ML20141N933
| ML20141N933 | |
| Person / Time | |
|---|---|
| Site: | Dresden |
| Issue date: | 02/28/1986 |
| From: | Maxwell D, Scott D COMMONWEALTH EDISON CO. |
| To: | NRC OFFICE OF ADMINISTRATION (ADM), NRC OFFICE OF INSPECTION & ENFORCEMENT (IE) |
| References | |
| 86-180, NUDOCS 8603180291 | |
| Download: ML20141N933 (33) | |
Text
. _.
OPERATING DATA REPORT i
g DOCKET NO. 050-237 DATE March 1, 1986 COMPLETED BY D. C. Maxwell TELEPHONE 815/942-2920 OPERATING STATUS NOTES 1.
Unit Name:
Dresden II 2.
Reporting Period:
February, 1986 3.
Licensed Thermal Power (MWt):
2 527 4.
Nameplate Rating (Gross MWe):
828 5.
Design Electrical Rating (Net MWe):
794 6.
Maximum Dependable Capacity (Gross MWe):
812 7.
Maximum Dependable Capacity (Net MWe):
772 8.
If Changes Occur in Capacity Ratings (items 3 Through 7) Since Last Report, Give Reasons:
N/A 9.
Power Level to Which Restricted, if Any (Net MWe): N/A 10.
Reasons For Restrictions, if Any:
N/A
' ). M.
This Month Yr-to-Date Cumulative II.
Hours in Reporting Period 672 1,416 138.480 12.
Number of Hours Reactor Was Critical 620.3 1,323.2 105.020.7 13.
Reactor Reserve Shutdown Hours 0
0 0
14.
Hours Generator On-Line 555.2 1,123.2 100.107.7 15.
Unit Reserve Shutdown Hours 0
0 0
~
16.
Gross Thermal Energy Generated (MWH) 1,234,874 2,584,205 204,217,844 17.
Gross Electrical Energy Generated (MWH) 402,699 842,418 65,342,181 18.
Net Electrical Energy Generated.(MWH) 383,663 802,260 61,738,374 19 Unit Service Factor 82.6 79.3 72.3 20.
Unit Availability Factor 82.6 79.3 72.3 21.
Unit Capacity Factor (Using MDC Net) 74.0 73.4 57.7 22.
Unit Capacity Factor (Using DER Net) 71.9 71.4 56.1 23.
Unit Forced Outage Rate 17.4 20.7 12.4
'24.
Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
Mid-May for a weekend snubber inspection.
25.
If Shut Down At End Of Report Period, Estimated Date of Startup:
N/A 86031802'f1 86022ts PDR ADOCK 05000237 l
R PDR l
N"p.k 0,
' OPERATING DATA REPORT
~
- DOCKET NO. 050-249 DATE March 1, 1986 4
i COMPLETED BY D. C. Manell TELEPHONE 815/942-2920 OPERATING STATUS' NOTES 1.
Unit Name: Dresden III l'
2.
Reporting Period:
February. 1986 3
Licensed Thermal Power (MWt):
2.527
'4. -Nameplate Rating (Gross MWe):
ann
~5 Design Electrical Rating-(Net MWe): 794 6.
Maximum Dependable Capacity (Gross MWe): R12 7
Maximum Dependable Capacity (Net NWe):
773 8.
If Changes occur in Capacity Ratings (ltems 3 Through 7) Since Last Report, Give Reasons:
N/A 9.
Power Level to Which Restricted, if Any (Net MWe): N/A 10.
Reasons For Restrictions, if Any: N/A 1
This Month Yr-to-Date Cumulative.
11.
Hours in Reporting Period 672 1,416 128,065
- 12. ; Number of Hours Reactor Was Critical 0
0 96.596.7 13.
Reactor Reserve Shutdown Hours 0
0 0
14.
Hours Generator On-Line 0
0 89.793.3 15.
Unit P.eserve Shutdown Hours 0
0 0
16.
Gross Thermal Energy Generated (MWH) 0 0
181.772.636 17.
Gross Electrical Energy Generated (MWH) 0 0
58.839.233 4
18.
Net Electrical Energy Generated.(MWH)
-4,205
-9,934 55.716.360 19.
Unit Service Factor-0 0
70.1 2'.
Unit Availability Factor 0
0 70.1 0
- 21. Unit Capacity Factor (Using MDC Net) 0 0
56.3 22.
Unit Capacity Factor (Using DER Net) 0 0
54.8
.i 23.
Unit Forced Outage Rate.
0 0
12.4 24.
Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
l' In 9th Refueling /RPR outage.
I 25.
If Shut Down At End Of Report Period, Estimated Date of Startup:
June, 1986 i
l f
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 050-237 VillT II DATE March 1, 1986 COMPLETED BY D. C. Maxwell TELEPHONE 815/942-2920 MONTH February, 1986 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (HWe-Net)
(MWe-Net) l 772 17 780 2
688 18 793 770 19 786 3
4 75 20 758 5
0
'21 771 6
0 22 787 7
0 23 720 8
'0 24 791 l
9 367 25 784 10 500 26 776 II 338 27 783 i
12 361 28 728 13 674 29 14 774 l
30 15 814 31 16-687 I
1
_..~.,
m-AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 050-249 UtilT III DATC March 1, 1986 COMPLETED BY D. C. Maxwell TELEPHONE 815/942-2920 MONTH February, 1986 DAY-AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Net) 1 0
17 0
2 0
18 0
3 0
19 0
4 0
20 0
5 0
21 0
6 0
22 0
7 0
23 0
8 0
24 0
9 0
25 0
10 0
26 0
11 0
0 27 12 0
28 0
O 13 29 14 0
~~
30 0
15 31
~~
0 16
t
_y i
COMMONWEALTH EDISON COMPANY DRESDEN STATION MAXIMUM DAILY LOAD MONTH OF February, 1986 f
HOUR MAXIMUM DAILY LOAD
. DAY.
'ENDING KW 1
2400 800,000 2
2400 785,600 3
1200 820,600 4
0100 699,200 0
5 0
6 0
7 0
8 9
0800 502.700 10 2400 622,200 11 0100 631,600 12 2400 576,200
-13 2400 781,700 14 1300 820,600 l
15 0800 819,300 16 0100 780,300 17 1300 826,700 18 1600 839,200 19 0100 832,600 20 2200 816,200 21 2200-825,700-22 1600 826.700 23 2300' 814,100 I.
'24 1400 825,000 i
25 2200 821,000 f
26 0100 821,000 f
27 1400 826,100 h
28 0200 821,200 29 30 3g-v
r-1 e
o DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 I.ER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION L2 Emergency Corrective W.R. #35899 N/A Replaced intake air hose.
Di:sel. EPN
- 2-6601 U2 El ctromatics Preventive W.R. #36442 N/A Rebuilt electromatics, installed new 2-203-B-C-D-E operation coils, switches and springs.
U2 Pr tective Preventive W.R. #38044 N/A Calibrated and checked protective Rel':ya relays.
Rx Building Vent Preventive W.R. #38961 N/A Performed routine surveillance DIS 1700-7.
Excharger Monitor No problem found.
"B", 2-1705-8B U2 Channel B Rx Preventive W.R. #39137 N/A Performed DIS 500-1.
No problem found.
Scram CRD J-10 HCU Preventive W.R. #39575 N/A Checked and calibrated per DIS 300-2.
2-305-130 Valve U2 MOV 220-1 Preventive W.R. f42102 N/A Inspected for E Q.
U2 MOV 3706 Preventive W.R. f42103 N/A Inspected for E.Q.
U2 MOV 202-7B Preventive W.R. #42121 N/A Inspected for E.Q.
U2 Elsctromatic Preventive W.R. #42170 N/A Inspected for E.Q.
203-3B U2 El ctromatic Preventive W.R. #42171 N/A Inspected for E.Q.
203-3C U2 El;ctromatic Preventive W.R. #42172 N/A Inspected for E.Q.
203-3D U2 Elcctromatic Preventive W.R. #42173 N/A Inspected for E.Q.
203-3E
e.
o DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U2 T rget Rock Preventive W.R. #42178 N/A Inspected for E.Q.
203-3A U2 Cora Spray Preventive W.R. #42182 N/A Inspected for E.Q.
Pump 1401B U2 LPCI Pump Preventive W.R. #42184 N/A Inspected for E.Q., drilled weep hole 1502D in bottom of motor main power conduit box.
U2 LPCI Pump Preventive W.R. f42185 N/A Inspected for E.Q., drilled weep hole, 1502C made new gasket for lead box cover on motor.
U2 MOV 202-5A Corrective W.R. #43579 N/A Corrected E.Q. deficiencies, added grease, replaced internal wiring and put in new torque limiter plate.
U2 MOV 1301-2 Corrective W.R. #43589 N/A Corrected E.Q. deficiencies, replaced grease, wiring and spliced motor leads.
U2 MOV 1402-24B Corrective W.R. #43592 N/A Corrected E.Q. deficiencies, replaced grease, wiring, spliced motor leads and replaced torque limiter plate.
U2 MOV 1402-25B Corrective W.R. f43596 N/A Corrected E.Q. deficiencies, replaced grease, wiring, spliced motor lead connections and replaced missing torque limiter plate.
U2 MOV 1402-38B Corrective W.R. f43598 N/A Corrected E.Q. deficiencies, replaced grease, wiring, spliced motor lead con-nections and replaced torque limiter plate.
U2 MOV 1501-11B Corrective W.R. #43601 N/A Corrected E.Q. deficiencies, replaced grease, wiring and spliced motor lead connections.
o O
G DRESDEN UNIT 2 SAF5:TY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U2 MOV 1501-32B Corrective W.R. #43609 N/A Corrected E.Q. deficiencies, replaced grease, wiring and spliced motor lead connections.
U2 MOV 2301-8 Corrective W.R. f43611 N/A Corrected E.Q. deficiencies, replaced grease, wiring and spliced motor lead connections.LPRM 16-25C, Preventive W.R. f43871 N/A Reset scale trip.
2-705-002 U2 MOV 1301-4 Corrective W.R. f44028 N/A Replaced rewound motor with new motor from limitorque.LPRM 24-41C, Preventive W.R. f44312 N/A Checked using DIP 700-13 and DIP 700-15.
2-705-002 No problem found.
Containment Atmos-Corrective W.R. f44911 N/A Replaced variable resistors ar work phera Pressure package.
Alrrm Cards 2/3-2540-18A and 19A LPRM IC 16-49, Preventive W.R. #44935 N/A Replaced power supply and fuses.
2-705-002 U2 ID-2D MSIV Preventive W.R. f45482 N/A Adjusted and aligned limit switch.
MO-2-2301-4 Preventive W.R. f45518 N/A Adjusted torque switch.
T;rque Switch MO-2-3706 Torque Preventive W.R. f45520 N/A Adjusted torque switch.
Switch U2 Barton DPIS Corrective W.R. #45666 N/A Replaced DPIS 2-1350B.
1350B
o DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPPENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION MSL Rad Monitor Preventive W.R. #45994 N/A Checked monitor using DIS 1700-1. No i
2-1705-2D problem found.
U2 Containment Corrective W.R. #45791 N/A Replaced defective H2 cell.
Air Monitor H 2 Sensor 2-2402-A U2 Refuel Grapple Preventive W.R. f46913 N/A Put limits back in place, removed cards, signed off jumper log.
LPCI/ Core Spray Corrective W.R. f47127 N/A Replaced thermostat.
Room Cooler 2-5746A LPCI/C;re Spray Corrective W.R. f47128 N/A Replaced thermostat.
Room Cooler 2-5746B LPRM 40-33-B Preventive W.R. f47228 N/A Checked LPRM using procedure. No problem found.
U2 Torus Tempera-Preventive W.R. f47238 N/A Performed E.Q. inspection.
tura Monitor U2 El ctrical Preventive W.R. f47239 N/A Performed E.Q. inspection.
P:netrction - 595 Rx Building U2 Elcctrical Preventive W.R. f47240 N/A Performed E.Q. inspection.
P netration - D/W 545 2A Recirculation Preventive W.R. f47241 N/A Performed E.Q. inspection.
Pump Discharge MO-2-202-5A
o DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION D/W Spray Valve Preventive W.R. #47242 N/A Performed E.Q. inspection.
MO-2-1501-27A 2B Recirculation Preventive W.R. f47243 N/A Performed E.Q. inspection.
Pump Discharge MO-2-202-5B LPCI Suction Preventive W.R. #47244 N/A Performed E.Q. inspection.
V1va MO-2-1501-SC U2 Cora Spray Preventive W.R. f47245 N/A Performed E.Q. inspection.
Pump Cable -
1402B HPCI Turbine Preventive W.R. #47247 N/A Performed E.Q. inspection.
Inlet Valve MO-2-2301-4 MSIV X-Area Preventive W.R. f47248 N/A Performed E.Q. inspection.
S02-203-2D MSIV X-Area Preventive W.R. f47249 N/A Performed E.Q. inspection.
S02-203-2C MSIV X-Area S02-Preventive W.R.
- 47250 N/A Performed E.Q. inspection.
203-2J MSIV X-Area SO2-Preventive W.R. #47251 N/A Performed E.Q. inspection.
203-2A U2 "C" LPCI Pump Preventive W.R. #47252 N/A Performed maintenance on breaker -
Br:1ksr 24-1-CUB E.Q. requirement.
2425
(
o DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U2 "A" Core Spray Preventive W.R. f47253 N/A Performed maintenance on breaker - E.Q.
Pump Breaker, Bus requirement.
23-1 CUB 2330 U2 "B" Core Spray Preventive W.R. f47254 N/A Performed maintenance on breaker - E.Q.
Pump Breaker, Bus requirement.
74-1 CUB 2429 U2 Air Line Corrective W.R. f47406 N/A Removed, applied sealant and reinstalled.
Lubric~ tor to Air St'_.rt Motors
- 2 Dinsel Genera-Preventive W.R. f47592 N/A Performed one and three month surveil-t:.r 2-6601 lance inspection as procedure.
U2 "D" LPCI Pump Preventive W.R. f47600 N/A Performed E.Q. inspection.
Br,:.k ;r 24-1 CUB 2427 U2 Bottom "B" Preventive W.R. f47722 N/A Charged cell to bring up to specifica-24/48 VDC Battery tions.
Cell #12, 3rd Floor Turbine Bldg. Battery Rs.
U2 TE2-1641-207 Preventive W.R. f47884 N/A Inspected for E.Q.
U2 TE2-1641-206 Preventive W.R. f47885 N/A Inspected for E.Q.
U2 TE2-1641-204 Preventive W.R. #47887 N/A Inspected for E.Q.
U2 TE2-1641-203 Preventive W.R. f47888 N/A Inspected for E.Q.
U2 TE2-1641-202 Preventive W.R. f47889 N/A Inspected for E.Q.
U2 TE2-1641-201 Preventive W.R. f47890 N/A Inspected for E.Q.
DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OLTTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTE14ANCE NUMBER CAUSE RESULT -
CORRECTIVE ACTION U2 TE2-1641-200 Preventive W.R. f47891 N/A Inspected for E.Q.
U2 Electrical Preventive W.R. f47894 N/A Replaced splices.
Penetretion
.X-205E U2 Elcctrical Preventive W.R. f47895 N/A Repaired and replaced splices.
Penetrction X-2008 U2 Elsetrical Preventive W.R. #47896 N/A Replaced splices.-
Penetretion X-204S U2 Drywell Equip-Preventive W.R. f47898 N/A Opened equipment hatch, meet Hatch U2 Drywell Equip-Preventive W.R. f47905 N/A Closed equipment hatch.
mest Hatch D2 East Bank Preventive W.R. f47908 N/A Installed new flanges and gaskets.
' 2-0388/2-0387 lU22-1001-1B Preventive W.R. #47919 N/A Cleaned limit stack contacts.
, Valva l
U2 Lifted Leads Preventive W.R. f47930 N/A Lifted black lead of cable; caution fer P2netration carded.
X-2045 Control Room U2 MOV 202-?B Preventive W.R. f47947 N/A Replaced grease.
U2 MOV 220-1 Preventive W.R. f48012 N/A Replaced sealtite, defective wire and splice - E.Q. requirement.
t
f
~
~.h O
o DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NL'MBER CAUSE RESULT CORRECTIVE ACTION U2 Electromatic Preventive W.R. #48014 N/A Replaced wiring and sealtite - E.Q.
203-3B requirement.
l U2 Electromatic Preventive W.R. f48015 N/A Replaced wiring and sealtite - E.Q.
203-3C requirement.
U2 "lectromatic Preventive W.R. #48016 N/A Replaced wiring and sealtite - E.Q.
203-3B requirement.
U2 Elcctromatic Preventive W.R. f48017 N/A Replaced wiring and sealtite - E.Q.
203-3E requirement.
U2 1C MSIV, Corrective W.R. f48026 N/A Installed new seal in top and bottom 2-203-lC of oil cylinder.
U2 Dicsel Genera-Corrective W.R. #48067 N/A Tightened coupling.
tcr Soak Back Oil Pump U2 1201-1A Preventive W.R. #48110 N/A Replaced grease.
U2 "B" Bottom Corrective W.R. #48144 N/A Replaced timer.
Chargcr Timer U2 Elcetrical Preventive W.R. #48154 N/A Performed E.Q. inspection.
Penetrrtion X 205E U2 LPRM 32-57C Preventive W.R. #48155 N/A Checked per procedure.
U2 LPRM 32-17C Preventive W.R. f48156 N/A Checked per procedure.
U2 New 125V Preventive W.R. f48158 N/A Charged batteries.
Battcry Cells
e DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Rx ' Idg. Fuel Corrective W.R. f48167 N/A Repaired broken connector wire in Pool Floor Chan-
"A" channel; recalibrated "A" and "B" nel "A" and "B",
per procedure.
U2 U2 MOV 2-2301-5 Preventive W.R. #48176 N/A Rebuilt limitorque operator.
U2 MOV 2-2301-8 Preventive W.R. f48177 N/A Rebuilt limitorque operator.
U2 MOV 2-202-5B Preventive W.R. #48178 N/A Rebuilt limitorque operator.
U2 MOV 2-202-5A Preventive W.R. #48179 N/A Rebuilt limitorque operator.
U2 Dinsel Genera-Preventive W.R. #48185 N/A Crimps on terminators from RACR c r #2 inspected - none found loose.
U2 2B Core Spray Corrective W.R. f48187 N/A Replaced relay and tripped check.
Pump Relay U2 2A Core Spray Preventive W.R. #48196 N/A Taped up switchgear and motor connec-Pump 2-1401-A tions - E.Q. requirement.
U2 2B Core Spray Preventive W.R. #48197 N/A Retaped at breaker and motor - E.Q.
Pump 2-1401-B requirement.
U2 2A LPCI Pump Preventive W.R. #48198 N/A Retaped at breaker and motor - E.Q.
2-1502-A requirement.
U2 2B LPCI Pump Preventive W.R. #48199 N/A Taped up switchgear and motor leads -
2-1502-B E.Q. requirement.
U2 2C LPCI Pump Preventive W.R. f48200 N/A Taped at motor and bus connections -
2-1502-C E.Q. requirement.
U2 2 Dicsel Preventive W.R. #48202 N/A Taped U2 diesel generator - E.Q.
Generct r requirement.
.9 DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - FEBRUARY,1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT
-CORRECTIVE ACTION U2 Transformer 28
~ Preventive W.R. #48204 N/A Taped at bus connections.- E.Q.
requirement.
i
- U2 Tracsformer 29 Preventive W.R. #48205 N/A Taped at bus connections - E.Q.
requ,irement.
U2 Bus Tie 23-Preventive W.R. f48206 N/A Taped at bus connections - E.Q.
23-1 requirement.
U2 Bus Tie 24 Preventive W.R. f48208 N/A Taped at bus connections - E.Q.
34-1 requirement.
Corrective W.R. #48245 N/A Installed new pump.
Drywell H2 and 02 Monit: ring System
, HM-2-2402B 1
U2 LPRM 08-33B, Preventive W.R. #48253 N/A Checked per procedure.
I APRM #5,08-33B l U2 Wide Range Corrective W.R. #48256 N/A Recalibrated per procedure - changed l T:rus Level "A" cover o-rings.
LT 1641 SA lU2WideRange Corrective W.R. #48257' N/A Recalibrated per procedure - changed l T:rus Level "B" cover gaskets.
l LT 1641 SB ll U2 2B LPCI Pump Preventive W.R. f48276 N/A Tightened connections, tested breaker l Crack 2r(24-1) per procedure.
l lU2IsolationCon-Preventive W.R. f48292 N/A Replaced reset button.
denser Valve Brerkar Valve 2-1301-1
O DRESDEN UNIT 2
~
SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U2 Medium Range Corrective W.R. f48311 N/A Corrected calibration error per proce-Drywell Pressure dure.
Receivnr 2-8540-2/4 U2 2B LPCI Pump Corrective W.R. #48316 N/A Replaced racking screw receptacle.
Bracker Cubicle U2 Bus 28 and 29 Corrective W.R. f48332 N/A Installed / removed jumpers.
U2 T:rus Thermo-Preventive W.R. f48375 N/A Drilled weep hole in bottom of junction couplo Junction box.
Boxen 2RB-207 to 222 U2 FCI Level Preventive W.R. f48396 N/A Completed slow fill FCI level switch Switch Response, response curves.
LS 2-302-82G, 82H, 82A, 82B U2 MOV 2-1301-4 Preventive W.R. #48180 N/A Rebuilt limitorque operarar.
U2 MOV 2-1301-1 Preventive W.R. #48239 N/A Rebuilt limitorque operator.
U2 MOV 2-1001-1B Preventive W.R. #48240 N/A Rebuilt limitorque operator.
U2 MOV 2-220-2 Preventive W.R. #48234 N/A Rebuilt limitorque operator.
U2 MOV 2-1001-1A Preventive W.R. f48241 N/A Rebuilt limitorque operator.
U2 1A MSIV Corrective W.R. #48294 N/A Rebuilt valve, int:5:ct-l block.
l U2 2A SBLC Pump Corrective W.R. f48435 N/A Installed new packing.
2A-Il02 I
i
1 r,
DRESDEN UNIT 2
~
SAFETY REI.ATED MAINTENANCE - FEBRUARY, 1986
~
LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U2 Replaced LS Corrective W.R. f48443 N/A Installed new FCI level switch, 2-302-82B completed " slow fill" response per procedure.
U2 Rx Head Seal Preventive W.R. f48461 N/A Adjusted limit switches.
V lve 2-220-52 12 MSIV 2-203-2A Corrective W.R. f48470 N/A Added packing.
U2 DWEDS Valve Preventive W.R. f48476 N/A Cleaned and lubed contrcl switch.
Contrni Switch 2001-3 and 2001-4 U2 1A MSIV Corrective W.R. f48478 N/A Repaired pilot valves and air operators.
U2 D2 MSIV ID Preventive W.R. f48480 N/A Adjusted packing.
2-203-1-D U2 MOV 1301-1 Preventive W.R. f48482 N/A Checked rotation, set limits and strip chart.
U2 A0 220-44 Corrective W.R. f48484 N/A Changed wiring to different contact.
U2 Scram Dis-Preventive W.R. #48497 N/A Tightened bolts.
charg7 Volume Flmg7 U2 MJV 2301-8 Preventive W.R. #48513 N/A Reset closed limit switch.
U2 MOV 202-5A Preventive W.R. f48514 N/A Reset closed limit switch.
U2 Head Vent Corrective W.R. f48516 N/A Replaced diaphragm.
V21va 2-220-47 U2 Hesd Vent Valvt Preventive W.R. #48517 N/A Adjusted limit arm.
2-220-46
o DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U2 Coro Spray Corrective W.R. f48528 N/A Installed new studs and nuts.
2-1402-4B U2 2-220-44 A0V Corrective W.R. #48561 N/A Installed new air diaphragm.
U2 2-220-51 A0V Preventive W.R. f48333 N/A Adjusted limits.
U2 Accu =ulator Preventive W.R. #48587 N/A Checked - no problem found.
26-11. LS 2-305-129 (26-11)
U2 Spare MSIV Preventive W.R. f48634 N/A Rebuilt spare 3-way valve.
3-Way Valve 2-203-1-A D2 "A" Recircula-Preventive W.R. f48635 N/A Installed keepers, removed and reinstal-tion Pump 2-202-A led spool piece, removed keepers and torque bolts.
U2 2 "D" CCSW Preve tve W.R. #48695 N/A Repacked pump.
Pu=p 2B-1501-44 U2 HPCI Oil Preventive W.R. #48705 N/A Cleaned filter.
Filt:Er U2 APRM Char.nel 4 Corrective W.R. #48815 N/A Replaced K-2 and K-16, verified trip setpoints.
D2 Snubber Moni-Corrective W.R. f48825 N/A Relocated ground cables.
t ring System U2 LPRM 40-09C Corrective W.R. f48839 N/A Replaced I.C. chip and transistor.
2-705-002 U2 Rx Level Preventive W.R. #48997 N/A Cleaned and installed new rings.
Switch (Yarway) 263-72D
e DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE-FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U2 2C LPCI Pump Preventive W.R. #49097 N/A Performed checks per procedure. No problems fcund.
U2 Containment H Preventive W.R. #49196 N/A Checked and calibrated analyzers per 2
0 Analyzer 2A procedure.
2 and 2B 902-64A-64' U2 H 0 Monitor Corrective W.R. #49199 N/A Replaced FIC 4 and recalibrated 0 2
2 (Ea1t) 2-2402A cell.
U2 CCSW Vault Corrective W.R. f49357 N/A Repaired leak.
Coot:r U2 APRM #6 Preventive W.R. #49396 N/A Checked per procedure.
U2 MO-2-1402-24B Preventive W.R. #49405 N/A Adjusted clip holding bulb.
U2 LPRM 08-33C, Preventive W.R. #49450 N/A Checked per procedure.
2-705-002 U2 "A" H 0 Preventive W.R. #49546 N/A Cleaned flowrator.
2 2 Monitar 2-2404A U2 Accumulator Preventive W.R. #49631 N/A Tightened fittings, adjusted FIC 4 18-11 117 Valve U2 2-1501-27B Preventive W.R. #49652 N/A Readjusted open limit switch and tested.
U2 2-1501-28A Preventive W.R. #49655 N/A Adjusted open limit switch and tested.
U2 Channel 7 Rod Preventive 4.R. #49678 N/A Adjusted per procedure.
Block Monitor
O DRESDEN UNIT 2
~
SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U2 Isolation Con-Preventive W.R. f49683 N/A Adjusted setpoint.
denser "A" Vent i Monit:r 2-1705-9A U2 Rod Block Corrective W.R. f49711 N/A Replaced 1 quad trip card and I flow
!!onit r Chennel 8 control trip reference card; calibrated per procedure.
D2 D/G Soak Back Corrective W.R. f49803 N/A Changed out pump.
Cil Pump U2 Discel Preventive W.R. f49841 N/A Inspected reverse power relay.
Generctor U2 Refueling Corrective W.R. f49930 N/A Replaced indicator trip unit, checked Floor ARM Channel and calibrated per procedure.
A, 2-1705-16A U2 Lube 011 Pres-Corrective W.R. f49955 N/A Replaced all hoses in panel.
sura Sensing Line Dicsel Generator U2 Terus Tempera-Corrective W.R. f49971 N/A Adjusted chart drive belt's tension.
tcra R; corder TR-2-1640-200A U2 APRM 6 Corrective W.R. f50086 N/A Repaired bad connector pin.
U2 T:rus Tempera-Pre.entive W.R. f50268 N/A Cleaned selector switch and slide wire.
tera Recorder 2-l!40-200A
C DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U3 IRM Channel 15 Preventive W.R. #47475 N/A Checked per procedure.
U3 Reactor Mode Preventive W.R. #47601 N/A Performed visual inspection.
Switch 590-300 U3 SRM 22 NM3-750-Preventive W.R. #47603 N/A Adjusted setpoint, completed procedure.
IC U3 HCU 30-27 Corrective W.R. #47606 N/A Rebuilt scram pilot valves.
U3 Scram Outlet Preventive W.R. f47617 N/A Tightened nuts.
Valva Accumulator 22-39, 3-0305-127 U3 Scram Pilot Corrective W.R. #47619 N/A Rebuilt and tested 20 scram pilot valves.
Vniv;a U3 Scram Outlet Preventive W.R. #47620 N/A Tightened nuts.
Valva Accumulator 22-35, 3-305-127 U3 CRD/ Accumulator Preventive W.R. #47621 N/A Tightened nuts.
26-39 Scram Outlet Elve 305-127 CRD/ Accumulator Preventive W.R. #47622 N/A Tightened nuts.
, 10-31 Scram Outlet
! Ulva 3-0305-127 U3 CRD/ Accumulator Preventive W.R. #47623 N/A Tightened nuts.
' 14-27 Scram Outlet Valv2 305-127 U3 CRD/ Accumulator Preventive W.R. #47624 N/A Tightened nuts.
18-27 Scram Outlet Valv2 305-127 l
1
9 J
DRESDEN UNIT 3
~.
1 SAFETT RELATED M&INTENANCE - FEBRUARY, 1986
-i j
LER OR OUTAGE MALFUNCTION
- EWIIFIENT NATURE OF M&INTENANCE IRMBER CABSE RESULT
'TurFrTIVE ACTION
~
l U3*CBD/Accumula-Preventive W.R. f47625 N/A -
Tightened nuts.
l
- tor-34-55 Scram i Outist Valve l.305-127 U3 CRD/Accumula-Preventive W.R. f47626 N/A Tightened nuts.
tor 38-55 Scram Outist Valve l305-127 l U3 CRD/Accumula-Preventive W.R. #47627 N/A ter 46-11 Scram Tightened bovn on flange bolts.
! Outict Valve l305-127 j U3 CRD/Accumula-Preventive W.R. f47628 N/A Tightened nuts, t:r 26-43 Scram
' Outist Valve 305-127 lU3 CRD/Accumula-Preventive W.R. f47629 N/A lt:r 30-35 Scram Tightened packing nuts.
l Outist Valve
,305-127 l
!U3 CRD/Accumula-Preventive W.R. f47630' N/A 1
tor 26-39 Scram Tightened packing nuts.
l Outist Valve 305-127 (U3 S.O.V. 302-Corrective W.R. f47683 N/A Replaced solenoid.
l20A i
U3 125VDC Bat-Preventive W.R. f47724 N/A tsry System Checked - no problem found.
e DRESDEN UNIT 3 SAFETY RELATED HAINTENANCE - FEBRUARY, 1986 LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION SDV Vent and Corrective W.R. #47727 N/A DrEin Air Header Replaced valve assembly and tested.
Supply Valve 3-0302-20B Recirc:nlation Preventive W.R. #47729 N/A I-Tia Valve Installed /remosed jumpers.
3-202-6A 3-302-18 Corrective W.R. f47734 N/A Rebuilt pilot valve and tested.LPRM 32-253 Preventive W.R. f47752 N/A (Group 2) 3-705-Checked per procedures. No problem found.
002 U3 IRM 17 RM3-Preventive W.R. f47785 N/A 750-7F Cycled and checked per procedure.
U3 ECCS Fill Pump Corrective W.R.
- 47867 N/A Replaced motor.
U3 Refuel Grapple Corrective W.R. #47903 N/A Replaced leaking air cylinder, cotter pin.
U3 SkM cnd IRM Preventive W.R. f47917 N/A Cabla Extensions Made up SRM and IRM extension cables.
U3 CRD 38-07 Preventive W.R. f47921 N/A (K-2) 305-117 Tightened nuts.
U3 125V System Preventive W.R. f48034 N/A Checked - no short found.
@3 24/48V B Top Corrective W.R. f48145 N/A Replaced timer.
Batt1ry Charger Ei=er
- 3 Di::sel Gene-Preventive W.R. f48183 N/A Inspected crimps.
r::t7r
a o
o DRESDEN UNIT 3
SAFETT RELATED M&INTENANCE - FEBRUARY,1986 LER OR OUTAGE MALFUNCTION EWIFIENT MATURE OF MAYuTE W rE INNSER CAUSE RESULT CORRECTIVE ACTION U3'Rx Building /
Preventive W.R. #48264 N/A Turbine Internal Adjusted closing mechanisms on turbine Door and Rx Building doors.
U3 "A" Core Spray Preventive W.R. #48344 N/A
, Suction Support Replaced missing nuts.
- l. 1402-W-205 U3 Crcpple Corrective W.R. #48499 N/A Replaced both micro switches.
U3 M03-1402-4A Corrective W.R. #48586 N/A Cora Spray Valve Removed MO from U3 and installed on U2 1402-4B valve.
Opercter U3 Recirculation Preventive W.R. d48952 N/A
' Pump Flanges 35-Removed blank flanges.and installed.
202 and 3A-202 decon. equipment.
lU3 RWCU Flanges Preventive W.R. f48954 N/A l 3-1201-1A and Removed blank flanges and installed
- 3-1265 Line decon. equipment.
l U3 2B Recircula-Preventive W.R. f49016 N/A Removed coupling.
J l tion Pump
- 3 Dicsel Cen-
. Preventive W.R. f49188 N/A Performei semi-annual inspection orater per procedures.
U3 Pracgure Preventive W.R. #49299 N/A Transmitter Replaced transmitter cover, inspected and Calibration PT3-calibrated PT, E.Q. requirement.
6478 U3 Rx Pressure Preventive W.R. #49300 N/A Inspected and calibrated PT.
Transmitter-Calibration PT3-647A 1
1 f
[
~i l
l i
DRESDEN UNIT 3 SAFETT RELATED M&INTINANCE - FEBRUARY,1986
\\
l LER OR OUTAGE MALFUNCTION EWi1FMENT MATURE OF M&INTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U3 Recirculation Preventive W.R. #49519 N/A Fused and drained instrument lines.
Syctem Instru-
' mentction.
il U3 Rx Building Preventive W.R. f49595 N/A Reinstalled fuse, adjusted door closure.
' Ictarlock Door l
lU3LLRTBoxDTS-Preventive W.R. f49950 N/A Performed monthly calibration per proce-
' 31 dures.
U3 LLRT Box DTS-Preventive W.R. #49951 N/A Performed monthly calibration per_proce-32 dures.
- U3 Rx Building Corrective W.R. f50232 N/A Installed new versa valve.
l Vent System I Idat Isolation
' Valva 3-B-5741 i
l
-r t
d
,d
~
I
?
.e
~
~
s DRESDEN UNIT 2/3
)
j SAFETY RELATED MAINTENANCE - FEBPUARY, $986
,/
[
LER OR OUTAGE MALFUNCTION
~
EQU1PMENT NATURE OF MAIMTENANCE NUMBER CAUSE RESULT-CORRECTIVE ACTION U-273 Safety Co' erective W.R. #35489
-/
~ N/A s
Vilve - Spare #1, Rebuilt safety valve.!
/
203
-U-2/3 Safety Corrective W.R. #35490-N/A Valve - Spare #2, Rebuilt safety valve.
T-203 U-2/3 Safety Corrective W.R. #35491 N/A Rebuilt safety valve.
Valva - Spare #3, 203 U-2/3 Safety Corrective W.R. #35492 N/A Rebuilt safety valve.
Valva - Spare #4, 223 U-2/3 "B" Corrective W.R. #35901 N/A Replaced rubber air intake hose.
Emergency Diesel U-2/3 Spare 18" Preventiva W.R. #37811 N/A Rebuilt check valve.
Tilting Check Valva U-2/3 SBGT Outlet Corrective W.R. f42892 N/A Replaced hand wheel.
Velva 7506A U-2/3 Sensor and Preventive W.n. f43225 N/A Repaired sensor and converter - returned Convertcr - G-1 to Storeroom.
M07 7504A 2/3 Preventive W.R. #43612 N/A Replaced grease, viring, spliced motor 7504A lead connections - E.Q. requirement.
U-2/3 MOV 7505A Preventive W.R. #43614 N/A Replaced grease, wiring, spliced motor lead connections - E.Q. requirement.
U-2/3 MOV 7507A Preventive W.R. #43616 N/A Replaced grease, wiring, spliced motor lead connections - E.Q. requirement.
r-DRESDEN UNIT 2/3 SAFETY RELATED MAINTENANCE - FEBRUARY, 1986
~
LER OR OUTAGE MALFUNCTION EQUIPMENT NATURE OF MAINTENANCE NUMBER CAUSE RESULT-CORRECTIVE ACTION RB}f Rslay Card
. Corrective W.R. f43635 N/A Replaced relay K-1.
DIS 32 Heise Preventive W.R. #43690 N/A Gaugs Gauge.will have to be replaced.
U-2/3 DG Cooling Preventive W.R. #44726 N/A W2tr.r Pump Repaired sealtite and burned to ground cable.
U-2/3 Spare Quad Corrective W.R. #44804 N/A Replaced G4 and Q1 trip card.
Trip Cerd U-2/3 Rosemount.
Corrective W.R. #45763 N/A Transnitter Repaired 3 transmitters.
U-2/3 GE Quad Corrective W.R. #46348 N/A Trip Card Replaced Op. Amp.
U-2/3 Diesel Preventive W.R. f48184 N/A Gin:rator Checked crimps.
'U-2/3 Diesel Preventive W.R. #48203 N/A
! G:;narctor Taped at breake'r.
- U-2/3 DTS-32 Preventive W.R. f48203 N/A Calibrated test gauge.
j U-2/3 Diesel Preventive W.R. #49474 N/A Relugged wire.
GinBrator
- U-2/3 DG "B" Air Corrective W.R. #49964 N/A Compree or Readjusted "B" compressort pfessure' control switch.
e 4
.g d
- 3. -
? -
DOCKET NO. 050-237 I
UNIT NAME II C
UNIT SHUTDOWNS AND POWER REDUCTIONS DATE March 1, 1986'-
COMPLETED BY D. C. Maxwell
. TELEPHONE (815) 942-2920 REPORT MONTH February, 1986 METHOD OF LICENSEE CAUSE & CORRECTIVE NO.
DATE' TYPEl DURATION REASON 2 SHUTTING EVENT SYSTEM COMPONENT ACTION TO (HOURS)
DOWN REACTOR 3 REPORT F CODE 4 CODES PREVENT RECURRENCE 3
.86-02-04 F
116:50 A
Manual Steam leak in x-area drain line.
(116.8) f 86-005-0 During subsequent start-up j
reactor scrammed while moving.
mode switch from refuel to start-up (Rx at 0 MWt).
i 4
i s
i i 1 2
3 4
i F: Forced Reason:
Method:
Exhibit G-Instructions for i
S: Scheduled A-Equipment Failure (Explain) 1-Manual Preparation of Data
}
B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee j
C-Refueling 3-Automatic Scram Event Report (
) File l
D-Regulatory Restriction 4-Other (Explain)
(NUREG-0161) j E-Operatcr Training & License Examination l
F-Administrative i
G-Operational Error
{
l H-Other (Explain)
a.
DOCKET NO. 050-249 UNIT NAME III UNIT SHUTDOWNS AND POWER REDUCTIONS DATE March 1, 1986 *
~
COMPLETED BY D. C. Maxwell TELEPHONE (815) 942-2920 REPORT MONTH February, 1986 METHOD OF LICENSEE CAUSE & CORRECTIVE NO.
DATE' TYPEl DURATION REASON 2 SHUTTING EVENT SYSTEN COMPONENT ACTION TO (HOURS)
DOWN REACTOR 3 REPORT F-CODE 4 CODES PREVENT RECURRENCE 6
.85-10-28 S
672:00 C
1 Off-line manually to 9th Refueling / Recirculation Pipe
~
Replacement outage.
I j
i 1
l
}
1 2
3 4
F: Forced Reason:
Method:
Exhibit G-Instructions for S: Scheduled A-Equipment Failure (Explain) 1-Manual Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3--Automatic Scram Event Report (
) File D-Regulatory Restriction 4-Other (Explain)
E-Operator Training & License Examination F-Administrati'.e I
G-Operational rrror I
H-Other (Explain)
l
?
\\
UNIQUE REPORTING REQUIREMENTS
. MAIN STEAM RELIEF VALVE OPERATIONS Relief valve operations during the reporting period of February, 1986 are summarized in the following table. Thel table includes information as to which relief valve was actuated. how it was actuated, and the circum-stances resulting in its actuation.
Valves
' Description Unit
' Reporting Period Actuated Actuations Conditions of Events
~
2
~02-01-86_to 02-28-86 None 3
02-01-86 to 02-28-86
'None 4 Safety / Relief valves removed during the outage were tested (challenEed)~
and all 4 lifted at set-point..After testing they were rebuilt prior to installation.
5 I
l l
~
SUMMARY
OF OPERATING EXPERIENCE UNIT TWO FEBRUARY, 1986 02-01-86'to 02-09. Unit 2 entered the month operating at a level of 790 MWe and at maximum core flow. The unit operated until February 4 at 0555 hours0.00642 days <br />0.154 hours <br />9.176587e-4 weeks <br />2.111775e-4 months <br /> when the generator was taken off-line because of a steam leak in a main steam drain line. The line was repaired and while the unit was preparing.for start-up on February 6, a reactor scram occurred at 1949 hours0.0226 days <br />0.541 hours <br />0.00322 weeks <br />7.415945e-4 months <br /> when the mode switch was moved from refuel to start'-up.
The scram was attri-buted to contacts in the mode switch that overtraveled to the run position. With mode switch contacts in the run position, the reactor scrammed on low condenser vacuum. The reactor was brought to critical at 2345.
02-09-86 to 02-28-86 The turbine was synchronized to the system on February 9 at 0245 hours0.00284 days <br />0.0681 hours <br />4.050926e-4 weeks <br />9.32225e-5 months <br /> and operated the remainder of the month reaching a power level of 840 MWe with an availability of 82.6% and a capacity factor of 71.85%.
1 m
m
.G '.
e-o-
SUMMARY
OF OPERATING EXPERIENCE UNIT THREE FEBRUARY, 1986-i, 02-01-86 to.02-28-86 Refueling outage activities continued throughout the entire period. The unit is presently scheduled to 4
start-up in mid-June,'1986. Major 1 work includes:
- Normal pump (s).and valve (s) maintenance.
- Decontamination of the removed recirculation piping.
- Replacement of the recirculation piping.
- ISI inspections.
1' J
4 -
1
.1" i
i '
J F
s i,
Commonwealth Edison Dresden Nuclear Power St: tion R.R. #1 f
Morris, Illinois 60450 Telephone 815/942-2920 March 1, 1986 DJS LTR:
86-180 Director, Office of Inspection and Enforcement United States Nuclear Regulatory Commission Washington, DC 20555 Attention: Document Control Desk
Dear Sir:
Enclosed, please find Dresden Station's operating data for the month of February, 1985. This information is supplied to your office per the instructions set forth in Regulatory Guide 1.16.
Sincerely.
Y D. J. Scott Station Manager Dresden Nuclear Power Station DJS:DCM:hjb Enclosure cc: Region III, Regulatory Operations, U.S. NRC Chief, Division Nuclear Safety, State of IL U.S. NRC, Document Management Branch Nuclear Licensing Administrator Nuclear Fuel Services Manager Nuc. Sta. Div. Vice. Pres.
Manager, Tech. Nuc. Sta.
Tech. Staff A.E.
On-Site NRC Inspector Sta. Nuc. Eng. Dept.
3 Sta. Q.A. Dept.
Comptroller's Office PIP Coordinator INPO Records Center File /NRC Op. Data File / Numerical 1
f)v'gpv i
V s\\
]