==g YANKEE A1MIC ELECTRIC COMPANY ~
DOCKET N0'. 50-29'~
=. _
~
YANKEE ATOMIC POWER' STATION (YANKEE-ROWE)
AMENDMENT *ID FACILITY OPERATING LICENSE p
fi Amendment No. 65
~
License No. DPR-3 1.
The Nuclear' Regulatory Comaiksion (the Commaission) has found that:-
A.
De application for amendment by Yankee Atomic Electric Company j
(the licensee) dated February 18, 1975, complies with the a
standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regula-tions set forth in 10 CFR Chapter I;
..:3
.......b
~
De facility will operate in conformity with the application, B.
the provisions of the Act, and the rules and regulations of '
the Commission;
=m
.l'.h C.
Dere is reasonable assurance (i) that the activities authorized 9
by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities
- ij will be conducted in compliance with the Commission's regula-tions; and 1.
9 D.
The issuance'of this amendment will not be inimical to the j.2 common defense and security or to the health and safety of r;
the public.
- j 2.
Accordingly, the license is amended by a change to the Technical Specifications as indicated in the attachment to this license a
amendment and Paragraph 3.A.(2) of Facility License No. DPR-3 is hereby amended to read as follows:
H orrice
- I SU.NAME>
DATE >
U UU'
=.
Forn ATC.)l0 (Rev. P 53) AECM 0240 W u. a. oOVERNMENT PRINTING OFFICE 31974 536 9 DG
,/
- =.==
rra
=:
[=
m.....
EiiE:. e' 2-
.=
"(2) Technical Specifications _
'dte Technical Specifications contained in Appendix A, as revised, are hereby incorporated in the license.
The licensee shall operate the facility in accordance.
..=====
with the Technical Specifications, as revised by issued' changes thereto through Change No. 288."
E l.
Iil 3.
Tnis license amendment is effective as of the date of its issuance.
POR THE NUCLEAR REGULATORY C0lef1SSION g
71
=
s\\tSb A. Giambusso, Director Division of Reactor Licensing Office of Nuclear Reactor Regulation
Attachment:
glg Change No. JEB to the Thehnical Specifications Date of IssuanceNAY Z 81975 e
e.
.'[<
k.
~
5 E...
?!!.
L::
- 0.
orric s 7 sunNA Me M
.7 D Ave >
ron. Arc.us <an, p.sn Ascu 024o
- u. 2.ovsnauswr enmvm. orrica i.u. u...
[..
I C=
(...
.==
- =
\\\\
ATTACHMENT TO LICENSE AbENDMENT NO. M
- ggg.g CHANGE NO. h TO THE TECHNICAL SPECIFICATIONS
~
FACILITY OPERATING LICENSE NO. DPR-18 E5 DOCKET NO. 50-29 Revise Appendix A as follows:
Add Section F, page 19.
!::i p=.
O a
g i
e e
- ly o
(-
I
=an'
'"*?? :
~
F.
ROD DROP TIME
' ??'
LIMITIMG CONDITION FOR OPEPATION
. 5?
- ":isii; The individual control rod drop times shall be < 2.50
=:
seconds from loss of stationary gripper coil voltage
.g.
~'
to 6 inch co n entry with:
a.
T
> 511 F and; avg -
e bi:
b.
all reactor coolant pump"s operating.
j;I.
r APPLICABILITY:
llot Standby.
- f..( :jjl=
l0).36 ACTION:
g.....,
a.
With the drop time of any rod determined to
!!E w exceed the above limit, restore the drop time to E
within the above limit prior to proceeding to ctartup or power operation.
b.
W1'th the rod drop times within limits but determined
- 3a with 3 reactor coolant purps operating, operation may proceed provided therr.a1 power is restricted to
. = =,
I Yl
< 75 percent of rated thermal power.
SURVEILL?.MCC F2QUIFr!ENTS.
i.;.
I The rod irop time of control rods shall be demonstrated through measurement prior to reactor criticality:
a.
for all rods following each renoval of the reactor vessel head; b.
for specifically affected individual rods following any maintenance on or modification to the rod drive F
system which could affect the drop time of those
[
specific rods, and;
[
c.
at Icast once per 18 rnonths.