Special Rept:On 851226,inoperable Containment Fire Spray Sys Removed from Svc to Facilitate Maint on Containment Sphere Spray Header Isolation Valve CV-92.Compensatory Measures Will Be Maintained Until Work Completed
ML20141E374
Person / Time
Site: San Onofre Southern California Edison icon.png
Issue date: 02/10/1986
From: Morgan H
SOUTHERN CALIFORNIA EDISON CO.
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
NUDOCS 8602250233
Download: ML20141E374 (1)


Text

......

d HECBVED

[f NnC:

Southem Califomia Edison Company l939

, l 3 pf 39. gy SAN ONOFRE NUCLEAR GENERATING STATION P. O. BOX t 28 SAN CLEMENTE, CALIFORNIA 92672 Q Q Q p y ("g February 10, 1986 O. S. Nuclear Regulatory Commission Region V 1450 Maria Lane, Suite 210 Walnut Creek, California 94596-5368 Attention: Mr. J. B. Martin, Regional Administrator

Dear Sir:

Subject:

Docket No. 50-206 Special Report San Onofre Nuclear Generating Station, Unit 1 Pursuant to Section 3.14.B.2.b of Appendix A, Technical Specifications to provisional Operating License DPR-13 for San Onofre Unit 1, this submittal provides the required Special Report for inoperable Fire Spray System.

-On December 26, 1985, with Unit 1 in a refueling outage, the Containment Fire Spray System was removed from service to facilitate maintenance of Containment Sphere Spray Header Isolation Valve CV-92. A continuous fire watch and backup fire suppression equipment, pursuant to Technical Specification 3.14.B.2.a, were established before the Cor,tainment Spray System was removed from service. Compensatory measures will be maintained until planned work associated _with CV-92 is completed, and the Containment Spray System is returned to service. The Containment Spray System will be retrned to service during the current refueling outage scheduled to end in May, 1986.

If there are any questions regarding the above, please contact me.

Sincerely, Mb L-F. R. Huey (USNRC Senior Resident Inspector, Units 1, 2 and 3) cc: