ATTACHMENT Consumers Power Company Big Rock Point Plant' Docket 50-155 SEMIANNUAL RADI0 ACTIVE EFFLUENT RELEASE REPORT JULY THROUGH DECEMBER 1985 February 28, 1986 l

12 Pages IC0286-0037-NLO4 8603120002 360228 PDR ADOCK 0S000155 r

PDR R

9 o

1 BIG ROCK POINT SEMIANNUAL EFFLUENT REPORT JULY - DECEMBER 1985 This report provides information relating to radioactive effluent releases and solid radioactive waste disposal operations of the Big Rock Point Plant during the period of July through December 1985 in the format contained in Plant Technical Specification 6.9.2.

1.

Supplemental Information a.

Batch Release Information relating to batch and continuous releases of liquid and gaseous effluents is provided in Table 1.

b.

Abnormal Releases None.

2.

Gaseous Effluents Table 2a presents a summary of all gaseous radioactive effluents released during the period. Release totals for each radionuclide determined to be present in gaseous effluents are contained in Table 2b.

Gaseous releases of I-132, I-133 and I-135 were determined from the ratios of monthly short-lived halogen analyses to the weekly I-131 analyses. The maximum noble gas release rate was 3.96E+03 uCi/second. There were no I-134 releases.

3.

Liquid Effluents Table 3a presents a summary of all liquid radioactive effluents released during the period. Release totals for each radionuclide determined to be present in liquid effluents are contained in Table 3b.

The maximum concentration was 4.80E-07 uCi/ml.

4.

Solid Waste Table 4 presents a summary of radioactive waste shipped offsite for burial during the period. Total volume of radioactive waste shipped offsite during the last six months of 1985 is 1451.0 cubic ft.

5.

Radiological Impact on Man Potential doses to individuals and populations were calculated using GASPAR and LADTAP computer codes. The annual totals for curies released were irput per nuclide.

a.

Doses to individuals in unrestricted areas received from water related exposure pathways are 9.01E-02 mrem maximum total body dose (adult) and 1.40E-01 mrem maximum organ dose (teenage liver dose).

IC0286-0052A-HP01

{

R b.

The maximum offsite air doses are 4.10E-01 mrads for beta and 7.12E-01 mrads for gamma.

c.

The most restrictive organ dose to the general popul'ation is 4.05E-01 mrem, infant thyroid dose. The average thyroid dose to individuals within a distance of 50 miles of the site from radio-active iodine and radioactive material in particulate form from major pathways of exposure is 7.92E-04 mrem.

d.

Total body doses to the population and average doses to individuals in the population from receiving water related pathways to a dis-tance of SC miles from the site are 4.27E-02 manRem and 2.77E-04 mrem respectively.

e.

Total body doses to the population and average doses to individuals in the population from gaseous effluents to a distance of 50 miles from the site are 1.16E+00 manRem and 7.53E-03 mrem respectively.

6.0 ODCM Changes The following are changes to the Big Rock Point ODCM. They were reviewed by PRC and approved by the Plant Superintendent on 2/17/86. The corrected pages are attached. The following is a discussion of the changes.

Page 1, A Technical was added to clarify Specification.

Page 8, 1.2.2.1 Equation 1.1 corrected to 1.3.

Page 9, 1.2.2.2 Printing errors deleted.

i Page 10, 1.2.2.3 Lamda symbol replaced in equation I.10.

printing ommission.

Page 12, Eq. 1.11 Equation I.10 corrected to I.11.

Page 15, 1.4 Technical added to clarify Specification.

lage 16, 4.0 Palisades changed to Big Rock Point Page 17 PWR changed to BWR Page 17, DI.0 Equation I.4 corrected to I.16.

Page 23, First paragraph clarified and missing data added. GASPAR code was run with Table 1.1 source terms to supply data.

Pages 28-35 Table 1.3 added.

Incorrectly omitted from submittal Pages 36-37 Table 1.4 and 1.4a added. Table 1.4 was incorrectly omitted from submittal and 1.4a was added for clarification.

Pages 50-51 Table 1.9 corrected for 1985 land use census critical receptor changes.

Page 52, II.A.I.

Technical was added to clarify Specification.

Page 53, eq. 2.2 Typo on duplicate subscript corrected.

Page 56, C.1 Technical was added to clarify Specification.

Page 57, C.2 Technical was added to clarify Specification (twice)

IC0266-0052A-HP01

- - -... -. - ~ - -

b 3

~

Page 58,1eq 2.6.

Summation symbol omitted in submittal Page 59, eq 2.8.

Summation symbol omitted in submittal Page 59, 2.2 Equation 2.13 corrected to 2.10.

Page 59, 2.2 Equations 2.14 and 2.11 corrected to 2.9 and 2.6.

Page 59, eq. 2.10 Summation symbol omitted in submittal Page 63, Second paragraph clarified'and missing data added. LADTAP code was run using Table 1.1 source term input to' supply data.

Page 63, III.A Technical added to clarify specification.

All changes are self explanatory.

'I I

IC0286-0052A-HP01

~..

\\

t l

i i

i 4

TABLE 1 i

BIG ROCK POINT I

BATCH RELEASES 4

July 1985 to December 1985

)

A.

CASEGOS - Continuous Elevated Releases J

5.

LIQUID Units 3rd Quarter 4th Quarter 4

l Nuseber of Releases 10 18 Total Release Time Min 2976 4185 Maximum Release Time Min 961 1240 l

Average Release Time Min 298 233 1

Minimum Release Time Min 178 22 1

t 1

MIO286-0011A-HP01

D TABLE 2a BIG ROCK POINT PLANT EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT GASEOUS EFFLUENTS - SUMMATION OF ELEVATED RELEASES July 1985 to December 85 Est Total A.

FISSION AND ACTIVATION GASES

' Units Qtr 3rd Qtr 4th Error %

1.

Total release Ci 9.72E+03 3.64E+03 10.99 2.

Average release rate for period uC1/see 1.22E+03 4.58E+02 3.

Percent of Tech Spec Limit 1.22E-01 4.58E-02 B.

10 DINES 1.

Total Iodine-131 Ci 7.77E-03 1.64E-03 4.03 2.

Average release rate for period uCi/sec 9.78E-04 2.06E-04 3.

Percent of Tech Spec Limit 8.15E-02 1.72E-02 C.

PARTICULATES 1.

Particulates with half-life l

>8 days Ci 5.56E-04 1.92E-03 10.89 i

2.

Average release rate for period uCi/sec 6.99E-05 2.41E-04 3.

Percent of Tech Spec Limit 5.26E-03 1.12E-02 4.

Gross alpha radioactivity Ci 4.50E 2.33E-07 D.

TRITIUM 1.

Total Release Ci 2.45E+00 2.20E+00 2.

Average release rate for period uCi/sec 3.08E-01 2.76E-01 3.

Percent of Tect Spec Limit 1.28E-02 1.15E-02 E.

1.

Percent of Gaseous Effluents of

' 1.53E+00 ( 6.49E-01 Appendix I Values MIO286-0011A-HP01

I TABLE 2B BIG ROCK POINT EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT GASEOUS EFFLUENTS - ELEVATED RELEASES July 1985 to December 1985 I

1.

FISSION GASES Units Qtr 3rd Qtr 4th Krypton-83m Ci 3.10E+02 8.81E+01 Krypton-85 Ci 8.89E-01 1.81E+00 Krypton-85m Ci 5.41E+02 1.52E+02 Krypton-87 Ci 1.16E+03 3.98E+02 Krypton 88 Ci 1.25E+03 3.86E+02 Krypton 89 Ci 1.48E+02 6.78E+01 Krypton 90 Ci 6.82E+01 5.26E+01 Xenon-131m Ci 1.12E+00 4.92E-01 Xenon-133 Ci 1.01E+03 2.02E+02 Xenon-133m Ci 2.72E+01 7.84E+00 Xenon-135 Ci 2.19E+03 5.66E+02 Xenon-135m Ci 5.34E+02 1.82E+02 Xenon-137 Ci 2.56E+02 1.13E+02 i

Xenon-138 Ci 1.84E+03 1.13E+03 l

Xenon-139 Ci 1.01E+02 7.27E+01 Nitrogen-13 Ci 2.87E+02 2.22E+02 Total for Period Ci 9./*'.+03 3.64E+03 I

i i

MIO286-0011A-HP01 l

TABLE 2B BIG ROCK POINT i

EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT

~ GASEOUS EFFLUENTS - ELEVATED RELEASES July 1985 to December 1985 2.

10 DINES Units Qtr 3rd

-Qtr 4th Iodine-131 Ci 7.77E-03

'1.64E-03 Iodine-132 Ci 5.16E-03

'6.15E-03 Iodine-133 Ci 8.62E-03 7.82E-03 Iodine-134 Ci Iodine-135 Ci 1.03E-02 1.30E-02 Total for Period Ci 3.19E-02 2.86E-02

3. PARTICULATES Chromium-51 Ci 1.10E-04 2.80E-04 Manganese-54 Ci 1.55E-05 6.10E-05 Iron 59 Ci 4.00E-06 Cobalt-60 Ci 2.06E-05 1.56E-04 Zine-65 Ci 4.95E-06 2.96E-04 Silver-110m Ci 1.31E-06 1.39E-04 Cesium-136 Ci Cesium-137 Ci 4.81E-05

~2.6SE-04 Barium-140 Ci 1.97E-04 3.57E-04 Mercury-203 Ci MIO286-0011A-HP01

s TABLE 2B BIG ROCK POINT EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT GASEOUS EFFLUENTS - ELEVATED RELEASES July 1985 to December 1985

\\

3.

PARTICULATES (cont'd)

Units Qtr 3rd Qtr 4th Cesium-134 Ci 1.91E-05 1.02E-04

' Cobalt-58 Ci 4.64E-06 Cerium-141 Ci 1.58E-06

    • Net Beta Ci 1.39E-04 2.53E-04
  • Lanthanum-140 Ci 5.57E-04 1.88E-03
  • Bromine-82 Ci 2.32E-03 1.07E-03
  • Cesium-138 Ci 7.70E-01 2.03E-01
  • Molybdenum-99 Ci 7.34E-06 4.47E-04
  • Barium-139 Ci 1.11E-03
  • Neptunium-239 Ci 7.47E-04
  • Strontium-91 Ci 2.29E-04 i

j Total for Period Ci 5.56E-04 1.92E-03 Note.

  • Particulates with half-lives <8 days, not reflected in overall isotopic totals.
    • Net beta was entered as Sr90 on GASPAR input for conservative dose calculations.

A MIO286-0011A-HP01 l

TABLE 3a BIG ROCK POINT PLANT EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT LIQUID EFFLUENTS - SUMMATION OF ALL RELEASES July 1985 to December 1985 Est Total A.

FISSION AND ACTIVATION PRODUCTS Units 3rd Qtr 4th Qtr Error %

1.

Total release (not including tritium, gases, alpha)

Ci 4.99E-02 7.88E-02 4.30 2.

Average diluted concentration during period uCi/ml 2.37E-09 4.61E-09 3.

Percent of Tech Spec Limit 3.11E-01 1.02E-01 B.

TRITIUM 1.

Total Release Ci 2.80E-01 9.20E-01 4.01 l

,2.

Average diluted concentration during period uCi/ml 1.33E-08 5.38E-08 3.

Percent of Tech Spec Limit 4.43E-04 1.79E-03 C.

DISSOLVED AND ENTRAINED GASES 1.

Total Release Ci 2.00E-03 1.47E-04 4.47 l

2.

Average diluted concentration during period uCi/ml 9.52E-11 8.59E-12 3.

Percent of Tech Spec Limit 4.76E-05 4.30E-06 D.

GROSS ALPHA RADIOACTIVITY (total release)

Ci 2.61E-06 6.35E-06 E.

VOLUME OF WASTE RELEASED (prior to dilution) liters 1.67E+05 2.60E+05 F.

VOLUME OF DILUTION WATER USED DURING '

j PERIOD l

liters 2.10E+10 1.71E+10 l G.

PERCENT OF APPENDEX I ANNUAL LIMIT f

l' 9.65E-01 f 1.98E+00 l MIO286-0011A-HP01

~

TABLE 3B BIG ROCK POINT PLANT EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT LIQUID EFFLUENTS July 1985 to December 1985 1.

NUCLIDES RELEASED Units Qtr 3rd Qtr 4th Cesium-137 Ci 1.00E-02 1.16E-02 Cobalt-58 Ci 9.45E-04 Manganese-54 Ci 3.05E-03 1.01E-02 Cobalt-60 Ci 4.74E-03 1.88E-02 Cesium-134 Ci 1.21E-03 8.25E-03 Iron-59 Ci 1.71E-04 1.24E-03 Lathanum-140 Ci Zine-65 Ci 7.75E-05 1.20E-03 Strontium-92 Ci 3.07E-05 2.87E-05 Iodine-131 Ci 1.79E-02 1.85E-03 Silver-110m Ci 1.05E-04 9.33E-04 l

Iodine-133 Ci 2.11E-03 i I

Molybdenum-99 i

Ci 1.59E-04 i Cesium-136 Ci 1.61E-04 l

Chromium-51 Ci i

1.04E-03 9.01E-05 i

1 i

MIO286-0011A-IIP 01 i

i r,

g.--n

--,,w._,----.r.-,

e

..w..,-..,rm-


r

- - - - - = - - _ - - - - - - * - - - - -., - - - - - -

TABLE 3B (cont'd)

BIG ROCK POINT PLANT EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT LIQUID EFFLUENTS July 1985 to December 1985 1.

NUCLIDES RELEASED Units Qtr 3rd Qtr 4th Sodium-24 Ci 5.26E-05 Iodine-135 Ci 1.37E-04 Mercury-203 Ci 1.63E-04 Niobium-95 Ci 2.32E-05 2.74E-06 Neptunium-239 Ci 1.59E-03 Strontium-89 Ci 8.67E-05 3.50E-04 Strontium-90 Ci 1.42E-04 3.68E-04 Net Unidentified Beta Ci 7.15E-03 2.29E-02 Total for Period (above)

Ci 4.99E-02 7.88E-02 I

Ci 2.00E-03 1.47E-04

)

Xenon-133 MIO286-0011A-HP01

TABLE 4 BIG ROCK POINT PLANT EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT SOLID WASTE AND IP. RADIATED FUEL SHIPMENTS July 1985 to December 1985 A.

SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (not irradiated fuel)

UNITS

'1.

Spent resins, filter sludges, evaporator 3

5.4 m

bottoms, etc.

ft3 189.0 Ci 81.0 3

2.

Dry compressible waste, contaminated m

35.8 equipment, etc.

ft3 1262 Ci 0.71 3

3.

Irradiated components, control rods, etc.

m ft3

-None-Ci' 4.

Other (describe) m3 ft3

-None-Ci B.

SOLID WASTE SHIPMENT DISPOSITION Date of Shipments Mode of Transportation Destination 8/9/85 and 12/6/85 Truck Barnwell, SC 11/21/85 Truck Richland, WA C.

IRRADIATION FUEL SHIPMENT DISPOSITION Date of Shipments Mode of Transportation Destination

- NOKE -

MIO286-0011A-HP01