ML20138E203

From kanterella
Jump to navigation Jump to search
Amend 69 to License NPF-6,revising Tech Spec Table 3.8-1 Re Containment Electrical Penetration Conductor Overcurrent Protective Devices
ML20138E203
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 10/11/1985
From: Butcher E
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20138E208 List:
References
NUDOCS 8510240619
Download: ML20138E203 (15)


Text

. ' o ne.

4 UNITED STATES o

4 g

NUCLEAR REGULATORY COMMISSION 3

o y

E WASHINGTON, D. C. 20555

'%4...../

1 ARKANSAS POWER & LIGHT COMPANY DOCKET NO. 50-368 ARKANSAS NUCLEAR ONE, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 69 License No. NPF-6 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Arkansas Power & Light Company (the licensee) dated March 13, 1985, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in confonnity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

8510240619 851011 DR ADOCK 05000368 p

PDR

' 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-6 is hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 69, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION Edward J.

utcher, Acting Chief Operating Reactors Branch #3 Division of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance: October 11, 1985 e

, +., - - - - - - - - _ - - - - - _ -, - - - - -,. - -,

ATTACHMENT TO LICENSE AMENDMENT NO. 69 FACILTIY OPERATING LICENSE NO. NPF-6 DOCKET NO. 50-368 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by amendment number and contain vertical lines indicating the areas of change. The corresponding overlead pages are also provided to maintain document completeness.

Remove Pages Insert Pages 3/6 8-13 3/6 8-13 3/4 8-14 3/4 8-14 3/4 8-15 3/4 8-15 3/4 8-15a 4

3/4 8-16 3/4 8-16 3/4 8-16a 3/4 8-17 3/4 8-17 3/4 8-17a 3/4 8-18 3/4 8-18 3/4 8-18a 3/4 8-20 3/4 8-20 m.

i

a*

TABLE 3.8-1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES r

Primary Backup Location Device Device of System Number Number Devices Powered A. 6900 VAC 152-11 152-13, or Switchgear 2H1 RCP 2P32A 152-14, or 152-15 152-12 152-13, or Switchgear 2H1 RCP 2P320 152-14, or 152-15 152-21 152-23, or Switchgear 2H2 RCP 2P328 152-24, or 152-25 1

152-22 152-23, or Switchgear 2H2 RCP 2P32C 152-24, or 152-25 B. 480 VAC 52-131 None, circuit 2B1 Containment shall not be Building energized Crane 2LM2 unless p~. ant is shutdown

'**52-523 52-512 285 Pressurizer L

Proportional Heater Bank 1 52-533 52-512 285 Hydrogen Recombiner 1 52-623 52-612 286 Pressurizer Proportional Heater Bank 2 ARKANSAS - UNIT 2 3/4 8-13 Amendment No. 35, 69 l

j

V

. v" L

i TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-5104 52-51H5 MCC 2B51 Containment Recirculating-Fan 2VSF31C-1 52-51E2.

52-51H6 MCC 2851 Reactor Drain Tank Drain Iso.

Valve 2CV-2201-1 52-51E4 52-51C1 MCC 2851 Pressurizer Relief Valve Isolation s

2CV-4730-1 52-51F1 52-51H7 MCC 2851 RCP Controlled 81eedoff Iso.

Valve 2CV-4846-1 52-51F2 52-51H8 MCC 2851 Safety Injection Tank 2T2A Discharge MOV 2CV-5003-1 52-51G2 52-51L2 MCC 2851 Shutdow'n Cooling Return Header Iso.

Valve 2CV-5084-1 52-51G3 52-51H9 MCC 2851 Check Valve Leakage Drain Valve 2CV -

5105-1 52-51H1 52-51L3 MCC 2851 Safety Injection Tank 2T2B Discharge MOV 2CV-5023-1 ARKANSAS - UNIT 2 3/4 8-15 Amendment No. 35, 69

1 TABLE 3.8-1 l

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered A. 6900 VAC 152-11 152-13, or Switchgear 2H1 RCP 2P32A 152-14, or 152-15 152-12 152-13, or Switchgear 2H1 RCP 2P32D 152-14, or 152-15 152-21 152-23, or Switchgear 2H2 RCP 2P32B 152-24, or 152-25 152-22 152-23, or Switchgear 2H2 RCP 2P32C 152-24, or 152-25 B. 480 VAC 52-131 None, circuit 2B1 Containment shall not be Building energized Crane 2LM2 unless plant is shutdown

' d'* 52-523 52-512 285 Pressurizer Proportional Heater Bank 1 52-533 52-512 285 Hydrogen Recombiner 1 52-623 52-612 286 Pressurizer Proportional Heater Bank 2 ARKANSAS - UNIT 2 3/4 8-13 Amendment No. 35, 69

s, TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-633 52-612 286 Hydrogen Recombiner 2 52-731 52-732 287 MCC 2871 52-824 52-823 2B8 MCC 2881 52-922 52-912 289 Pressurizer Backup Heater Bank 3 52-923 52-912 289 Pressurizer Backup Heater Bank 5 52-1022 52-1012 2810 Pressurizer Backup Heater Bank 4 52-1023 52-1012 2B10 Pressurizer Backup Heater Bank 6 C. 480 VAC MCC 52-51A4 52-51H2 MCC 2851 Reactor Cavity

.ag.

Cooling Fan 2VSF34A-1 42-5182

\\

52-51H3 MCC 2851 Containment Sump Isolation MOV2CV-2060-1 I

52-5103 52-51H4 MCC 2851 Containment Recirculating i

Fan 2VSF31A-1 ARKANSAS - UNIT 2 3/4 8-14 Amend:nent No. 35, 69 l

L.

.r I

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-5104 52-51HS MCC 2851 Containment Recirculating-Fan 2VSF31C-1 52-51E2 52-51H6 MCC 2851 Reactor Drain Tank Drain Iso.

Valve 2CV-2201-1 52-51E4 52-51C1 MCC 2851 Pressurizer Relief Valve Isolation 2CV-4730-1 52-51F1 52-51H7 MCC 2851 RCP Controlled Bleedoff Iso.

Valve 2CV-4846-1 52-51F2 52-51H8 MCC 2B51 Safety Injection Tank 2T2A t

Discharge MOV 2CV-5003-1 52-51G2 52-51L2 MCC 2851 Shutdown Cooling Return Header Iso.

Valve 2CV-5084-1 52-51G3 52-51H9 MCC 2B51 Check Valve Leakage Drain Valve 2CV-5105-1 52-51H1 52-51L3 MCC 2851 Safety Injection Tank 2T2B Discharge MOV 2CV-5023-1 ARKANSAS - UNIT 2 3/4 8-15 Amendment No. 35, 69

)

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-51K1 52-51L4 MCC 2851 Containment Sump Isola-tion MOV 2CV-5647-1 52-51K2 52-51J4 MCC 2851 Pressurizer Relief Iso.

Viv. 2CV-4741-1 l

i ARKANSAS - UNIT 2 3/4 8-15a Amendment No. 35, 39 ne,.w,,.

n..-

.e 1

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-51K3 52-51L5 MCC 2851 Containment Air Purge Isolation Valve 2CV-8289-1 52-51K4 52-51L6 MCC 2851 Containment Air Purge Isolation Valve 2CV-8291-1 52-51L1 52-51L7 MCC 2851 Containment Vent Header Isolation Valve 2CV-2401-1 52-51M1 52-51L8 MCC 2851 Regenerative Heat Exchanger Inlet Valve 2CV-4821-1 52-51N3 52-51L9 MCC 2B51 Reactor Cavity Cooling Fan Bypass Damper 2HCD8243-1 52-53G1 52-53A5 MCC 2853 Containment Cooling Fan Bypass Damper Motor 2VCDM8203-1 52-53G2 52-53A6 MCC 2B53 Containment Cooling Fan ~

Bypass Damper Motor 2VCDM8209-1 52-53H3 52-53H2 MCC 2853 Pressurizer Spray Valve 2CV-4652 ARKANSAS - UNIT 2 3/4 8-16 Amendment No. 23, 69 l

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered j

52-53L1 52-53K5 MCC 2853 Containment Cooling Fan 2VSFIA 52-53L2 52-53K6 MCC 2B53 Containment' Cooling Fan 2VSF1B a

ARKANSAS - UNIT 2 3/4 8-16a Amendment No. 33, 69

. ~

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES 1

Primary Backup Location Device Device of System Number Number Devices Powered 52-54G2 52-54C5 MCC 2854 H2 Purge Containment Iso. Valve 2CV-8233-1 52-54G3 52-54B4 MCC 2854 H2 Purge Containment Iso. Valve 2CV-8259-2 52-54J2 52-54J3 MCC 2854 Containment Elevator Motor 2MM6 52-54K2 52-54J4 MCC 2854 Containment Building Lighting Panel 27 LA 52-54K3 52-54J8 MCC 2854 RCP 2P3A 011 Lift Pumps 2P63Al & A2 52-54K4 52-54F3 MCC 2854 RCP 2P328 Oil Lift Pumps 2P6381 & B2 52'-61A4 52-61H3 MCC 2B61 Reactor Cavity Cooling Fan 2VSF348-2 52-6103 52-61H4 MCC 2861 Containment Recirculating Fan 2VSF318-2 52-6104 52-61H5 MCC 2861 Containment Recirculating Fan 2VSF310-2 ARKANSAS - UNIT 2 3/4 8-17 Amendment No. 35, 63 4

,,,_....___._._..r-

.,,,_c,c,.-,---.,,_.m.

7m. rm.--

.--r

w

..r TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device ~

Device of System Number Number Devices Powered 52-61F2 52-61H6 MCC 2B61 Safety Inject.

Tank 2T2C Discharge MOV 2CV-5043-2 52-61G2 52-61K8 MCC 2B61 Check Valve Leakage Drain Valve 2CV-5106-2

's.

mr i

ARKANSAS - UNIT 2 3/4 8-17a Amendment No. 33,69

b TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-61G3 52-61H7 MCC 2861 Reactor Coolant System Charging Line MOV 2CV-4831-2 52-61G4 52-61H8 MCC 2B61 Reactor CoolantSysteml Charging Line MOV 2CV-4827-2 52-61H1 52-61K3 MCC 2861 Safety Inj.

Tank 2T2D Dis.

MOV 2CV-5063-2 4

52-61H2 52-61K7 MCC 2861 Containment Sump Iso.

MOV 2CV-5648-2 52-61L2 52-6102 MCC 2B61 Pressurizer Relief Iso.

V1v. 2CV-4731-2 i

52f6hl3 52-61K4 MCC 2861 Letdown Line Stop Valve 2CV-4820-2 52-61L4 52-61L1 MCC 2861 Pressurizer l

Spray Viv.

2CV-4651 52-61N2 52-61K6 MCC 2861 Reactor Cavity Cooling Fan' Damper 2HCD 8244-2 j

52-62E5 52-62C2 MCC 2862 Shutdown Cooling 4

Return Header Iso. Valve 2CV-5086-2 l

ARKANSAS - UNIT 2 3/4 8-18 Amendment No. 35, 69 i

J

m TABLE 3.8-1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-63F2 52-63E1 MCC 2B63 Containment Chilled Water Isol. Valve 2CV-3850-2 A

i t-e ARKANSAS - UNIT 2 3/4 8-18a Amendment No. 35, 69

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE DEVICE LOCATION OF SYSTEM NUMBER NUMBER DEVICES POWERED 52-63G4 52-63E2 MCC 2B63 RCP Cooler Iso. Vaive 2CV-5254-2 52-63L1 52-63J1 MCC 2B63 Containment Cooling Fan 2VSF1C 52-63L2 52-63J2 MCC 2B63 Containment Cooling Fan 2VSF1D 52-6404 52-64B3 MCC 2864 Containment Cooling Fan Bypass Damper Motor 2UCDM 8216-2 52-64E3 52-6484 MCC 2B64 Pressurizer Auxiliary Spray MOV 2CV-4824-2 52-64E4 52-64C2 MCC 2B64 Containment Cooling Fan Bypass Damper i

Motor 2VCDM 8222-2 l

52-64J1 52-64B1 MCC 2864 RCP 2P32C Oil Lift Pumps 2P63C1 & C2 52-64K1 52-64H2 MCC 2B64 RCP 2P32D Oil Lift Pumps 2P63D1 & D2 l

ARKANSAS - UNIT 2 3/4 8-19 Amendment No. 35

E

?*.

(

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR 0VERCURRENT PROTECTIVE DEVICES Primary Backup Location ~

Device Device of System Number Number Devices Powered D.

480/277 21PA-19 52-15C1 Primary -21PA Space Heater Backup -2815 for RCP 2P32A 21PA-25 52-15C1 Primary -21PA Space Heater Backup -2815 for RCP 2P32B 21PA-31 52-15C1 Primary -21PA Space Heater Backup -2815 for RCP 2P32C 21PA-20 52-15C1 Primary -21PA Space Heater Backup -2815 for RCP 2P32D E. 125 VDC l

72-0318 72-0320 DC Control Containment Center Bldg 125 VDC 2003 Lighting Panel 22DA 72-26A3 72-26A2 DC MCC Pressurizer 2026 Vent Valve 2CV-474D-2 72-27A3 72-27A2 DC MCC Pressurizer 2D27 Vent Valve 2CV-4698-1 F.

240 VAC CEA 1 CB3021 2C72 CEA 1 i

CB101 CB3022 ARKANSAS - UNIT 2 3/4 8-20 Amendment No. 25, 69 l

I

"