ML20137X056

From kanterella
Jump to navigation Jump to search
Forwards LERs 85-028-00,85-029-00,85-030-00 & 85-031-00
Date released: 05/30/2020 Download: ML20137X056


:on 851101,Div 1 RWCU Isolation Occurred.Caused by Actuation of Area Selection Switch When Operator Took RWCU Room Temps for Surveillance Test Procedure STP-000-001 & Failed to Place Switch in Bypass.Isolation Reset
ML20137X140
Person / Time
Site: River Bend 
Issue date: 12/01/1985
From: Shirey S
GULF STATES UTILITIES CO.
To:
References
Download: ML20137X140 (2)
:on 851101,Div 1 RWCU Sys Isolation Occurred. Caused by Spurious Rwcs Filter Demineralizer Room 1 High Temp Alarm.Rwcu Sys Placed Back in Operation.Mod in Progress to Correct Flashing & Noise Spiking Problems
ML20137X118
Person / Time
Site: River Bend 
Issue date: 12/01/1985
From: Shirey S
GULF STATES UTILITIES CO.
To:
References
Download: ML20137X118 (2)
:on 851031,isolation of Div 1 RWCU Sys Occurred Causing Closing of Four Outboard Isolation Valves.Caused by Spurious Opening of Contacts on Riley Temp Modules.Mods to Temp Modules to Reduce Transient Susceptibility Begun
ML20137X109
Person / Time
Site: River Bend 
Issue date: 11/30/1985
From: Bysfield G
GULF STATES UTILITIES CO.
To:
References
Download: ML20137X109 (3)
:on 851030,main Supply Breaker in 13.8 Kv Normal Switchgear Mistakenly Tripped,Causing Several Actuations.Caused by Personnel Error.Equipment Returned to Normal Operation
ML20137X069
Person / Time
Site: River Bend 
Issue date: 11/29/1985
From: Bysfield G
GULF STATES UTILITIES CO.
To:
References
Download: ML20137X069 (2)
Forwards LERs 85-028-00,85-029-00,85-030-00 & 85-031-00
ML20137X052
Person / Time
Site: River Bend 
Issue date: 11/27/1985
From: Booker J
GULF STATES UTILITIES CO.
To:
NRC OFFICE OF ADMINISTRATION (ADM)
References
Download: ML20137X052 (1)