Amend 125 to License NPF-15 Revising SRs 3.8.1.14 & 3.8.1.15 to Temporarily Restore Provisions of EDG SR as Prior to Rev as Part of Amend 116
ML20147E259
Person / Time
Site: San Onofre 
(NPF-15-A-125)
Issue date: 02/10/1997
From: Fields M
NRC (Affiliation Not Assigned)
To:
Shared Package
ML20147E264 List:
References
NUDOCS 9702180254
Download: ML20147E259 (5)


Text

.

A cezu 3

UNITED STATES l

g

,g NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 30866-0001 l

n SOUTHERN CALIFORNIA EDIS0N COMPANY SAN DIEGO GAS AND ELECTRIC COMPANY j

THE CITY OF RIVERSIDE. CALIFORNIA THE CITY OF ANAHEIM. CALIFORNIA DOCKET NO, 50-362 SAN _ONOFRE NUCLEAR GENERATING STATION. UNIT NO. 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 125 License No. NPF-15 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Southern California Edison Company, et al. (SCE or the licensee) dated January 14, 1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's regulations set forth in 10 CFR Chapter I; i

B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and i

E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

1 9702180254 970210 PDR ADOCK 05000362 l

p PDR

- 2.

Accordingly, the license is amended by changes to the Technical Speci-fications as indicated in the attachment to this license amendment, and paragraph 2.C(2) of Facility Operating License No. NPF-15 is hereby amended to read as follows:

(2)

Technical Soecifications The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, as revised through Amendment No. 125, are hereby incorporated in the license. Southern California Edison Company shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION fjd Mel B. Fields, Project Manager Project Directorate IV-2 Division of Reactor Projects III/IV Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance:

February 10, 1997 4

1 r

m

ATTACHMENT TO LICENSF AMENDMENT AMENDMENT NO.125 TO FACILITY OPERATING LICENSE NO. NPF-15 DOCKET NO. 50-362 j

Revise Appendix A Technical Specifications by removing the pages identified below and inserting the enclosed pages.

The revised pages are identified by Amendment number and contain marginal lines indicating the areas of change.

l REMOVE INSERT 3.8-11 3.6-11 3.8-11a i

I i

1 l

l

AC Sources--Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.149


NOTES-----------------

l 1.

Momentary transients outside the load and power factor ranges do not invalidate this test.

2.

Credit may be taken for unplanned events that satisfy this SR.

Verify each DG, when operating with the 24 months maximum kVAR loading permitted during testing, operates for 2 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />s:

a.

For 2 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded 2 4935 kW and 5 5170 kW; and b.

For the remaining hours of the test loaded 2 4450 kW and s 4700 kW.

1 SR 3.8.1.15#


NOTES-----------------

l 1.

This Surveillance shall be performed i

within 5 minutes of shutting down the DG after the DG has operated 2 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded 2 4450 kW and s 4700 kW.

Momentary transients outside of load range do not invalidate this test.

2.

All DG starts may be preceded by an engine prelube period.

Verify each DG starts and achieves, in 24 months s 10 seconds, voltage 2 3924 V and s 4796 V, and frequency 2 58.8 Hz and s 61.2 Hz; and operates 2 5 minutes.

(continued)

SAN ONOFRE--UNIT 3 3.8-11 Amendment No. ++6,125

j i

J AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued) i 9

This SR is not applicable until the next test scheduled to occur during the Unit 3 Cycle 9 refueling outage.

Until that time the following SR I

is applicable:

Verify the diesel generator operates for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. During the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this test, the diesel generator shall be loaded 'to j

greater than or equal to 5170 kw and during the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this test, the diesel generator shall be loaded to greater than or equal to 4700 kw.

The generator voltage and frequency shall be 4360 i 436 volts and 60 i 1.2 Hz after the start

  • signal; the steady state generator witage and frequency shall be maintained at 43601436 volts and 60 + 1.2 / -0.3 Hz for the first 2 hcurs of this test and 4360 t 436 volts and 60 i 1.2 Hz during the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this test.

l

  • The engine start for the purpose of this surveillance test may be preceded by an engine prelube period and/or other warmup procedures recommended by the manufacturer so that mechanical stress and wear on the engine is minimized.

This SR is not applicable until the next test scheduled to occur during the Unit 3 Cycle 9 Refueling Outage.

Until that time the following SR is applicable:

Within 5 minutes after conipleting the 24-hour test, simulate a loss of offsite power by itself, and verify the diesel starts on the auto-start signal, energizes the emergency busses with permanently connected loads within 10 seconds and operates for greater than or equal to 5 minutes i

while its generator is loaded with the permanently connected loads.

After energization, the steady state voltage and frequency of the emergency busses shall be maintained at 4360 i 436 volts and 60 i 1.2 Hz during this test.

SAN ONOFRE--UNIT 3 3.8-11a Amendment No.125 4

..