ML20150C467

From kanterella
Jump to navigation Jump to search
Concurs W/Plans to Implement Administrative Controls Until Mod to Correct Design Anomaly Whereby MSIVs Would Open Upon Deenergization of Reactor Protection Sys Buses Complete. Detailed Info Re Proposed Change Requested within 120 Days
ML20150C467
Person / Time
Site: Perry 
Issue date: 03/13/1988
From: Colburn T
Office of Nuclear Reactor Regulation
To: Kaplin A
CLEVELAND ELECTRIC ILLUMINATING CO.
References
NUDOCS 8803180266
Download: ML20150C467 (2)


Text

March 13, 1988 Docket No. 50-440 DISTRIBUTION:

NEET7ffes7 NRC & Local PDRs

~PDIII-3 r/f KPerkins

~

Mr. Alvin Kaplin, Vice President GHolahan PKreutzer Nuclear Group TColburn 0GC-WF1 The Cleveland Electric Illuminating EJordan JPartlow Company ACRS(10)

PDIII-3 Gray Files 10 Center Road Pe*ry, Ohio 44081

Dear Mr. Kaplin:

SUBJECT:

MSIV LOGIC MODIFICATION PLANS We have received your February 12, 1988 letter on the subject item advising us of your plans to correct the design anomaly, discovered on January 23, 1988 whereby either the outboard or inboard MSIV's would open upon deenergization of Reactor Protection System (RPS) Bus A or B (respectively) if an isolation signal is not present.

We concur with your plans to implement administrative controls until the modifi-cetion is couplete to prevent future MSIV openings upon RPS bus deenergization.

We further find your proposed schedule for implementation of the design change during the first refueling outage to also be acceptable. However, in light of recent problems with the MISV's, including solenoid power supply wiring and those listed above, the staff has determined that our prior approval should be obtained prior to irnplementation of the proposed modification.

Therefore, within 120 days of your receipt of this letter, we request that you send us detailed design information related to the proposed change, including logic and wiring diagrams, electrical power schematics, and relay sequencing information. To the extent that staff previously approved designs may be in place at other facilities identical to changes proposed for your facility, it would be appropriate to reference the submittals and NRC approval related to the other facilities.

This request for information affects fewer than 10 respondents; therefore OMB clearance is not required under Pub. L.96-511.

Sincerely, a

C

/J Timothy G. Colburn, Project Manager Project Directorate III-3 Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation ec: See next page 7/aC SICB[i PD/PDdh3 Office:

LA/PQJ II-3 FH/PDIII-3 P rebt2er TColburn/tg SNewberry KPe Kins 0}3/q/88 Surname:

03/e/88 03/6/88 03/l5/88 Date:

i 8803180266 080313 PDR ADOCK 05000440 P

PDR

?

~

Mr. Alvin Kaplan Perry Nuclear Power Plant The Cleveland Electric Unit 1 Illuminating Company cc:

Shaw, Pittman, Potts & Trowbridge Mr. James W. Harris, Director 2300 N Street, N.W.

Division of Power Generation Washington, D.C.

20037 Ohio Department of Industrial Relations David E. Burke P.O. Box 825 The Cleveland Electric Columbus, Ohio 43216 Illuminating Company P.O. Box 5000 The Honorable Lawrence Logan Cleveland, Ohio 44101 Mayor, V111 age of Perry 4203 Harper Street Resident inspector's Office Perry, Ohio 44081 U.S. Nuclear Regulatory Comission Parmly at Center Road The Honorable Robert V. Orosz Perry, Ohio 44081 Mayor, Village of North Perry North Ferry Village Hall Regional Administrator, Region 111 4778 Lockwood Road U.S. Nuclear Regulatory Commission North Perry Village Chio 44081 799 Koosevelt Road Glen Ellyn, Illinois 60137 Attorney General Department of Attorney General Frank P. Weiss, Esq.

30 East Broad Street Assistant Prosecuting Attorney Columbus, Ohio 43216 105 Main Street Lake County Administration Center Radiological Health Program Painesville, Ohio 44077 Ohio Department of Health 1224 Kinnear Road Ms. Sue Hiatt Columbus, Ohio 43212 OCRE Interim Representative 8275 Munson Ohio Environmental Protection Mentor, Ohio 44060 Agency 361 East Broad Street Terry J. Lodge, Esq.

Columbus, Ohio 43266-0558 618 N. Michigan Street Suite 105 Mr. James R. Secor, Chairman Toledo, Ohio 43624 Perry Township Board of Trustees Box 65 John G. Cardinal Esq.

4171 Main Street Prosecuting Attorney Perry, Ohio 44081 Ashtabula County Courthouse Jefferson, Ohio 44047 State of Ohio Public Utilities Comission Eileen M. Buzzelli 180 East Broad Street The Cleveland Electric Columbus, Ohio 43266-0573 Illuminating Company P. O. Box 97 E-210 Mr. Murray R. Edelman Perry, Ohio 44081 Centerior Energy 6200 Oaktree Blvd.

Independence, Ohio 44131 L

- - -