May 27, 1997-LICENSEE:

Florida Power Corporation FACILITY:

Crystal River Unit 3 4

SUBJECT:

SUMMARY

OF MEETING ON MAY 20, 1997, REGARDING STATUS OF THERMO-LAG FIRE-BARRIER SOLUTION On May 20, 1997, representatives of the Florida Power Corporation, licensee j

for Crystal River Nuclear Plant, Unit 3 met with members of the staff at NRC 1

Headquarters in Rockville, Maryland, to provide an overview and current status of its Thermo-Lag resolution effort. is a list of attendees. contains copies of handouts distributed at the meeting.

The licensee's initial Thermo-Lag resolution strategy involved four parallel paths; reevaluation of the safe shutdown analysis, application of Nuclear Energy Institute guide, installation of an alternate fire-barrier material (Mecatiss) and the Electric Power Research Institute tailored collaboration effort.

The licensee discussed details and status of these strategies.

l

_The licensee indicated that it has revised the safe shutdown analysis taking into account several design modifications that have been implemented since 1985, and had not been previously credited in the analysis.

Operation procedure changes, and associated circuit calculations are complete. The revised fire hazard analysis and topical design basis documents are scheduled to be completed suu after restart from the current outage.

Engineering 3

effort for circuit modifications is in progress and physical rerouting is scheduled to be completed by the end of year 2000.

The licensee indicated that its revised safe shutdown analyses and circuit modifications could result in approximately 80% reduction in the currently protected raceways.

The licensee also indicated that installation of the alternative Mecatiss is completed.

l^

The staff questioned the licensee as to why the circuits modifications and sprinkler additions could not be accomplished during the current outage, and requested the licensee to discuss the schedule details during its upcoming meeting with the staff on June 11, 1997 relating to 10 CFR 50 Appendix R design basis issues. The licensee agreed.

original signed by L.Raghavan L. Raghavan, Project Manager Project Directorate II-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation Docket No. 50-302

Enclosures:

1.

Attendance List 2.

Meeting Handout gg g g l

cc w/

Enclosures:

See next page Document Name: G:\\ CRYSTAL \\970520. SUM 0FFIC2 PDil 3/PM l

PDIl-3/LA lO PDII 3/D $ )

lC l

NAME LRaghavan W BClayton 4#[/

FHebdon }d 0 ATE 05/2&/97 05/$97 7

05/Tl/97 0FFICIAL RECORD COPY 9705300224 970527 PDR ADOCK 05000302 P

PDR

i i

Y MQ i

l g-UNITED STATES g

j NUCLEAR REGULATORY COMMISSION 2

WASHINGTON, D.C. 20656 4001

\\..... p!

May 27, 1997 LICENSEE:

Florida Power Corporation FACILITY: Crystal River Unit 3 l

SUBJECT:

SUMMARY

OF MEETING ON MAY 20, 1997, REGARDING STATUS OF THERM 0-LAG FIRE-BARRIER SOLUTION On May 20, 1997, representatives of the Florida Power Corporation, licensee for Crystal River Nuclear Plant, Unit 3 met with members of the staff at NRC Headquarters in Rockville, Maryland, to provide an overview and current status of itc Thermo-Lag resolution effort. is a list of attendees.

E'.closu N 2 contains copies of handouts distributed at the meeting.

l The licensee's initial Thermo-Lag resolution strategy involved four parallel l

paths; reevaluation of the safe shutdown analysis, application of Nuclear Energy Institute guide, installation of an alternate fire-barrier material l

(Mecatiss) and the Electric Power Research Institute tailored collaboration l

effort. The licensee discussed details and status of these strategies.

i The licensee indicated that it has revised the safe shutdown analysis taking into account several design modifications that have been implemented since 1985, and had not been previously credited in the analysis. Operation I

procedure changes, and associated circuit calculations are complete. The revised fire hazard analysis and topical design basis documents are scheduled to be completed soon after restart from the current outage.

Engineering effort for circuit modifications is in progress and physical rerouting is scheduled to be completed by the end of year 2000. The licensee indicated that its revised safe shutdown analyses and circuit modifications could result in approximately 80% reduction in the currently protected raceways.

The l

licensee also indicated that installation of the alternative Mecatiss is l

completed.

The. staff questioned the licensee as to why the circuits modifications and sprinkler additions could not be accomplished during the current outage, and 1

requested the licensee to discuss the schedule details during its upcoming meeting with the staff on June 11, 1997 relating to 10 CFR 50 Appendix R design basis issues.

The licensee agreed.

l vs$

L. Raghavan, Project Manager Project Directorate 11-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation Docket No. 50-302 1

L

Enclosures:

1.

Attendance List 2.

Meeting Handout cc w/

Enclosures:

See next page I

l

m 8

Florida Power Corporation CRYSTAL RIVER UNIT N0. 3 GENERATING PLANT cc:

Mr. R. Alexander Glenn Senior Resident Inspector Corporate Counsel Crystal River Unit 3 Florida Power Corporation U.S. Nuclear Regulatory Comission MAC-A5A 6745 N. Tallahassee Road I

P.O. Box 14042 Crystal River, Florida 34428 St. Petersburg, Florida 33733-4042 l

Regional Administrator, Region II l

Mr. Bruce J. Hickle, Director U.S. Nuclear Regulatory Comission Nuclear Plant Operations (NA2C) 61 Forsyth Street, SW., Suite 23T85 i

Florida Power Corporation Atlanta, GA 30303-3415 Crystal River Energy Complex 15760 W. Power Line Street Mr. John P. Cowan Crystal River, Florida 34428-6708 Vice President - Nuclear Production (SA2C) 4 i

Mr. Robert B. Borsum Florida Power Corporation B&W Nuclear Technologies Crystal River Energy Complex 1700 Rockville Pike, Suite 525 15760 W. Power Line Street i

Rockville, Maryland 20852 Crystal River, Florida 34428-6708 Mr. Bill Passetti Mr. Roy A. Anderson Office of Radiation Control Senior Vice President, Department of Health and Nuclear Operations l

Rehabilitative Services Florida Power Corporation 1317 Winewood Blvd.

ATTN: Manager, Nuclear Licensing l

Tallahassee, Florida.32399-0700 Crystal River Energy Complex (SA2A) i 15760 W. Power Line Street Attorney General Crystal River, Florida 34428-6708 Department of Legal Affairs The Capitol Mr. Kerry Landis i

l Tallahassee, Florida 32304 U.S. Nuclear Regulatory Comission 61 Forsyth Street, SW., Suite 23T85 Mr. Joe Myers, Director Atlanta, GA 30303-3415 Division of Emergency Preparedness l

Department of Community Affairs l

2740 Centerview Drive l-Tallahassee, Florida 32399-2100 Chairman l

Board of County Comissioners Citrus County 110 North Apopka Avenue Iverness, Florida 34450-4245 Mr. David F. Kunsemiller, Director Nuclear Operations Site Support i

(SA2A)

Florida Power Corporation Crystal River Energy Complex-15760 W. Power Line Street Crystal River,. Florida 34428-6708

.-..n......

a.

- - ~..

~. n.

t l

SUMMARY

OF MEETING ON MAY 20, 1997, REGARDING STATUS OF Thermo-Lag FIREBARRIER l

SOLUTION Distribution:

HARD COPY w/ Enclosures 1 and 2 Docket File:

PUBLIC' Crystal River Reading OGC' ACRS

'E-Mail w/ Enclosure 1 S. Collins /F. Miraglia (SJC1 FJM)

R. Zimerman (RPZ)

S. Varga (SAV,RCN)

J. Zwolinski (JAZ)

F. Hebdon (FJH)

L. Raghavan (LXRI)

B. Clayton (BAC2)

D. Ross (SAM)

J. Jaudon (JPJ)

G. Tracy (GMT)

S. Cahill (SJC2)

J. Johnson, RII W. Miller, RII S. West T. Marsh E. Connell L. Tran D. Qudinot H. Calvo R. Jenkins j

i a#

l

1 CRYSTAL RIVER 3 MEETING MY 20.1997 Malgt Oraanization L. Raghavan NRR S. West NRR T. Marsh NRR E. Connell NRR L. Tran NRR D. Qudinot NRR W. Miller (by phone)

Region II C. Willbanks NUS N. Fioravante FPC J. Baumstark FPC D. Kunsemiller FPC J. Maseda FPC l

J. Dymek FPC A. Spear FPC F. Emerson NEI ENCLOSURE 1 i

l J

t 6

i M hMM M e

a

?

f THERMO-LAG RESOLUTION t

NRC/FPC MEETING i

MAY 20,1997 i

0 ENCLOSURE 2 g e t

j

I 1

P ~~RPOSE i

' W N-W eT

'T 6

~

c

-7 mp; f

Provide an Overview of the Thermo-Lag Resolution Effort for Crystal River Unit 3 i

6 Florida PRWFJ i

i l

=

AGEXDA

. _ ~

Introduction J. S. Baumstark t

Describe Thermo-Lag Installations at CR-3 W. L. Rossfeld Review Thermo-Lag Resolution Strategy W. L. Rossfeld Present Ongoing Resolution Plan W. L. Rossfeld Status of Resolution Effort W. L. Rossfeld Summary J. S. Baumstark i

Florida Power

CRYSTAL RIVER EXIT 3 e

Extensive installation of Thermo-Lag

- 7700 LF of Protected Conduit and Cable Tray

- 15516 LF of Protected Supports e

Upgraded Construction

- Material Thickness j

- Pre-and Post-Buttered Joints

- Close Band and Tie Wire Spacing i

- Trowel Grace Overlay e

Many Unique Configurations j

- Conservative Application of the 18" Rule

.j ' g

- Compact Electrical Equipment Areas 4.#

Florida 89.WF.r l

m

i I

RESOLETIOX STRATEGY in mm - -

v.

m.

?

e Re-Evaluation of Safe Shutdown Analysis l

e NEl Application Guide e Alternate Barrier o

EPRI Tailored Collaboration l

i i

Florida Power t

FLORIDA POWER CORPORATION THERMO-LAG RESOLUTION STRATEGY Re-analysis NEI Application Guide Alternative Barrier EPRI Tailored Collaboration l

App. R Phase i NEl Appleaton Identify CR3

, ' ~5todei A'lli EPRI-TC

~'

Identify Guide Test Fire Areas l Tools Options Waixdown Confxturation

' for IPEEE/F,lVE!

Methodology I f I f I f l

A1 NEl Fire Rating Therm R ag Conduct CR3 Screen All L

Appleaten Chemical Fire Test Fire Areas F

of the EPRI Bounding l

Determination Testing EPRI FlVE Model TC-Toob I E I f App. R Phase il

) f Hanger {

,' A'p' ply'I'P'E'E'E' '.,

NEl-ISi lC3 l Verify Options B1 Calculationsi PSA to All ;

Combustabet ty Cost Estimate

', Fire Areas,,/

Determination Ampacity.

lA2 l lC3 l Resolution -

lA2 l lB2l I f I f I f I f I f I f I f I f Thermo-Lag Mecatiss

" Common Sense Evaluaton" i

Acceptability Acceptability Evaluate and Compare Results of Determination Determination Fire Modeling with Risk Analysis V

V V

ii f l1 1 l2 3l l4 5l le-7-l RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT / COST EVALUATION)

1. Thermo-Lag not required (analysis / safety evaluation or modification)
5. Thermo-Lag is unacceptable - will be replaced with Mecatiss
2. Thermo-Lag is a 1 hr / 3hr rated barrier
6. Thermo-Lag is acceptahle for the installed configuration *
3. Thermo-Lag would be a ihr / 3hr barrier with minor upgrades
7. Thermo-Lag would be acceptable with additional fire protection *
4. Thermo-Lag would be acceptable with Mecatiss overlay
  • These options require NRC approval of an exemption

EXPECTED RESL~LTS C'F i

RESOLETION STRATEGY n_

\\

e Identify Methods to Achieve Shutdown Without T-L e

Demonstrate Some Existing Barriers are 1 or 3 Hour Rated e

Demonstrate Some Barriers are Acceptable for Existing Configuration and Hazards l

I e

Identify Minor improvements to Establish 1 or 3 Hour Rating t

e identify Additional Fire Detection or Suppression Needs

[

t r

e Demonstrate Use of Mecatiss as an Upgrade to Existing T-L

(

-)

Floricia I'OWer e

Demonstrate Mecatiss as a Replacement Barrier

~~

FLORIDA POWER CORPORATION THERMO-LAG RESOLUTION STRATEGY NEI Application Gukie Ahernative Barrier EPRI Tallored Collaboration l

f NEl Applicaten Mentify CR3

,' '$lodel'Illi EPRI-TC Guide Test Fire Areas l Tools Walkdown Configuration

  • for IPEEE/FIVE,'

Methodology ECost CalculationsI PSA to All :

Combustibility i

l I A1 NEl Fire Rating Thermo-Lag Conduct CR3 Screen All l

L Applicaten Bounding Determination Chemical Fire Test EPRI FIVE Modelgl Fire Areas 7

of the EPRI l

Testing TC-Tools l E Hanger [

,' dp~py!'P'E'E'E '.,

NEl-TSI lC3 l B1

,, Fire Areas,,/

Determination i

Ampacity A2 lC3 l Resolution lA2 l 182 l i

l I I f I f lf I f I f I f l f Thermo-Lag Mecatiss

" Common Sense Evaluation" i

Acceptability Acceptability Evaluate and Compare Results of l

Determination Determination Fire Modeling with Risk Analysis h

B2 V

V i 1 P l

l1 l l2 3l l4 5l l ' 6*

7* l l

RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT 1 COST EVALUATION) 4

1. Thermo-Lag not required (analysis / safety evaluation or modification)
5. Thcrmo-Lag is unacceptable -wlN be replaced with Mecatiss l
2. Thermo-Lag is a 1 hr / 3hr rated barrier
6. Thermo-Lag is acceptab!e for the installed configuration *
3. Therm @ would be a ihr / 3hr berrier with minor upgrades
7. Thermo-Lag would be acceptable with additional fire protection *
4. Thermo-Lag would be acceptable with Mecatiss overlay
  • These options require NRC approval of an exemption i

[

i

SHLTDOWX AXALYSIS ACTIVITIES i

r ' r" z r r: r:r i

e All Fire Areas Containing Thermo-Lag were Evaluated e

Based on Analysis Changes (Offsite Power, Auxiliary Feedwater l

Pump, Makeup, EFIC/EFW) Means have been Identified for:

i

- Overall 62% reduction in Raceways Requiring Protection e

Modifications Consisting Mainly of Circuit Modifications Could:

- Reduce Raceways Requiring Protection an Additional 18%

e Therefore, Shutdown Analysis Activities Could Provide:

- An Overall 80% Reduction in the Raceways Requiring Protection c,b i

i Moricia P,oyyer

FLORIDA POWER CORPORATION THERMO-LAG RESOLUTION STRATEGY ~

j Re-enalysis Alternative BarrW EPRI Tailored Collaboration App. R Phase 1 identify CR3

~$lodel'Alls EPRI-TC

~

Identify Test Fire Areas l Tools l

_g Confirruration

  • forJPEEE/FIVE/

Methodology l

1 f I f A1 Conduct CR3 Screen All u

Apphcaten Fire Test Fire Areas 7

of the EPRI j

EPRI FIVE Model TC-Tools i

I I I f.

App. R Phase ll 1 ;; -

, ' A'p'piy'I'P"E'EE's NEl-TSt lC3 i

Verify Options B1 PSA to All ;

Combustbilty y Estimat

,, Fire Areas,,/

Determination lA2 l IfEmlution lA2 l I f I f I f I f I f l f Mecatiss

" Common Sense Evaluation" i

Acceptability Evaluate and Compare Results of Determination Fire Modeling with Risk Analysis l

B2 1 P V

i 1 I l1l l2 3l l4 5l l: 6*

7* l f

RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT / COST EVALUATION) 4

1. Thermo-Lag not required (onelysis/ safety evaluation or modification)
5. Thermo-Lag is unacceptable -will be replaced with Mecatiss i
2. Thermo-Lag is a 1 hr / 3hr rated, barrier
6. Thermo-Lag is acceptable for the installed configuration *
3. Thermo-Lag would be a ihr / 3hr barrier with minor upgrades
7. Thermo-Lag would be acceptable with additional fire protection
  • l
4. ThomW would be acceptable with Mecatiss overlay
  • These options require NRC approval of an exemption

[

i l

-.~. -._ _

m XEI APPLICATIOX GUIDE e

NEl Application Guide Walkdown Completed for Sample Set of Raceways o

NEl Fire Rating Bounding Determination Completed for Sample f

Set of Raceways e

NEl Application Guide Did Not Result in Qualifying Any Existing 1 & 3 Hour Barriers e

Intervening Aluminum Conduits Complicated the Qualification of i

Fire Barriers i

e The NEl Application Guide Did Not Lead to Resolution of /.ly $)

[;' g Raceways

~ _ -.

~

t FLOR lDA POWER CORPORATION THERMO-LAG RESOLUTION STRATEGY Re-analysis NEI Application Guide Barrier EPRI Tailored Collaboration

, !WMN j I,'

Model All 'i EPRI-TC App. R Phase i NEl Application h,Tep,CR3 j,!

Fire Areas l Tools i

Identify Guide Options Walkdown eA%

t. (for IPEEE/FjVE!

Methodology j

1 r r

A1 NEl Fire Rating Therrno-Lag

.Qaeddetf,R3

  • Screen All k

Apphcation I;g [h M M~W. <

pfestN Bounding

~

Chemical Fire Areas 7

of the EPRI I

Determination Testing y

EPRI FIVE Mode:.

TC-Too;s

[

l r I f App. R Phase 11 l f Hanger [

h, 4 hjE Appiy'I"P'E'EE i NEl-ISI lC3 l j

. $gW'h

~~

3 E

Qj +, Fire Areas Verify Options B1 Calculations !

'g PSA to All :

Combustibihty 7

Cost Estimate Determinaton i

n 4

1 q

W Np Y

Ampacty.

'. E O

\\"i W lA2 l b

Resolution 7 i idN hj$f

[A2 l 182 l l

r E,B L M h%s 1 ;g w

syd 1 r1 r j !?

Ih N

1 r 1 r 1 r 1 P 1 r

)h

' TfMoostiss it 3b

" Common Sense Evaluation" i

ThermWg i

.5M h

Evaluate and Compare Results of

[

Acceptability Determination

'M Fire Modeling with Risk Ar.alysis j

h B2 1 r 1 r 1 r i1 r i

11_1 12 al l4 si le-7-l RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT / COST EVALUATION)

+

1. Thermo-Lag not required (analysis /ssfety evaluation or modification)
5. ThermW is unacceptable -wiu be replaced with Mecatiss

[

2. Therm @ is a 1 hr/ 3hr rated barrier
6. Thermo-Lag is acceptable for the installed configuration
  • l
3. Thermo-Lag would be a ihr / 3hr barrier with minor upgrades
7. Thermo-Lag would be acceptable with additional fire protection
  • l
4. Thermo-Lag would be acceptable with Mecatiss overlay
  • These options require NRC approval of an exemption i

l i

I r

[

ALTERNATE BARRIER TEST PROGRAM m'..,..,--

~v *1=yti-v:..

e Many Materials Were Evaluated as an Overlay and/or Replacement i

e Mecatiss Was Selected i

e An Extensive Testing Program at U.L. was completed for Mecatiss l

- All Testing in Accordance with GL 86-10, Suppl.1

- 69 Raceway Configurations Were Tested

- Additional Configurations Were Tested May 1996 and g.ga.g l

Approved by the NRC in SER dated January 29,1997

%*..//

l El$$

r OXE & THREE HOUR FIRE TEST COXFIGURATIONS e Mecatiss Replacement and Upgraces for 6" x 4" to 24"x 4" Aluminum Tray and 3/4" to 4" Aluminum Conduit e Mecatiss Replacement and Upgrades for Structural l

Supports, Adhesion to Walls and Penetration Seals and in a Compressed State (50%)

e Mecatiss Replacement and Upgrades for Various Unique Configurations (g,).

=

i i

FLORIDA POWER CORPORATION THERMO-LAG RESOLUTION STRATEGY Re-analysis NEI Application Guide Alternative Barrier vjEPftiTaBiided Crountsiirall6a#Apq" I

)..a.E. k. %W%.-.k%$g f,.i.W.:p.TkW %1 W W W

T2 E

t g

.f.g l

App. R Phase i NEl Apphcation identify CR3

.,c g; tyM ] g: k $$ Tools'!jl j $

ledelAlis

  • EPRI-TC4 fg

"{.h.. W Identify Guide Test

, rii%],}.

852 l

g.

f!jg ""-t-_M-2y Opt ons Walkdown Confirluration Q

j

_1P 1 I i

(

A1 NEl Fire Rating Thermo-Lag Conduct CR3 3.qf 4'sScreenA5jr;I

@@L (Apptcebon Eg

[

$ysp$qp EPRIFlVE Modelg "k.?g NFir Bounding iof the EPRI QM Determination Chemical Fire Test ph g,,C-Tools f p.h l

hT j

Testing

..% Q -h

,, M ;;.\\

v App. R Phase il l f I

h q%, ApplyIPEEE ?Qh411 $":TFireAraes&g Hanger NEl-TSI M

C3 lK!F Verify Options 81 Calculations PSAto ARE Combusubety $ (,jg Cost Estimate 1

M Determination

&.. 7 i m ; pA I spj,..t,.A%.s W.d&.,

K:M N. q..,g,, g+.g: y

,, q. v,.,

g.

tJdA..s

,,p r

w

,: r;, l A2 l 3 Resolution {

y3 w$.

s 47,7 y

Ampacity

b-

.Q R : p.g

'n 1

lA2 l lC3 l

.,4. 4,,9

, w. g e o I

,g g y;j

.s.

og+;!g

. i3, p/ $

g.w.

~..m c

t y

7.&p.

$t 4 b];, g 6 [ h

~@ W[r

%MIU I-M

%q t

+

m.

.... b fv% h1-l fe 'Ll Np dhiEk1fL R.Qg.].t l

647.$1f#du k%w 1 f 1 f 1 f 42 E

OtbQ$.-4w.r%. ", Common Sen.se Evolustiorr4mt ;4, JF M "'cM MP ThermWg Mecatiss t

p g

xwd

.s 'n"^^$f %,Evalu, sta and Compare Results of.q'WWM-y,Mt 4w m

Acceptabiltty AcceptabHity f

+$

~~_y-g.y.g*

qin j

Determination Determination L.

S b e. Fire Modeling wth RisliAnalysie 4isc O

- -.- v. w w u n - m x x.am m,x.. hii

\\

82 I f

'l f V

}i f

[

l1 l l2 3l l4 5l lt6*

7* l RESOLUTION EVALUATION & SELECTION (SAFETY BENEFITI COST EVALUATION)

?

1. Thermo-Lag not required (analysis / safety evaluation or modification)
5. Thermo-Lag is unacceptable - will be replaced with Mecatiss
2. Thermo-Lag is a 1 hr / 3hr rated barrier
6. Thermo-Lag is acceptable for the installed configuration *
3. Thermo-Lag would be a ihr / 3hr barrier with minor upgrades
7. Thermo-Lag would be acceptable with additional fire protection *

[

4. Thermo-Lag would be acceptable with Mecatiss overlay
  • These options require NRC approval of an exemption I

_ _ _ ~ _. ___ _ - -

EPRI-TAILORED COLLABORATIOX (TC) we

?*

- m w--- tr.*'avsumusuur mmmmmmmmer -

7 e

Completed initial PSA of All Fire Areas e

Completed Development of the EPRI-TC Tools e

Completed initial Application of the EPRI-TC e

Completed initial" Classical" Fire Protection Assessment e

Completed Preliminary " Common Sense" Evaluations e

Candidates for Exemptions Based on Preliminary Results f

Were the Control Complex, Auxiliary Building, and

(

.)

Intermediate Building pgg i

THERMO-LAG RESOLUTION e

Shutdown Analysis Changes Will Be implemented to Achieve a 62% Reduction in the Currently Protected Raceway l

l 1

l e

Re-route and Circuit Modifications Will Be Used to Provide an 18% Reduction in the Currently Protected Raceways e

Mecatiss Will Be Used For 3% of the Currently Protected Raceways e

Upgraded Thermo-Lag Will Be Used as Radiant Energy Shield for 2% of the Currently Protected Raceways e

Exemption Requests Will Be Used to Address 15% of the Currently Protected Raceways ihg'h,,

1 I28$1

l i

J

?

i i

i 1

i Thermo-Lag Resolution Results Banier Upgrades 3%

li 4

1 Exemption Requests 17%

i i

I Analysis Changes j

62%

Circuit Modifications l

18%

l 4

1 i

3 l

l i

a i

k l

THERMO-LAG RESOLUTIOX SCHEDULE n._.

r E r z -

e By Dec.1995 Letter to the NRC

- Implement Analysis Changes by 9/30/96 (Amended to 90 Days After Restart by Jan.1997 Letter)

- Re-route and Circuit Modification by 12/31/00

- Preliminary Designs of Re-routes by 12/31/96 (Completed)

- Install Mecatiss by 12/31/96 (Completed)

- Submit Exemption Requests by 5/31/96 (Completed)

I

=

FLORIDA POWER CORPORATION THERMO-LAG RESOLUTION IMPLEMENTATION PLAN i

i RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT / COST EVALUATION) 7 i

Anaiysis Changes Circuit Mods Repair Procedure Mecatiss Exemptions Ampacity Re-format MARS MAR to Support l l

Submit l

Testing l

Submt AP-880 Prepare Repair Activities l Test Reports l Exemption l

-__acpage l

l Requests Y

I P

Associated Perform Work V

V l

l Re mrt l

T Circuits Draft Procedure NRC l

T f

Document l Calculation Review l

NRC l

T Changes l Work Request i

Review l

l Calculations l l

t Y

i Fire T

Melatiss Y

Y T

Protection issue Procedure Instal.ition MAR l

l NRC Review l Issue Deviations-Prepare Update Work Request MAR AP-880 Prepare Install Package Perform Work f

I V

U V

V V

T Y

Y l

l THERMO-LAG FIRE BARRIERS RESOLVED h

Y h

h Y

h Revise Update Fire Update Assess Fire Close Barrier Terminate Fire Study Topical DBD FHA Protection Program Breaches Fire Tours I

Y Update Barrier Surveittance Proc.,

r

j FLORIDA POWER CORPORATION THERMO-LAG RESblUTION IMPLEMENTATION PLAN RESOLUTION EVALUAilON & SELECTION (SAFETY BENEFITICOST EVALUATION)

Post-Fire Mf4to 1Re-fbrmet hh-,

f p

Ef Submit l

Testing l

Submit l

MARS MAR to Support l AP-880 A {

35 Prepare Repair Activities l Test Reports l Exemption

.>~.3-E

_ Package l

{

Requests V

V4 @db.:q@iD$j

_1N[CjroutsF4 i.

d$

_PerformWork___

V V

l l

Re > ort l

15["it i

t lNd l

V

Documerstll[.f MM f

.jf, (([

Draft Procedure NRC l

T Review I

NRC FChanges"' Il 4%3MS lj8 L Work Request l

Review l

l Calculation l Ws.-(W if ($

? $ b kI T

ihis K-

+t rW i e i:f,fFire$f V

Mecatiss Y

V I

M V 2 %,, @

f (%[

l l NRC Review l Issue Procedure Installation MAR

i. Issue y is f f. p ~ Deviations' Prepare t

z j,M'

%Q:

Work Request MAR 5%g,[g Prepare 9

{j

'AP-880 > ;[

jf ppjfa, i ' y install

,_ _ Package _

%if1

-Quuf fk,N INi eh M Perform Work

.i2/i$ '$62 if I b

~

j V

1 P W

W V

V V

V THERMO-LAG FIRE BARRIERS RESOLVED I

l l

l i

V V

V V

Y Y

Revise l Update Fire Update l

Assess Fire Close Barrier l Terminate Fire Study l Topical DBD FHA l

Protection Program Breaches l Fire Tours lV Update Barrier l

[

Surveillance Proc. l f

i

STATES OF AXALYSIS CHANGES e

Re-Format and Update Operations Procedure (Completed)

-Improve the Quality of the information Presented to the Operator e Associated Circuit Calculations (Completed) e Document Changes (Drafted)

- Revise Fire Study and Topical DBD

- 90 Days After Restart e

Fire Protection Deviations (Drafted)

(,kh.!.!

Florida P9.wgr

1 FLORIDA POWER CORPORATION t

THERMO-LAG RESOLUTION IMPLEMENTATION PLAN l

RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT / COST EVALUATION)

Post-Fire

'2iiult W, h,k j

Repair Procedure Mecatiss Exemptions Ampacity Analysis Changes

@!@@ff9d Re-format l 39RMARs@1st MAR to Support l l

Submit l

Testing l

Submit AP-880 l lbf WJ Repair Activities l Test Reports l Exemption l

Requests V

s Associated "Perfbrm Wtwkh Y

V l

l Re > ort l

{

V Circuits j

l V

rw V e*

Draft Procedure NRC Calculation 1

Review l

NRC Document l l

V f

Changes l

{,

Work Request j

Review l

l Calculation l M

i Y

l I

i T

Mecatss Y

Y

[

Fire

{(

V Protection I

issue Procedure Installation MAR l NRC Review l l

Issue Deviations i

, $y,;)

Prepare Update

- < Mpj Work Request

~~~

Prepare h

MAR b

. '{

lnstall Packa n

[

AP-880 e

l Perform Work I

Y u

v v

v V

v THERMO-LAG FIRE BARRIERS RESOLVED I

I I

I i

i Y

Y Y

Y Y

Y Revise l Update Fire l Update l

Assess Fire l

Close Barrier l l

Termmate Firs Study l Topical DBDI FHA l

Protection Program l Breaches l Fire Tours I

(

IY Update Barrier l

. I Surveillac Droc l

STATUS OF CIRCUIT MODIFICATIONS

_- = = = : - ; : ~ = ::-

e Majority of the Circuit Reroutes involve Reroute of Control Circuits in the Control Complex e Targeted Completion - December 2000

- Preliminary Designs for the Circuit Modifications Have Been 1

Completed f

- MARS for Circuit Modifications Have Been Initiated

- Some Circuit Modifications Will Be Completed During Current Outage t

Horida

?RM1 i

FLORIDA POWER CORPORATION THERMO-LAG RESOLUTION IMPLEMENTATION PLAN I

RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT / COST EVALUATION) jmitEE SifRf

.: N N !h Analysis Changes Circuit Modifications WWWGMY Mecatiss Exemptions Ampacity Re-format l MARS gMARio Supportpl Submit l

Submit l

Testing l

AP-880 l Prepare TRepair ActMbes"l Test Reports l Exemption l

Associated

___Pacpage,_

3ggggyp, 4gjggg]

l Requests y

l Perform Work MMUy CM ~,

T l

f Rewrt l

T Circuits it Procedure.

NRC T

f&L Document l Calculation Review NRC l

V Changes l 7 Work Request l' l

Review l

l Calculation l kdQdl;

,$... 9.

l l

gg y

9 9

Y Protection

.f.lasue Procedure Instattaten MAR l NRC Review l hhf:& ${

Prepare Issue Deviations Update

' KWork Request

.____R__-.

Prepare l

MA 80 i

. ;]gg instan

,, {ac{ ape _,

l jg?

g

4d15!

Perform Work

$g d's $f l

$$b$

y 1 r 1r y

S$ve Wis!M 1r y

y THERMO4.AG FIRE BARRIERS RESOLVED I

l l

l l

l I

Y Y

Y Y

Y Y

l Fire Study lTopical DBDl Revise Update Fire Update l

Assess Fire l

Close Barrier l Terminate l l

I FHA l

Protection Program l Breaches l Fire Tours l lV Surveillance Proc. ll Update Bamer i

I

STATUS OF POST-FIRE REPAIR PROCEDURE M

,,1 r-

,37-o A Circuit Reroute Will Be Pre-staged to Facilitate a Post-Fire Cooldown Repair for the RW and SW Pumps e

Installation of Two 4kV Termination Boxes i

i e

The Post-Fire Cooldown Repair Procedure Will Be Prepared o

Targeted Completion - December 2000 Florida l

Powcr i

i l

.i FLORIDA POWER CORPORATION THERMO-LAG RESOLUTION IMPLEMENTATION PLAN l

RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT / COST EVALUATION) i Post-Fire j

, Analysis Changes Circuit Modifications Repair Procedure

Mecatiss, f,

Exemptions Ampacity j

n.

Re-format l Submit l

Testing l

l MARS MAR to Support l

" Submit. l AP-880 l Prepare Repair Activities l Test Reports l Exempton

___acjage,_

l Requests V

I P

Associated Perform Work V

V -

(

Re > ort l

l V

Circuits Draft Procedure NRC.

l V

j Document l Calculation Review l

NRC l

V l

Changes l Work Request l

Review l

l Calculation l

[

I l

l Fire Y

Mecatiss Y

Y I

V Protection Issue Procedure Installation MAR l NRC Review l 1ssue Deviations Prepare

[

Update Work Request MAR Prepare

~ ~ ~ 'taY ~

__ Package __.

[

AP-880 i

Ins 1

Perform Work I

iw[:

L..u.

c.a u V

1 r v

1 r Y

v v

v i

THERMO4.AG FIRE BARRIERS RESOLVED -

I I

I I

i V

V Y

Y Y

Y r

l Update Fire l Update l

Assess Fire Close 8 amer l l

[

Revise Terminate Fire Study l Topical DBDl FHA l

Protection Program Breaches l Fire Tours I

?

t Y

i Update Barrier l Surveillance Proc. I 4

x

STATUS OF MECATISS

. _.. - --, - r:

e UL Test Program Completed e Test Reports and Bounding Analysis Submitted to NRC e

Follow-up Test Completed t

e Circuit / Conduit Fleroutes Completed o

Mecatiss Installation Completed e

NRC Approved Test Results l

Florida P9.WR!

3

_._m..._

-_..m.

-_..__.____..___m FLORIDA POWER CORPORATION THERMO-LAG RESOLUTION IMPLEMENTATION PLAN RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT / COST EVALUATION)

Post-Fire Analysis Changes Circuit Modifications Repair Procedure Mecatiss Exemption.sj Ampacity g

l Submit,

l Testing l

f Re-format l MARS MAR to Support l Submit AP-880 l Prepare Repair Activites l Test Reports l Exempbop l

_ _ fac3 age __

l l

Reque-ts V

Associated Perform Work V

V J

l Report l

f V

Circuits Draf; Procedure NRC V '" I l

l Document l Calculation Review NRC l'

Y Changes l Work Request i

Review l

l Calculation l l

l Fire Y

Mecatiss V

T T

Protection issue Procedure Installation MAR l NRC Review l Issue Deviations Prepare Update Work Request

,,_ MAR, _ _

Prepare AP-880 i

install

,, g,,,

Perform Work I

Y 1 P W

1 P V

V V

V THERMO-LAG FIRE BARRIERS RESOLVED f

f I

l l

l l

V V

V Y

Y Y

i Fire Study lUpdate Fire l Update l

Assess Fire l

Close Barrier l Revise Terminate l l

Topical DBDI FHA l

Protection Program l Breaches i Fire Tours l lV Update Barrier l l

Surveillance Proc. l l

i

REACTOR BUILDIXG EXEMPTION REQUEST

-7

. = - _

o Exemption Was Submitted October 16,1995 e

Eliminated Thermo-Lag Based on Alternate Fire Protection Configuration

- Multiple Redundancies With a High Degree of Separation

- Protection Provided by Conduit

- Automatic Fire Detection l

e initial Feedback Acceptable Except in Penetration Area e

Penetration Area Resolved by Encapsulating Thermo-Lag and Exemption Request Was Withdrawn f'g Y'.. Y P

9.

STATUS OF REMAINIXG EXEMPTIOX ACTIVITIES

_ _ _ _ _ _ _ _ _ _ _ _ _ _.___ --=. -... :.r.. L. = T ~ ~

e Exemption Requests Have Been Submitted e

RAI Response Has Been Submitted e

Modifications in Support of Exemptions (Early Design Phase)

- 52 Additional Sprinkler Heads in three Plant Areas i

P I

  • e og e

e' s *

  • 7 i

FACTORS THAT MAY IMPACT TEE SCHEDULE

\\

o Ongoing Plant Modifications t

e Overall Outage Duration i

b

[

1 I*

j

.=

Florida I?9W.e.!

l b

i

THERMO-LAG RESOLUTION

SUMMARY

.. n,n.

e Accomplishments - 1996 - 5% Resolution 1

- Reactor Bldg. Radiant Energy Shields Upgraded

- Mecatiss Test Program Completed l

- Mecatiss Installation Completed i

- Exemption Request Submitted

- Analysis Changes Drafted (th.. ;);

- Circuit Modifications Preliminary Designs Prepared Florida P9.WS.!

- r

s THERMO-LAG RESOLETION

SUMMARY

i CONT'D3>

.Z Z..'_.'"._ 'E.

__Zl _ l_5..I '

~

e Near-Term Activities - 1997 (Restart) 67% Resolution

-Implement Analysis Changes

- Initiate Circuit Modifications e

Remaining Activities - 1998-2000 - 28% Resolution

- Complete Exemption Request Modifications

- Complete Circuit Modifications e

Evaluate Means to Shorten Schedule Florida l

89,We!

I

.m

. i...

. _.. ~.. -. _ ~. - - - -. - - -.... _ -. - - -. _ -.... - - -. -. - -..

o a

s FLORIDA POWER CORPORATION THERMO-LAG RESOLUTION IMPLEMENTATION PLAN RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT / COST EVALUATION)

Po.st-Fire Analysis Changes Circuit Modifications Repair Procedure Mecatiss Exemptions Ampacity]j Re-format l MARS MAR to Support l Submit l

Submst l

Testeg l

AP-880 I Prepare Repair Actnnties l Test Reports l Exernption ti Associated "PeEo~r~ ~Woh~

T T

~ Requests V

Nf Package ~

l l

l I Rexwt l

m V

Circuits Draft Procedure NRC V

Document l Calculation Review NRC l

_V '

Changes l Work Request i

Review l

l Calculation l l

Y I

a Fire Y

Mecatiss Y

V ' ' '"

V Protection issue Procedure Installation MAR l NRC Review l Issue Deviations Prepare Update Work Request

_ _ _ _,AR _

Prepare M

j AP-880 instaII Package i

Perform Work y

l Y

U V

1 P Y

Y Y

Y THERMO LAG FIRE BARRIERS RESOLVED I

l l

l l

I V

V V

V V

V l

Update Fire l Update l

Assess Fire l

Close Barrier l Revise Terminate l Fire Study l Topical DBDl FHA l

Protection Program l Breaches l Fire Tours l lV Updete Barrier Surveillance Proc.

o

)

f i

r AMPACITY l

- - - -..~.m.

m v.

e UL Tests for Mecatiss and Thermo-Lag Completed e Test Report Submitted June 26,1996 e Ampacity Evaluations of Thermo-Lag Protected Circuits in Progress t

e Corrective Actions Based on Results of Calculations

- Thermo-Lag Removal or Cable Replacement I

Florida

?9.WP.T b

. _.. _ _ _. _ _. _ _. _ _ _..... _ _ _. _ _ _ _ _. _. _.. _ _ _.... _.. _ _ _ _. _ _.... _. _ _ _. _ _ _.., ~.. _

~

s b

\\

5 FLORIDA POWER CORPORATION THERMO-LAG RESOLUTION IMPLEMENTATION PL' AN RESOLUTION EVALUATION & SELECTION (SAFETY BENEFIT / COST EVALUATION) i Post-Fire l

  1. .nalysis Changes Circuit Mods Repair Procedure Mecatiss Exemptions Ampacity l

]

Mi MAR to Support l Nub ~]

fo Submit l7C l

-8 l

Prepare Repair Activities l Re l

Exe. ton l

sociat '

_ _ f ac!"92_ _

l 1

- '9=5b Y

Perform Work V

V l

lMT_l V

C its Draft Procedure N C/)

Y l

j

, Iculat AevieA _I 4NRCg.jj Y

t 3IfN@

Work Request j

Yd Review 'i l l Calculation 3l l

Y l

Y

% cans <

Y Y-l B"

V issue Procedure Jastaliahons klhb$btb$?J' l

hER; l NRC Revewl

[

w *%6 mp e' L

.J[Nl

_.N..

Prepare Work Request AR M inetat ;

Package,_,

t i

Perform WoNj I

1 t

V 1 P V

V V

V V

Y THERMO4.AG FIRE BARRIERS RESOLVED I

I l

l l

l l

I Y

Y Y

Y Y

Y Fire Study lTopical DBDl Revise Update Fire Update l

Protection Program llClose Bamer l Termmate l Assess Fire l

3 FHA l

Breaches l Fire Tours I

[

l Y

Surveillance Proc. l Update Barrier I

{

X = COMPLETE l

SHADED = IN PROGRESS

)

.