ML20148G310

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept CP-87-12 Re Containment Pressure/Temp Analysis Computer Error.Initially Reported on 870612.No Significant Deficiency Created by Increased Peak Temp Value. Issue Determined Not Reportable Per 10CFR50.55(e)
ML20148G310
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 01/18/1988
From: Counsil W
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CP-87-12, TXX-88120, NUDOCS 8801260465
Download: ML20148G310 (1)


Text

..

ammmmmmmme

==

r7 Log # TXX-88120 C

File # 10110

__.=

=

906.2

" # IU"" U'O

}

1UELECTRIC INm",Sd5,"$,

January 18, 1988 V. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C.

20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION DOCKET N05. 50-445 AND 50-446 CONTAINMENT P/T ANALYSIS COMPUTER ERROR SDAR: CP-87-12 (FINAL REPORT)

Gentlemen:

On June 12, 1987 we notified you via our letter logged TXX-6512 of a computer error in our containment pressure / temperature analysis which we conservatively deemed reportable based on the potential safety implications.

Our most recent interim report was logged TXX-7074, dated December 10, 1987.

After further evaluation, we have concluded this issue is not reportable under the provisions of 10CFR50.55(e).

The correction of the computer error resulted in an increase in peak containment temperature (following main steam line break) from our original value of 333 degrees F to 345 degrees F.

We have subsequently evaluated safety-related equipment inside containment and have determined that all safety-related equipment inside containment required to be qualified for this condition is qualified for the analyzed peak containment temperature of 345 degrees F.

Therefore, no significant deficiency was created by the increased peak temperature value and our earlier determination that this issue was reportable was based on preliminary information.

Supporting documentation is available onsite for your inspector's review.

Very truly yours, df(M W. G. Counsil JCH/grr c-Mr. R. D. Martin, Region IV Resident Inspectors CPSES (3) 9 8801260465 880118 PDR ADOCK 05000445 S

DCD g

400 North Oltw Strees LB81 Dal s Tenas 73.'01