ENCLOSTJRE '
y-DESCRIPTION OF VIOLATIO"S y
=a-
.. iii3, IJuclear.Fue Services, Incorporar.ed
==
West Valley, New York Doeket No.o50 201-
. Certain activities. under your license appear to be in noncompliance with I.:.:.,,j
..,g-g.
AEC license -requirc=ents, as indicated below:
3.
nc; 1.
Technical Specification 4.13.3 requires that solid radioactive
-[
vaste to'bc buried shall be placed in packages which shall pre-
- m;
. vent dispersion of contents and prevent contamination of handlers.
?
. c.7:
for i Contrary to the above, grossly contnminated cement blocks.sent burial which had been formerly used in an acid.r2covery cell, vere
&#a The pr.;;g.
packaged ~ only.Lin plastic which had torn prior to transf et.
. transfer'on July 26, 1972 resulted in one handler being contamina-
.;;g ted borh.on his' clothing and person.
g.
7,
'2.
Technical' Specification 5.1.l requires that all batches of liquid.
E
~
previourly in contact with procuss equipment be analyzed for radio-activity prior to disposal to unrestricted. areas.
g 1
Co'ntrary to the above, the water siphoned frcm the filter media s.,,
and released te the ground on June 15 and 16,1972 was not anal-5..
.yzed for radin ctivity prior to release.
~
3.
Technical Specitication 7.1.2 requires that procedures be main-
[
tained 'under the overall direction of the general canager cover-
- J ing standard operating procedures, letters of authorization, run-f.'
sheets, special work procedures, and-extended work procedurts.
' [{ i,y
~
where nuclear critfeelity or radiatio'n safety are considerations.
Paragraph S.2.5.4 of the 11ealth and Saf ety procedurer requires h' 5 ite=s'being transferred for burial be surveyed both for radiation levels and renovable conterination.
g,
.1 l
Contrary to the above, ce=ent blocks removed frca an acid recovery m
sys ter, on June 26, 1972 v.Me not surveyed for removable contamina-tion' prior to transfer for burial.