TOLEDO EDISON DAVIS-BESSE NUCLEAR POWER STATION UNIT NO. I SAFETY-RELATED PIPING SYSTEM SUPPORT AND HANGER DISCREPANCIES

SUMMARY

REPORT --

REVISION 5 AUGUST 16, 1985 4

1 l

SECTION I.0 AUXILIARY FEEDWATER PUMP TURBINE STEAM SUPPLY PIPING SYSTEM i

l i

Fahup.

1 AFPTSS SYSTEM EhSlhEEFlhE FlhtihSS U2/13/B5 REV. 5 SUFFORT NO.

DESCRIFTION DATE h:R NO.

DISF'D RESF bEITTEh thD EEL-19-H147 SWAf STRUT FULLED FROM WALL 03/01/55 85-0016 Y

SJD A3 LODSE Ah: HOR E0LTS HUTS 03/13/85 55-0018 Y

EF EED-19-H34 DEF05.MED STAN:HION 03/13/E5 85-0019 Y

SNF EED-19-H32 h0N-CD:E eELD ON WRAPFER FLATE TO PIFlh5 WELD 03/27/B5 E5-0026 Y

5J0 EBD-19-H59 LEFECTIVE MECHAhlCAL ShUEEER 04/11/95 85-0032 Y

SJO EBD-19-H5B EICESSIVE LATERAL MOVEMENT OF SUSFORT 04/11/B5 SRSS-79 Y

SJD EEL-19-H144 HYDRAULIC SNJ5PER PISTON ROD BROKEN 04/1B/B5 85-0038 V

SJO Ei!-19-H136 TWELVE (121 ANCHOR BOLTS IN LIEU OF SEVEN 01 SFECIFIED 04/30/E5 E5-0042 Y

SMF EED-19-H54 WELD DETAIL INACCURATE 04/30/85 85-0043 Y

6NF EED-19-H142 LODSE AN: HOR BOLT NUT 05/01/85 B5-0045 Y

GMF EPD-19-H51 WALL INTERFERENCE WITH SUPPORT MEMBER 05/08/85 85-0052A Y

RAA

(

EED-19-H132 LODSE ANCHOR BOLTS, BASEPLATE 6AP 05/16/85 B5-0019A Y

6NF EBD-19-H32 LODSE ANCHOR BOLTS, SNUBBER PIPE CLAMP MIS-All6MED, 05/16/85 85-0019A Y

SJO WASHERS MISSINS EBD-19-H2B PIPE SADDLES DEFORMED 05/16/85 85-0019A Y

SJO EBD-19-H25 SHEARED BOLT 05/16/85 85-0019A Y

SJG EED-19-H26 WALL CRACK 05/16/85 85-0019A Y

SJO EED-19-H14 SNUPiER PIPE CLAMP MIS-Atl6MED 05/16/85 85-0019A Y

530 EED-19-H135 LODSE ANCHOR BOLTS, ONE BOLT DID NOT TORGUE 05/16/65 65-00194 Y

BF EID-19-H66 LOOSE ANCHOR POLTS 05/16/85 35-0019A Y

6F EED-19-H50 RESTRAlWT FULLED FRDM WALL 05/16/B5 85-0019A Y

GNF EID-19-H49 SWAY STRUT PULLED FROM MALL 05/16/85 85-0019A Y

6NF EBD-19-H142 RESTRAINT PULLED FRDM WALL 05/16/85 85-0019A Y

ShF EPD-19-H67 LOOSE ANCHOR BOLTS 05/16/B5 85-0019A Y

SF EBD-19-H145 SWAY STRUT JAM NUT LODSE, LOOSE AhCHOR BOLT 05/17/B5 B5-0067 Y

530 L

IIgeNo.

2 AFFTSS SYSTEN ENGINEEk!NG FIClh33 08/13/t3 1

REV. 5 SUFFORT NO.

DESCRIPil0N

.DATE NCR NO.

DISP'D RESP NRITTEN lhD EBt-19-P62 SNAY STRUT JM NUT LOOSE 05/17/85 85-0068 Y

SJO i

EEE-2-H2O SUPPDET NOT SHONN ON HAN6ER LOCATION DRANIN6 05/17/95 85-0069 Y

SJO ESD-19-H14 SNUBBER PIPE CLMP NIS-All6NED, LOOSE ANCHOR BOLTS 05/17/85 85-0070 Y

SJO I

i i

e J

r f

I i

t 1

1 i

(

f 2

, _. _,.,... _.., _ _. _ _ -. _., _ _ ~.

f ge Nc.

1 ATPTSS SVSTEM GC thSFECTION FINDIh65 05/13/83 REV. 5 SUFFDRi NO.

DESCRIFTICN DATE NCE NO.

DISP'D RESP bRITTEN IND EBD-19-H51 ANCHOR BOLT INSTALLED AT AN ANGLE, EASEFLATE BAP 04/30/85 85-0044 Y

GNT ESD-19-H59 BOLTS LONSER THAN SPECIFIED, BROUT 2* THICK IN LIEU OF 05/02/65 85-0046 Y

GhF l'

EBD-19-H59 REMCTE RESERVOIR NOT SHOWN ON DRAWING 05/08/65 85-0048 Y

RAA EBD-19-H51 INCORRECT SFRING SETilNS 05/08/85 85-0052 Y

RAA EBD-19-H50 CHIPPED CONCRETE ARQUND BASEPLATE 05/08/85 85-0053 Y

6NF EBD-19-H143 FIREPROOFING BROKEN AWAY 05/09/85 E5-0054 Y

TWH EBD-19-H147 ANCHDR BOLT INSTALLED AT AN ANSLE 05/09/85 65-0055 Y

6NF EED-19-H154 SHIM SIZE Nui PER DRAWING 05/09/85 85-0056 Y

RAA E5D-19-H62 FIREPROCFIN6 BROKEN AWAY 05/09/85 85-0057 Y

TWH EBD-19-H60 NRONS SIZE SPRING HANGER 05/09/85 85-0058 Y

RAA

{

EBD-19-H141 BOOT SEAL TORN 05/10/85 85-0059 Y

TWH EBD-19-H58 EICESSIVE LATERAL MOVFMENT OF SUPPORT 05/10/85 SR85-79 Y

SJO EBD-19-H55 BASEPLATE ANCHOR ' DOLT NASHERS SIZE QUESTIONABLE 05/10/85 SR85-79 Y

SNF EiD-20-H1 LOOSE ANCHOR BOLTS NUTS, BASEPLATE 6AP 05/16/85 85-0064 Y

6MF A3 BASE PLATE 6AP 05/16/85 85-0065 Y

6NF EBD-19-H142 BASE PLATE BAP 05/16/85 85-0066 Y

6MF E5D-19-H144 BASE PLATE 6AP 05/16/B5 85-0066 Y

6MF I

EBD-19-H145 BASE PLATE CAP 05/16/85 85-0066 Y

GNF l

EBD-19-H147 BASE PLATE BAP 05/16/85 85-0066 Y

SNF l

EBD-19-H70 SWAY STRUT JAM NUT LODSE 05/21/85 85-0092 Y

SJO j

EBD-19-H14 ALL THREAD R0D USED IN LIEU OF BOLTS 05/21/85 85-0092 Y

6NF EBD-19-H20 ALL THREAD R0D USED IN LIEU OF BOLTS 05/21/85 85-0092 Y

6NF l

EBD-19-H38 HANGER LOCATION DRAWING INCORRECT 05/21/85 85-0092 Y

SJD 1

EBD-19-H39 HAN6ER LOCATION DRAWING INCORRECT 05/21/85 85-0092 Y

SJD

F' age hc.

2 AFFTSS SVSTEQ QC thSFECT10N FINDlh55 08/13/85 REV. 5 SUFF;RT NO.

DESCRIPT!DN DATE NCR NO.

DISP'D RESP WR!iTEN IND EBD-19-H132 BOLTS USED NOT REFLECTED ON DRAW!h6 05/21/85 85-092 Y

6NF EBL-19-H2B CRACLED FIREPROCFING 05/21/B5 hA Y

TWH EBD-19-H29 CRACKED FIREPROOFING 05/21/85 NA Y

TWH EBD-19-H34 MISSih6 FIREPR00 FINS 05/21/85 hA Y

TWH EBD-19-H35 CRACKED FIREPROOFING 05/21/85 NA Y

TWH EBD-19-H38 CRACKED FIREFRC0 FIN 6 05/21/85 NA Y

TWH EBD-19-H39 CRACFED FIREPR00 FINS 05/21/85 NA Y

TWH A221 CRACLED FIREPRDOFING 05/21/B5 NA Y

TWH EBD-20-H1 SWAY STRUT PIFE CLAMP MIS-All6NED 05/21/85 SR85-79 Y

SJO EBD-19-H21 TWO (2) EDLTS NOT MARKED FDR TORQUE TEST 05/21/B5 SRB 5-79 Y

6NF EBD-19-H25 UPPER 6UIDE ANGLE BENT 05/22/B5 85-0071 Y

RAA EBD-19-H132 FIREPR00 FIN 6 BROKEN 05/22/85 85-0072 Y

TWH EBD-19-H133 FIREPROOFING BROKEN 05/22/85 85-0072 Y

TWH EBD-19-H13 SWAY STRUT JAM NUT LOOSE 05/24/85 85-0074 Y

530 EBD-19-H13A SWAY STRUT JAM NUT LODSE 05/24/85 85-0074 Y

SJO

~

EBD-19-H15 SWAY STRUT JAM NUT LODSE 05/24/85 85-0074 Y

SJO EBD-19-H16 SWAY STRUT JAM NUT LODSE 05/24/05 85-0074 Y

SJO EBD-19-H74 FLASHING RISSINS ON INSULATION 05/24/85 B5-0074 Y

SJO EBD-19-H19 THREE (3) 0F FOUR (4) PINS HAVE MAILS IN LIEU OF COTTER 05/24/85 85-0074 Y

SJO KEYS EED-19-H20 WASHER MISSIN6, NO FREE ROTATION DN BUSHIN6 05/24/85 85-0074 Y

SJO EBD-19-H26 INSUL DWN, STRAPS LOOSE & MISSING 05/24/85 B5-0074 Y

SJO EBD-19-H32 SNUBBER PIPE CLAMP MIS-AL16NED, SNUBBER JAM NUT LOOSE C5/24/85 B5-0074 Y

530 EBD-19-H33 SWAY STRUT ROTATES ON EITENSION THREADS NOT SUSHING 05/24/85 85-0074 Y

SJO i

EBD-19-H36 STRAFS LOOSE, INSULATION DOWN,(ALSO H37) 05/24/85 B5-0074 Y

SJO l

L

Fage hc.

3 AFPTSS SYSTEM GC INSPECT!CN FINIINSS 08/13/E5 REV. 5 SUPPORT NO.

DESCRIPT!CN DATE NCR NO.

DISP *D RESP hRITTEh IND EiD-19-H37 CORRESPONDS TO EBD-19-H36 DN 85-0074 05/24/85 85-0074 Y

SJO EED-19-H133 SNAY STRUT P!FE CLAMP MIS-ALI6hED 05/24/65 85-0074 Y

SJD EBD-19-H65 SNAY STRUT MIS-ALIGNED 05/29/85 85-0082 Y

SJO EBD-19-H10 BASEPLATE 6AP 06/06/85 85-0090 Y

GNF EBD-19-H8 BASEPLATE 6AP 06/06/85 85-0090 Y

GNF EBD-19-H6 BASEPLATE 6AP 06/06/85 85-0090 Y

GNF EBD-19-H66 BASEPLATE 6AP 06/06/85 85-0090 Y

6MF EBD-19-H65 BASEPLATE 6AP 06/06/85 85-0090 Y

6NF EBD-19-H150 BASEPLATE BAP 06/06/85 85-0090 Y

SNF E8D-19-H67 BASEPLATE 6AP 06/06/85 85-0090 Y

SNF EBD-19-H135 BASEPLATE 6AP 06/06/85 85-0090 Y

6MF

(

EBD-19-H74 BASEPLATE BAP 06/06/85 85-0090 Y

GNF ED8-19-H21 BASEPLATE 6AP 06/06/85 85-0090 Y

GNF EBD-19-H22 BASEPLATE 6AP 06/06/85 85-0090 Y

GNF EBD-19-H23 BASEPLATE 6AP 06/06/85 85-0090 Y

6NF

~

EBD-19-H24 BASEPLATE 6AP 06/06/85 85-0090 Y

6NF EBD-19-H133 BASEPLATE 6AP 06/06/85 85-0090 Y

GNF EBD-19-H132 BASEPLATE SAP 06/06/85 65-0090 Y

6NF EBD-19-H131 BASEPLATE 6AP 06/06/85 85-0090 Y

GNF EBD-19-H12 BASEPLATE 6AP 06/06/85 85-0090 Y

SWF EPD-19-H26 BASEPLATE 6AP 06/06/85 85-0090 Y

6NF EBD-19-H72 BASEPLATE 6AP 06/06/85 85-0090 Y

6NF A362 BASEPLATE 6AP 06/06/85 85-0090 Y

6MF EBD-19-H49 BASEPLATE BAF 06/06/85 85-091 Y

BNF EBD-19-H50 BASEPLATE 6AP 06/06/85 85-091 Y

GNF l

l l

l

Pa'ge Mc.

4 AFPTSS 5)STEQ GC INSFEtitute FIkDIN55 08/13/83 REV. 5 f

SUFFORT NO.

DESCRIPTIDN DATE NCR NO.

DISP'D RESP NRITTEN IND EiD-19-H52 IASEPLATE 6AP 06/06/85 85-091 Y

GNF EfD-19-H53 BASEPLATE SAP 06/06/95 85-091 Y

GNF EBD-19-H54 BASEFLATE 6AP 06/06/85 85-091 Y

6NF EBD-19-H55 BASEPLATE SAP

-06/06/85 85-091 Y

GNF EBD-19-H54 BASEPLATE 6AP 06/06/85 85-091 Y

GNF EBD-19-H51 BASEFLATE 6AP 06/06/85 85-091 Y

6MF EBD-19-H141 CONCRETE CRACKS 06/06/05 SR85-74 Y

6NF EBD-19-H47 CONCRETE CRACKS 06/06/85 SRB 5-74 Y

SNF EBD-19-H48 CONCRETE CRACKS 06/06/05 SR95-74 Y

GNF A3 CONCRETE CRACKS 06/06/85 SRB 5-74 Y

SNF EBD-19-H133 AN6LE NOT NELDED PER DRANING 07/10/85 85-0092A Y

SJO i

EBD 19-H132 NASHERS 11 : 82 DISHED (CONCAVE) 07/11/85 85-0092A GNF k

P' age No.

1 AFPTSS SYSTEN FINTJ!h55 AFTER BASELINE 06/13183 REV. 5 i

SUPPMT NO.

DESCRIPT10N DATE NCR NO.

DISP'D FESP WRITTEN IND EED-19-H49 AhCHCR BOLTS PULLED OUT 05/14/85 85-0060 Y

GNF E5D-19-H136 OhE INACTIVE POLT 05/15/85 65-0042A Y

Ehr E!D-19-H49 SWAY STRUT PIPE CLAMP MIS-All6NED 05/16/85 85-0093 Y

SJO EFD-19-H47 BASEPLATE AhCHOR BOLT WASHERS NOT SHOWN DN DRAWINB 05/!6/85 SRS5-79 Y

SNF EPD-19-H52 SNUBBER REAR BUSHING NOT FREE TO MOVE 05/16/85 SRB 5-79 Y

SJO EPD-19-H150 PIFE CLAMP EDLTS LOGSE 05/21/55 65-0092 Y

SJD EED-19-H67 CLEARANCE GAP DN RESTRAINT NOT PER DRAWING 05/21/85 85-0092 Y

SJO E5D-19-H38 SHIM WELDED TO SUPPORT NOT PER DRAWINB 05/21/85 SRE5-79 Y

SJO EBD-19-H39 SHIM WELDED TO SUFPORT NOT PER DRAWINS 05/21/85 SR85-79 Y

SJO EED-19-H17 SWAY STRUT END BEARINS DOES NOT MOVE FREELY 05/23/85 65-0092 Y

SJO EBD-19-H14 CONCRETE AROUND BASEPLATE IS CHIPPED 05/23/85 SR85-73 Y

GNF EBD-19-H132 CONCRETE CRACKS IN WALL 05/23/85 SR85-73 Y

GNF EBD-19-H67 CONCRETE CRACKS IN WALL 05/23/85 SR85-73 Y

SMF EBD-19-H68 CONCRETE CRACKS IN WALL 05/23/85 SR85-73 Y

GNF EBD-19-H12 CONCRETE CRACK IN WALL 05/23/55 SRB 5-73 Y

GNF EPD-19-H148 CONCRETE CRACK IN WALL 05/23/85 SR85-73 Y

6MF EBD-19-H65 CONCRETE CRACK IN WALL 05/23/85 SR85-73 Y

6NF EBD-19-H26 CONCRETE CRACK IN WALL 05/23/85 SRB 5-73 Y

SNF EBD-19-H22 CONCRETE CRACK IN WALL 05/23/85 SR85-73 Y

6NF EBD-19-H2O CONCRETE CRACK IN WALL 05/23/85 SR85-73 Y

SNF EPD-20-H1 LOOSE SWAY STRUT JAM NUT 06/05/85 85-0088 Y

SJO EBD-20-H1 BROKEN FIREFR00FING 06/05/85 85-0089 Y

TWH EBD-19-H154 BROKEN FIREPR00FING 06/05/85 85-0089 Y

TWH EBD-19-H1B SWAY STRUT ROTATES ON THREADS 06/06/85 85-0092 Y

SJD EBD-20-H1 LOO 3E SWAY STRUT JAM NUT 06/06/85 85-0092 Y

SJO

Fage ho.

2 AFF155 SiSTEM FINDlh65 AFTER BASEllhE 02/13183 REV. 5

-g SUFFORT hD.

DESCRIPTION DATE N:R NO.

DISP'D RESP WRITTEN IND EBD-19-H16 SWAY STRUT JAM NUT LODSE, PIPE CLAMP LCDSE 0e/11/95 95-0094 Y

SJO i

EBD-19-Hl3A SWAY STRUT EYELET CONTACTS PIPE CLAMP 06/11/95 B5-0094 Y

SJG A004 LOWER RI6HT NUT LOOSE 08/02/65 85-124 6NF 4

1

(

l i.

I

~

i i

I 1

1 i

I i

4, e

j.

I i

_. _ ~ _,...,.,..,. _..

h a

h SECTION 2.0 l

AUXILIARY FEEDWATER SYSTEM t

a b

b l

h l

s.

Fage No.

1 SYSTEM: AU11LIARY FEEDb4TER 08/13/23 DAVIS - BESSE PIPING / SUPPORTS INSPECIDh F]NDINGS REV. 5 SUFFORT DESCRIPTIDN DATE NCR/SR DISF'D RESP hUMBER NUMBER IND EBD-14-H76 CDNCRETE CHIPPED 05/08/B5 B5-0049 Y

6NF EBD-14-HBO BASEPLATE 6AP/ CONCRETE CHIPFED 05/08/95 85-0050 Y

6NF EBD-14-H90 BASEFLATE 6AP 05/08/05 85-0051 Y

BNF EED-14-H54 BOLT SIZE INCORRECT 05/23/85 85-0073 Y

SNF i

EBD-14-H69 LDOSE BOLT 05/24/85 85-0075 Y

6NF EBD-14-H68 DNE BDLT NILL NOT T0REUE 05/28/85 B5-0076 Y

BNF EBD-14-H67 BDLT TYPE INCDRRECT 05/28/85 85-0077 Y

6hF ESD-14-H77 BOLT SIZE & DGANTITY INCORRECT 06/25/95 85-0102 Y

SNF EBD-14-H91 $DLT SIZE INCORRECT 07/10/85 85-0108 Y

BNF

(