ML20148H970

From kanterella
Jump to navigation Jump to search
Forwards IE Circular 78-18
ML20148H970
Person / Time
Site: Catawba, Perkins, Cherokee  
Issue date: 11/06/1978
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Dail L
DUKE POWER CO.
References
NUDOCS 7811150081
Download: ML20148H970 (1)


Text

_ - _ - _ - _ -

'TFS &

p**"CW UNITED ST ATES c

j NUCLEAR REGULATORY COMMISSION c

+

ch 1

REGION 11

,_. (

{'

o-

-j 101 M ARIETT A STRE E T, N Vv.

ATL ANTA. GEORGI A 30303

'+ ]' /

{

~

NOV 0 1978 In Reply Refer To:

%Q RII:JPO 9h 50-413, 50-414 50-488, 50-489 I

50-490, 50-491 50-492, 50-493 Q jl{

Duke Power Company Attn:

Mr. L. C. Dail, Vice President Design Engineering P. O. Box 2178 Charlotte, North Cecolina 28242 Gentlemen:

The enclosed :ircular 78-18 is forwarded to you for information.

So specific action is requested and no written response is required.

If you desire additional information regarding this matter, please contact this office.

Sincerely, 7

7

/

/;

/ames P. O'Reilly J

~ Director

Enclosures:

1.

IE Circular 78-18 2.

1.ist of 1E Circulars issued in 1978 cc w/ enc 1:

Mr. D. G. Beam, Project Manager Catawba Nuclear Station P. O. Box 223 Clover, South Carolina 27910 Mr. J. T. Moore, Project Manager Cherokee Nuclear Station P. O. Box 422 Gaffney, Fouth Carolina 29340

-7 81115 0 D l' S

sqf'.ob O03

UNITED STATES STCLEAR REGULATORY COFS!ISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D. C.

20555 November 6, 1978 IE Circular 78-18 UL FIRE TEST

Background

On. September 15, 1978, a fire test of a full-scale vertical cable tray array was conducted at.the Underwriters Laboratory (UL) near Chicage, Illinois.

It was part of the fire protection research program managed by Sandia Laboratories under NRC contract.

The purpose of the test was

.to demonstrate the effectiveness of area sprinklers and cable tray fire barriers. constructed of ceramic fiber blankets in preventing damage to cables as a result of an exposure to a flam=able liquid fire. The test resulted in damage to some electrical cables.

Discussion The configuration of the fire test wao selected to simulate a section of a plant area with vertical cable trays cent 'ning redundant safety divisions arranged such that the reduniin' visions could be simul-

.ag from an inadvertent spill taneously exposed to a potential fire of. flammable liquid in the area. The attungement of the cable trays and the_ designation of the redundant tray divisions is shown in Figure 1.

Figure 2 shows the location of the fire detectors and the three groups of sprinklers.

Each of the five cable trays contained cable insulated with polyvinyl chloride and was enclosed in a separated ceramic fiber blanket fire barrier from floor to ceiling in accordance with the canu-facturer's recommendations.

The sprinkler and detector arrangement was as permit t ed by NFPA Code.

However, no water was actually used at any time during this test due to the failure of some sprinkler heads te actuate, as explained below.

Each sprinkler' location in the test arrangement contained three nominallv

' identical temperature sensing sprinkler heads with fusible links adjacent to an open sprinkler nead which was connected to a manual water supp'v valve.

The temperature sensing heads were wired to signal when their links fused. -After all three temperature sensing heads at a given loca-tion activated, then the waterisupply for the open head was to be

~

manually admitted; 'The sprinklers were of.a type which actuate at the slew end of acceptance for reaction time.

The test procedure required that;all three temperature' sensing. heads.had.tc activate before water would be turned on.

In this way, it was expected to get some data on variability in the response time of identical sprinklers.

6 IE Circular 78-18 November 6, 1978 Test Details The test was started by igniting the two gallons of heptane that was poured into the floor pan.

A fully developed fire occurred almost immediately.

The ceiling smoke detector alarmed in about 15 seconds.

In about 50-60 seconds, two of the three temperature sensing sprinklers located between the wall and cable trays 1 and 2 activated.

The fire between cable trays 1, 2, 3, and 4 appeared most intense, apparently because of a chimney effect between the four trays. The flames between cable trays 3 and 5 did not appaar to be so intense. The ceramic fiber blanket absorbed some of the h;ptane so that after the heptane in the pan burned, most of the flame seemed to come from the bottom outside surface of the ceramic fiber blanket.

No additional temperature sensing sprinkler heads at any location activated; thus, the sprinkler water supply was not turned on for any of the three sprinkler locations.

The apparent slow response of the third temperature sensing sprinkler is being investigated, since this was not intended to be a slow response sprinkler.

At about 3 minutes into the test there was an in ati 1 of a short cv - ' fire. After circuit in cable tray 3, which was probably cause.

5-7 minutes the height of the flames appeared to.

at

however, residual flames continued for about 40 minutes.

Preliminary Results and Analyses Preliminary information indicates that the flac=able liquid or flames penetrated the protective barriers at the bottom of the vertical trays and caused fire damage to the polyvinyl chloride insulation on cables in four of the five trays.

On subsequent 500-volt megger test s, it was found that another cable in tray 2 had also experienced some damagt, as evidenced by a conductor te ground short.

probable cause of the fire damage in certain cable trays appears The most to be related to the absorption or aeepage of heptane under the ceramic fiber blanket at the juncture with the fleer. Once the heptane entered then ignitien apparently occurred the interior regions of the cable tray, the floor or through a vape r / air path wit hin via the amall opening at the joints. There is some indication that some cable damage was caused by absorption of heptane on the inaide of the barrier (wicking effect) and its ignition which heated a cable tray ladder rung, carring damage to a cable in contact with the rung. The ingress of the heptane into the ceramic fiber needs to be further evaluated since this appears te be the most significant failure mode.

November 6, 1978 IE Circular 78-18 Tentative Conclusions The test results are still being analyzed, and it would be premature to establish firm conclusions at this time; however, the results now available indicate that the following areas of the fire protection program need close consideration:

1.

To protect against spills of flammable liquids, barriers or curbs may be needed to prevent entry of the flammable liquid behind fire barriers. A wick effect may also need to be considered in the design of fire barriers.

2.

Some small fires may not actuate sprinkler heads.

To reduce this possibility in sprinkler systess to be installed, fast response sprinkler heads should be considered (less than approximately 3 minutes in the UL Standard 199 " Automatic Sprinklers for Fire Protection Service").

3.

The location of the fire detection devices and the sprinkler heads relative to the fire and components being protected is of great importance.

The path of the air movement in the area influences the actuation of such devices and should be considered in the system layout.

The final results of this test will be issued when the analysis of the test is complete.

This circular is being issued for information only.

No specific action is requested and no written response is required.

If you desire addi-tional information regarding this matter, contact the Director of the appropriate NRC Regional Office.

Attachments:

1.

Figure 1 2.

Figure 2

l t

IE Circular No. 78-18 November 6, 1978 LISTING OF IE CIRCULARS ISSUED IN 1978 l

Circular Subject Date Issued To No.

of Issue 78-01 Loss of Well Logging 4/5/78 All Holders of Source Well Logging Source Licenses 78-02 Proper Lubricating 011 4/20/78 All Holders of for Terry Turbines Reactor OLs or cps 78-03 Packaging Greater Than 5/12/78 All Holders of Type A Quantities of Reactor OLs, cps, Low Specific Activity Fuel Cycle, Radioactive Material Priority I Material for Transport and Waste Disposal Licenses 78-04 Installation Error That 5/15/78 All Holders of Could Prevent Closing of Reactor OLs or Fire Doors cps 78-05 Inadvertent Safety Injection 5/23/78 All Holders of During Cooldown Reacter Ots or cps 78-06 Potential Common Mode 5/23/78 All Holders of Flooding of ECCS Equipment Reactor OLs or Rooms at BWR Facilities cps 18-07 Damaged Components of a 5/31/78 All Helders of Bergen-Paterson Series Reactor Ots er 25000 Hydraulic Test cps Stand 78-08 Environmental Qualification 5/31/78 All Holders of React or OLs or of Safety Related Equipment at Nuclear Power Plants cps 78-09 Arcing of General Electric 6/5/78 All Holders of cps Company Size 2 Contactors Enclosure Page 1 of 2

IE Circular No. 78-18 November 6, 1978 LISTING OF IE CIRCULARS ISSUED IN 1978 Circular Subject Date of Issued to No.

Issue 78-30 Control of Sealed 6/14/78 All Medical Sources Used in Licensees in Radiation Therapy Categories G and G1 78-31 Recirculation M-G 6/15/78 All Holders of Set Overspeed Stops Bk'R OLs or cps 78-12 HPCI Turbine Control 6/30/78 All Holders of Valve Lift Rod Bending BWR OLs or cps for plants with HPCI Terry Turbine 78-13 Inoperability of Multiple 7/10/78 All Holders of Service Water Pumps Reactor OLs and cps except for plants located in: AL, AM, CA, I'L, GA, LA, MS, SC 78-14 HPCI Turbine Reversing 7/12/78 All Holders of Bb?

Chamber Hold Down Bolting OLs or cps for plants with a HPCI Terry Turbine excepting Duane Arnold and Monticelle 78-15 Checkvalves Fall to 7/20/78 All Holders of Close In Vertical Reactor OLs or cps Position 78-16 timitorque Valve 7/26/78 All Holders of Actuators Reactor Ots or cps 78-17 Inadequate Guard Training /

10/13/78 All Holders of Qualification and Falsified and applicants Training Reccrds for Reactor OLs.

Enclosure Page 2 of 2

Figure 1

~

Approximate boundary of pan for liquid spill fire

/

// / / / / / /1 1 / '/ f 1 / /1 f / / / / / I

^

\\

/

3'

/

13 "It-

/

/

[0. v i i

I Div 1 I at

\\Dk*

/

g D

i j

l Di 3

};T

' -3 9__ e v

/.

l

/

W

/

/

r l I Div 1 JI

~

')

s wit-d l an

._ i

/

l _ _._.

-s Yertical Tray corner Test

0 e

9 m

4

_Z e

8 e

9

.. Y.

\\

(

Yb k

N

. L*, -

_d_

o 9"T)

~

(

4 4l a

1

"*4 r-J 9

k W.'

s a

w S

1 W

N h

4 4

rw 1

w E

's

$.7, S

t *5-

~

< b-y 4,

de--4 JL 3 4 ~A M

s A

g3A Y^f h

  1. s a

3 s

,W1 btl j

+

q

___-_ _ _ _ _ - - _ _ _ - _