ML20151K145

From kanterella
Jump to navigation Jump to search
NPDES Noncompliance Notification:Effluent Discharge Data for June 1997 Indicated Biological Oxygen Demand for Five Days Value of 12.0 mg/1.Caused by Mixing W/Water in Ditch Sys
ML20151K145
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 07/31/1997
From:
FLORIDA POWER CORP.
To:
Shared Package
ML20151K138 List:
References
NUDOCS 9708050349
Download: ML20151K145 (1)


Text

..

.~

4

, U. 5. Nuclear Regulatory Commission 3F0797s13 Page 2 of 4 ADDENDUM 1 (to the June 1997 NPDES Monthly Discharge Report)

Crystal River Mariculture Center NPDES FL0000159/IT09-154804F i

The effluent discharge. data for June 1997 indicated a Biological Oxygen Demand for 5 days (BOD ) value of 12.0 mg/1.

The permit limit for B00 is 5.0 mg/1.

3 The background B00 was measured in the ditch prior to discharge. 3 The result of 3

this analysis was 9.4 mg/1.

A BOD sample collected from the tank being 3

discharged had a BOD value of 2.1 mg/1, well below the permit maximum, 3

i Therefore, it~is likely that the high BOD value was the result of mixing with 3

water in the ditch system and not characteristic of the effluent discharged from the Mariculture Center.

f i

i I

9708050349 970731 PDR ADOCK 05000302 S

PDR