopkins:sw fylV LM DChatthews 7/Jl/88
/l 7 /p/88 7 /jg/88
{7/(/88
4 ATTACHMENT TO LICENSE AMENDMENT NO.
7-FACILITY OPERATillG LICENSE NO. NPF-68 DOCKET NO. 50-424 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by Amendment number and contain vertical lines indicating the areas of change. The corresponding overleaf pages are also provided to maintain document completeness.
Amended Page Overleaf Page 3/4 6-14 3/4 6-13 B 3/4 6-3 B 3/4 6-4 l
l e
i d
j CONTAINMENT SYSTEMS 3/4.6.2 OEPRESSURIZATION AND COOLING SYSTEMS CONTAINMENT SPRAY SYSTEM LIMITING CONDITION FOR OPERATION 3.6.2.1 Two independent Containment Spray Systems shall be OPERABLE with each Spray System capable of taking suction from the RWST and transferring suction to the containment emergency sump.
APPLICABILITY:
MODES 1, 2, 3, and 4.
ACTION:
With one Containment Spray System inoperable, restore the inoperable Spray System to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STAN0BY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; restore the inoperable Spray System to OPERABLE status within the next 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in COLD SHUTOOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
SURVEILLANCE REQUIREMENTS 4.6.2.1 Each Containment Spray System shall be demonstrated OPERABLE:
a.
At least once per 31 days by verifying that each valve (manual, power-operated, or automatic) in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position; b.
By verifying, that on recirculation flow, each pump develops a differential pressure of greater than or equal to 196 psid when tested pursuant to Specification 4.0.5; c.
At least once per 18 months during shutdown, by:
1)
Verifying that each automatic valve in the flow path actuates to its correct position on a containment spray actuation test signal, and 2)
Verifying that each spray pump starts automatically on a containment spray actuation test signal.
d.
At least once per 5 years by performing an air or smoke flow test through each spray header and verifying each spray nozzle is unobstructed.
V0GTLE - UNIT 1 3/4 6-13
. CONTAINMENT SYSTEMS SPRAY ADDITIVE SYSTEM LIMITING CONDITION FOR OPERATION 3.6.2.2 The Spray Additive System shall be OPERABLE with:
a.
A spray additive tank containing a volume of between 3700 (89.9%) and 4000 (97.2%) gallons (LI-0931A, LI-09318) of between 30 and 32% by weight NaOH solution, and b.
Two spray additive eductors each capable of adding Na0H solution from the spray additive tank to a Containment Spray System pump flow.
APPLICABILITY:
MODES 1, 2, 3, and 4.
ACTION:
With the Spray Additive System inoperable, restore the system to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; restore the Spray Additive System to OPERABLE status within the next 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in COLD SHUTOOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
SURVEILLANCE REQUIREMENTS 4.6.2.2 The Spray Additive System shall be demonstrated OPERABLE:
a.
At least once per 31 days by verifying that each valve (manual, power-operated, or automatic) in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position; b.
At least once per 6 months by:
1)
Verifying the contained solution volume in the tank, and 2)
Verifying the concentration of the NaOH solution by chemical
- analysis, c.
At least once per 18 months during shutdown, by verifying that each automatic valve in the flow path actuates to its correct position on a containment spray actuation test signal; and d.
At least once per 5 years by verifying each eductor suction flow rate (to be determined during preoperational tests) by isolating the spray additive tank, opening the valves in the miniflow lines, and the valve in the eductor test line, and running the respective pump:
1)
Train A 130 1 30 gpm, and 2)
Train B 120 t 30 gpm.
V0GTLE - UNIT 1 3/4 6-14 Amendment No. 7
.A
CONTAINMENT SYSTEMS BASES CONTAINMENT VENTILATION SYSTEM (Continued)
The use of the containment purge lines is restricted to the 14-inch purge supply and exhaust isolation valves since, unlike the 24-inch valves, the 14-inch valves are capable of closing during a LOCA or steam line break accident.
There-fore, the SITE BOUNCARY dose guideline of 10 CFR Part 100 would not be exceeded in the event of an accident during containment PURGING operation.
Only safety-related reasons; e.g., containment pressure control or the reduction of air-borne radioactivity to facilitate personnel access for surveillance and main-tenance activities, should be used to justify the opening of these isolation valves.
Leakage integrity tests with a maximum allowable leakage rate for containment purge supply and exhaust supply valves will provide early indication of resilient material seal degradation and will allow opportunity for repair before gross leak-age failures could develop.
The 0.60 L leakage limit of Specification 3.6.1.2b.
shallnotbeexceededwhentheleakagefatesdeterminedbytheleakageintegrity tests of these valves are added to the previously determined total for all valves and penetrations subject to Type B and C tests.
3/4.6.2 DEPRESSURIZATION AND COOLING SYSTEMS 3/4.6.2.1 CONTAINMENT SPRAY SYSTEM The OPERABILITY of the Containment Spray System ensures that containment depressurization and cooling capability will be available in the event of a LOCA or steam line break.
The pressure reduction and resultant lower containment leakage rate are consistent with the assumptions used in the safety analyses.
The Containment Spray System and the Containment Cooling System both provide post-accident cooling of the containment atmosphere.
However, the Containment Spray System also provides a mechanism for removing iodine from the containment atmosphere and therefore the time requirements for restoring an inoperable Spray System to OPERABLE status have been maintained consistent with that assigned other inoperable ESF equipment.
3/_4.6.2.2 SPRAY ADDITIVE SYSTEM The OPERABILITY of the Spray Additive System ensures that sufficient NaOH is added to the containment spray in the event of a LOCA.
The limits on NaOH volume and concentration ensure a pH value of between 8.5 and 10.5 for the solution recirculated within containment after a LOCA.
This pH band minimizes the evolution of iodine and minimizes the effect of chloride and caustic stress corrosion on mechanical systems and components.
The solution volume limits (3700-4000 gallons) represent the required solution to be delivered (i.e., the delivered solution volume is that volume above the tank discharge).
These assumptions are consistent with the iodine removal efficiency assumed in the safety analyses.
V0GTLE - UNIT 1 B 3/4 6-3 Amendment No.
7 i
)
CONTAINMENT SYSTEMS BASES 3/4.6.2.3 CONTAINMENT COOLING SYSTEM The OPERABILITY of the Containment Cooling System ensures that: (1) the containment air temperature will be maintained within limits during normal operation, and (2) adequate heat removal capacity is available when operated in conjunction with the Containment Spray Systems during post-LOCA conditions.
3/4.6.3 CONTAINMENT ISOLATION VALVES The OPERABILITY of the containment isolation valves ensures that the con-tainment atmosphere will be isolated from the outside environment in the event of a release of radioactive material to the containment atmosphere or pressuri-zation of the containment and is consistent with the requirements of General Design Criteria 54 through 57 of Appendix A to 10 CFR Part 50.
Containment isolation within the time limits specified for those isolation valves designed to close automatically ensures that the release of radioactive material to the environment will be consistent with the assumptions used in the analyses for a LOCA. A list of containment isolation valves is provided in Table 16.3-4 of the VEGP FSAR.
3/4.6.4 COMBUSTIBLE GAS CONTROL The OPERABILITY of the equipment and systems required for the detection and control of hydrogen gas ensures that this equipment will be available to maintain the hydrogen concentration within containment below its flammable limit during post-LOCA conditions.
Either recombiner unit is capable of con-trolling the expected hydrogen generation associated with: (1) zirconium-water reactions, (2) radiolytic decomposition of water, and (3) corrosion of metals within containment.
These Hydrogen Control Systems are consistent with the recommendations of Regulatory Guide 1.7, "Control of Combustible Gas Concen-trations in Containment Following a LOCA," Revision 2, November 1978.
The Hydrogen Mixing Systems are provided to ensure adequate mixing of the containment atmosphere following a LOCA.
This mixing action will prevent localized accumulations of hydrogen from exceeding the flammable limit.
V0GTLE - UNIT 1 B 3/4 6-4
-_