Att:chment 1 Page 1 of 2 SNRC-1220 TABLE 3.3.7.9-l FIRE DETECTION INSTRUMENTATION SAFETY RELATED' ZONE TOTAL NUMBER OF INSTRUMENTS
- HEAT SMOKE FLAME (x/y)
(x/y)
(x/y) 1.
Control Building Emergency Seitchgear Room 101 0/6 6/0 Emergency Switchgear Room 102 0/6 6/0 Emergency Switchgear Room 103 0/6 6/0 Battery Room A 0/2 3/0 Battery Room B 0/2 4/0 Battery Room C 0/3 5/0 Diesel Generator Room 101 0/9 1/0##
3/0 Diesel Generator Room 102 0/11 1/0##
3/0 Diesel Generator Room 103 0/10 1/0##
3/0 Relay Room 0/24 14/0 HVAC Equipment Roon El. 44'-0" 3/0 HVAC Equipment Room El. 63'-0" 5/0 Chiller Equipment Room El. 44'-0" 10/0 Chiller Equipment Room El 63'-0" 10/0 CRAC - FLT 2A El. 63'-0" 4/0 CRAC - FLT 2B El. 63'-0" 4/0 CRAC CR Exh El. 63'-0" 1/0 l
Corridor 8 El. 25'-0" 5/0 Corridor 9 El. 25'-0" 3/0 2.
Reactor Building Primary Containment #
4/0 Secondary Containment El. 8'-0" 30/0 Secondary Containment El. 40'-0" 38/0 l
Secondary Containment El. 63'-0" 14/0 Secondary Containment El. 78'-7" El. 95'-3", & 101'-6" 4/0 42/0 Main Steam Tunnel El. 76'-5" 11/0**
Secondary Containment El. 112'-9" 2/0 55/0 Secondary Containment El. 126'-9" 7/0 Secondary Containment El. 150'-9" & 159'-9" 5/0 27/0 Secondary Containment El. 175'-9" 3/0##
MG Room 111 E1. 150'-9" 4/0 MG Room 112 El. 150'-9" 3/0 MG Room 113A El. 161'-0" 4/0 MG Room 113B El. 161'-0" 3/0 MCC West Room El. 112'-9" 2/0 MCC East Room El. 112'-9" 3/0 F512110265 851209 DR ADOCK 05000322 p
. Attach =cnt 1 Page 2 of 2-
'~
SNRC-1220 TABLE 3.3.7.9-1 (continued)
' FIRE DETECTION INSTRUMENTATION i
SAFETY RELATED ZONE TOTAL NUMBER OF INSTRLTENTS*
HEAT SMOKE FLAME (x/y)
(x/y)
(x/y)
Remote Shutdown Panel Enclosure El 63'-0" 0/2 HPCI Turbine El 8'-0" 0/6 RCIC Turbine El 8'-0" 0/5
]
1TK607R Horizontal Cable' Trays 2/0 ITX600R Vertical Cable Trays 5/0 1
RBSVS - FLT 1A El 112'-9" 2/0 RBSVS - FLT 1B El 112'-9" 2/0 MCC Room El. 40'-0" 2/0 3.
Turbine Building i
Electrical Manhole No. IEl 5'-8" 0/2 2/0 (located in normal switchgear room) 4.
Screenwell Pump House Pump Cubicle A 3/0##
Pump Cubicle B 3/0##
i
}
5.
Yard
~
i Emergency Diesel F.O. Transfer Pump i
House A 2/0 j
Emergency Diesel F.O. Transfer Pump House B 2/0 Emergency Diesel F.O. Transfer Pump House C 2/0 i
i TABLE NOTATIONS
- (x/y):
x is number of Function A (early warning area fire detection and notification) instruments. y is. number of Function B (actuation of fire suppression system and notification) instruments.
f.
The fire detection instruments located within the primary containment are not required to be OPERABLE during the performance of Type A Containment Leakage Rate Tests.
1 Heat detectors are non-restorable spot type fixed temperature.
Includes projected beam type smoke detector A
1
=
-