ML20137U244

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 851126-860117
ML20137U244
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 02/12/1986
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20137U189 List:
References
50-302-85-44, NUDOCS 8602190094
Download: ML20137U244 (2)


Text

__ .

1 1

ENCLOSURE I NOTICE OF VIOLATION n Florida Power Corporation Docket No. 50-302 Crystal River Unit 3 License No. DPR-72 The following violations were identified during an inspection conducted on November 26, 1985 - January 17, 1986. The Severity Levels were assigned in

, accordance with the NRC Enforcement Policy (10 CFR Part 2, Appendix C).

1. The Crystal River Unit 3 Final Safety Analysis Report (Section 8.2.3.3) requires that two independent sources of control power be provided for the 230 KV breakers and the protective relaying schemes for the 230 KV substation.

10 CFR Part '50.72 requires the NRC Operations Center be notified via the Emergency Notification System within one hour of any event during operation that results in the nuclear power plant being in a condition that is outside the design basis of the plant.

Contrary to the above, on December 5,1985, a one hour report was not, made to the NRC Operations Center, when it was determined _that two independent sources of 125 volt DC control power that provided prot,ective relaying power for the 230 KV breakers were found to be in a. condition 1outside the design basis of the plant.

This is a Severity Level V violation (Supplement I).

2. Technical Specification 6.8.1.a requires adherence to the written procedures listed in Appendix A of Regulatory Guide 1.33, November 1972. Appendix A of Regulatory Guide 1.33, Section 5.6, requires procedures for radiation work permits (RWPs).

i Chemistry and Radiation Protection Procedure RSP-101, Basic Radiological

Safety Information and Instructions for " Radiation Workers", step 3.1.3.4 directs that the requirements established on RWPs .be observed and adhered to.

i Contrary to the above, on December 30, 1985, orocedure RSP-101 was not adhered to in that an individual was observed inside a contaminated area without the required protective clothing listed on the RWP.

This is a Severity Level IV violation (Supplement I).

Pursuant to 10 CFR 2.201, you are required to submit to this office within 30 days of the date of this Notice, a written statement or explanation in reoly, including: (1) admission or denial of the alleged violations; (2) the reasons for the violations if admitted; (3) the corrective steps which have been taken and the results achieved; (4) corrective steps which will be taken to avoid

, further violations; and (5) the date when full compliance will be achieved.

e .

Florida Power Corporation Docket No. 50-302 Crystal River Unit 3 2 License No. OPR-72 Security . or safeguards information should be submitted as an enclosure to facilitate withholding it from public disclosure as required by 10 CFR 2.790(d) or 10 CFR 73.21.

FEB 19 im Date: