LOCAL PDR Docket No. ', 50-29 ORB #1 Reading ASchwencer Yankee Atomic Electric Company SMSheppard ATTH: Mr. Robert 11. Groce A8 urger Licensing Engineer DEisenhut 20 Turnpike Road JZwetzig Westboro,- Massac husetts 01581 OELD I&E(3)
Gentlemen:.
ACRS(16) i TBabernathy RE:
YAl*EE-ROWE ATOMIC POWER STATION JRBuchanan It has come to our attention that licensees with Westinghouse designed reactors have been advised by Westinghouse that the pressurizer limiting heatup rate of 200 F/ hour presently. stated in facility Tech-nical Specifications is in error and should be changed to 100 F/ hour.
Discussions with Westinghouse indicate that this corrected limit applies only to the heatup rate and that the present limit un cooldown rate of 200 F/ hour is acceptable.
In the event pu have not already done so, you are requested to submit within 60 days ef receipt of this letter a request for amendment of your i
. facility Technical Specifications to provide a limit of 100 F/ hour on the rate of pressurizer bestup.
Discussions with Westinghouse indicate that it is highly unlikely that the heatup rate of 100 F/ hour has been exceeded in the past. This is because system capabilities and Technical Specification limits on the rate of reactor coolant system heatup and pressurization effectively preclude pressurizer heatup rates in excess of 50 to 75 F/ hour.
llever-theless, you should examine your operating records and advise us of any instances where the pressurizer heatup rate exceeded 100 F/ hour. Provide the pertinent data for each such occurrence including the maximum rate, and the time interval during which the rate exceeded 100 F/ hour. The results of this survey, whether positive or negative, should be submitted to us with your request for a Technical Specification change or within 60 days of receipt of this letter, if a request for a change of Technical Specifications has already been submitted.
This <Jeneric request was approved by GAO, B-180225 (R0072), clearance expires July 31, 1980.. Approval was given under a blanket clearance spec'ifically for identified generic problems.
Sincerely.
THIS DOCUf.1ENT CONTAINS
[
POOR QUAUTY P3GES Mb
~
C& I t, n i e t
,+ v n ; n.
ac m ocer,
- g0R
.D 00R:0RB#1,
DORahg Operating.Rea< tors. ErAnch #1 o,m.
on fW erating ReacWs AB.Egeril E wetzig...
ASchwencej
.u a-See$1/hage
_.1/M/78 l/dD8 t
ee<
NRCJ,ORg8y6(NRg,t[i(,,,
n, W upomnusynnsum orrigag.- use 12180 M C M
[
L.;" ;. '
C)
(:)
in the Bran:h Technical Position on Fire Protection, the Reguletory Guide developed from that BTP, and any NRC letters on the subject of Fire Protection.
b.
Responsible for fire protection and prevention procedures developed by Yankee Rowe, Vermont Yankea and ' Maine Yankee.
j c.
Responsible for plant personnel and fire brigade training and manual fire fighting activities.
d.
Responsible for technical contact with NELPIA and review of recommendations.
3.
Design a.
Responsible for coordination of building layout and systems design with fire requirements.
b.
Responsible for coordination and review of design for fire deteccion; suppression and extinguishing systems.
c.
Responsible for techncal contact with NELPIA.
~
- = ~
i 4.
Construction a.
Review of fire prevention training and f.
activities duri*g the construction phase of a plant.
b.
Responsible for technical contact with NELPIA.
i e
s i
i 5
)
a isnkee Atomic tieuvric Company January 13, 1978 cc:
Mr. Donald G. Allen, President Yankee Atomic Electric Company 20 Turnpike Road llestboro, Massachusetts 01581 Greenfield Community College 1 College Drive Greenfield, Massacnusetts 01301 I