ML20150B470

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept CP-86-40 Re Procurement and Use of Nonqualified Agastat Relays.Initially Reported on 861010. Vendor Designed Equipment Drawings Revised to Show Use of pre-qualified Relays.Other Corrective Actions Discussed
ML20150B470
Person / Time
Site: Comanche Peak  
Issue date: 03/11/1988
From: Counsil W
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CP-86-40, TXX-88252, NUDOCS 8803160449
Download: ML20150B470 (2)


Text

. _.

3 I

asummmmmmmes Lo

  1. TXX-88252 Fi e # 10110

=

r 903.11 1

1UELECTRIC March 11, 1988

$$',T,hS/,"$.,

V. S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, D.C.

20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 APPLICATION OF NON-QUALIFIED AGASTAT RELAYS SDAR:

CP-86-40 (FINAL REPORT)

Gentlemen:

On October 10, 1986, we notified you by our letter logged TXX-6017 of a deficiency involving the procurement and use of non-qualified Agastat relays in several Class 1E applications which we deemed reportable under the provisions of 10CFR50.55(e). Our most recent interim report was logged TXX-88242, dated February 19, 1988.

This final report is issued to status corrective actions taken to resolve this issue.

The following corrective actions have been completed:

1)

Vendor designed equipment drawings showing application of Agastat 7000 series timing relays have been reviewed and revised to show the use of pre-qualified ("E" prefixed) relays where necessary.

This will preclude repetition of the deficiency in future maintenance activities.

(Reference TXX-6017 dated October 10,1986)

+

2)

The Nuclear Operations Defective items List (N0DIL) has been updated to preclude future procurement of non "E" prefixed relays for use in IE applications.

Future purchases of these relays will remain segregated

("E" prefix from non "E" prefix).

(Reference TXX-6475 dated May 29, 1987, Corrective Actions 1 and 4) l l

l p>I I

O 8803160449 880311 PDR ADOCK 05000445 S

DCD 400 North Olive Street LBof Dallas. Texas 73.'01

.l

TXX-88252 March 11, 1988 Page 2 of 2 The remaining corrective actions involving removal of non "E" prefixed relays currently installed in IE applications, and segregation of "E" prefixed from non "E" prefixed relays currently in stores (Reference TXX-6475, Corrective Actions 2 and 3) will be completed for Unit I and Unit 2 prior to their respective fuel loads.

Very truly yoers Th W. G. Counsil WJH:clk c-Mr. R. D. Martin, Region IV Resident Inspectors, CPSES (3) 1 i