Forwards Lists of Welds to Be Inspected & Welds to Be Replaced,Per Generic Ltr 84-11 & as Result of RWCU Sys Piping Upgrade for IGSCC Insp During Reload 6 Outage Commencing 851201
ML20137N061
Person / Time
Site: Brunswick Duke Energy icon.png
Issue date: 11/27/1985
From: Zimmerman S
CAROLINA POWER & LIGHT CO.
To: Vassallo D
Office of Nuclear Reactor Regulation
References
GL-84-11, NLS-85-423, NUDOCS 8512040060
Download: ML20137N061 (4)


Text

.. -

Carolina Power & Light Company NOV 2 7 g SERIAL: NLS-85-423 Director of Nuclear Reactor Regulation Attention:

Mr. D. B. Vassallo, Chief

_ _ Operating Reactors Branch No. 2 Division of Licensing United States Nuclear Regulatory. Commission Washington, DC 20555 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NO. 2 DOCKET NO. 50-324/ LICENSE NO. DPR-62 IGSCC INSPECTIONS

Dear Mr. Vassallo:

On November 1,1985, Carolina Power & Light Company submitted our plans to perform intergranular stress corrosion cracking (IGSCC) inspections and mitigative actions during the Brunswick-2 Reload 6 outage, scheduled to begin on December 1,1985. In a recent telephone conversation, your staff requested more detailed information regarding the scope of the planned inspections. As stated in our November 1,1985 submittal, the IGSCC inspections will be performed in accordance with the requirements of Generic Letter 84-11. Table I lists the welds which we currently plan to inspect. Table 2 list-,

those welds which will be replaced as a result of the reactor water cleanup system piping upgrade. The information contained in these tables is preliminary and intended to be used for informational purposes only. The final results of the inspections, the specific scope of the Induction Heating Stress Improvement Program, and a description of any further corrective actions will be submitted prior to Brunswick-2 startup.

.Please refer any questions to Mr. Stephen D. Floyd at (9l9) 836-6901.

Yours very truly,

= =

S.

. Zim terman ager i

Nuclear Licensing Section MAT /ccc (3057 MAT) cc:

Mr. W. H. Rutand (NRC-BNP)

Dr. J. Nelson Grace (NRC-RII)

Mr. M. Grotenhuis (NRC) h G

rd I

411 Fayetteville Street

  • P. O. Box 1551
  • Raleign. N. C. 27602

y TABLE 1

. PRELIMINARY LIST OF WELDS TO BE INSPECTED DURING THE BRUNSWICK-2 RELOAD 6 OUTAGE 2-B32-28"-A-2 '

SS Safe End to SS Pipe 2-B32-28"-A-3 SS Pipe to SS Elbow 2-B32-28"-A SS Elbow to SS Pipe 2-B32-28"-A-5 SS Pipe to SS Tee 2-B32-28"-A-6 SS Tee to SS Pipe 2-B32-28"-A-7 SS Pipe to SS Elbow 2-B32-28"-A-8 SS Elbow to SS Valve 2-B32-28"- A-9 SS Valve to SS Pipe 2-B32-28"-A-10 SS Pipe to SS Elbow 2-B32-28"-A-l l SS Elbow to SS Pump 2-B32-28"-A-12 SS Pump to SS Pipe 2-B32-28"-A-13 SS Pipe to SS Valve 2-B 32-28"-A-14 SS Valve to SS Elbow 2-B32-28"-A-15.-

SS Elbow to SS Pipe 2-B32-28"-A-16 SS Pipe to SS Tee

' 2-B 32-28"-A-17 SS Tee to SS Cross 2-B32-28"-A-18 SS Cross to SS Reducer 2-B 32-28"-B-2 SS Safe End to SS Pipe 2-B32-28"-B-3 SS Pipe to SS Elbow 2-B32-28"-B SS Elbow to SS Pipe 2-B32-28"-B-5 SS Pipe to SS Tee 2-B32-28"-B-6 SS Tee to SS Pipe 2-B32-28"-B-7 '

SS Pipe to SS Elbow

' 2-B32-28"-B-8 SS Elbow to SS Valve 2-B 32-28"-B-9 SS Valve to SS Pipe 2-B32-28"-B-10 SS Pipe to SS Elbow 2-B 32-28"-B-l l SS Elbow to SS Pump 2-B32-28"-B-12 SS Pump to SS Pipe 2-B 32-28"-B-13 SS Pipe to SS Valve 2-B 32-28"-B-14 SS Valve to SS Elbow 2-B32-28"-B-15 SS Elbow to SS Pipe 2-B 32-28"-B-16 SS Pipe to SS Tee -

2-B 32-28"-B-17 SS Tee to SS Cross 2-B 32-28"-B SS Cross to SS Reducer 2-B 32-22"- AM-1 SS Valve to SS Pipe 2-B32-22"-AM-2 SS Pipe to SS Valve 2-B32-22"-AM-3 SS Valve to SS Pipe 2-B32-22"-AM-4 SS Pipe to SS Pipe i

2-B32-22"-AM-5 SS Pipe to SS Cross 2-B32-22"-AM-6 SS Cross to SS Pipe

' 2-B32-22"-BM-1 SS Cap to SS Pipe 2-B32-22"-BM-2 SS Pipe to SS Cross 2-B32-22"-BM-3

,SS Cross to SS Pipe 2-B32-22"-BM-4 SS Pipe to SS Valve 2-B 32-12"- A R-A-1 SS Sweepolet to SS Pipe 2-B32-12"-AR-A-2 SS Pipe to SS Elbow 2-B 32-12"-AR-A-3 SS Elbow to SS Pipe 2-B32-12"-AR-A-4 SS Pipe to SS Safe End (3057 MAT /ccc) i

n l

l o

. 2-B32-12"-AR-B-1 SS Sweepolet to SS Pipe 2-B32-12"-AR-B-2 SS Pipe to SS Elbow 2-B32-12"-AR-B-3 SS Elbow to SS Pipe 2-B32-12"-AR-B-4 --

SS Pipe to SS Safe End 2-B32-12"-AR-C -I SS Sweepolet to SS Pipe 2-B32-12"-AR-C-2 SS Pipe to SS Elbow 2-B32-12"-AR-C-3

-SS Elbow to SS Pipe 2-B32-12"-AR-C SS Pipe to SS Safe End 2-B32-12"-AR-D-1 SS Sweepolet to SS Pipe 2-B32-12"-AR-D-2 SS Pipe to SS Elbow 2-B32-12"-AR-D-3 SS Elbow to SS Pipe 2-B32-12"-AR-D-4 '

SS Pipe to SS Safe End

. 2-B32-12"-AR-E SS Sweepolet to SS Pipe 2-B32-12"-AR-E-2 SS Pipe to SS Elbow 2-B32-12"-AR-E-3 SS Elbow to SS Pipe 2-B32-12"-AR-E-4 SS Pipe to SS Safe End 2-B32-12"-BR-F SS Sweepolet to SS Pipe 2-B32-12"-BR-F-2 SS Pipe to SS Elbow 2-B32-12"-BR-F-3 SS Elbow to SS Pipe 2-B32-12"-BR-F-4 SS Pipe to SS Safe End 2-B32-12"-BR-G-t SS Sweepolet to SS Pipe

' 2-B32-12"-BR-G-2.

SS Pipe to SS Elbow 2-B32-12"-BR-G-3 SS Elbow to SS Ftpe 2-B32-12"-B R-G-4 SS Pipe to SS Safe End 2-B32-12"-BR-H-1 SS Sweepolet to SS Pipe

. 2-B32-12"-BR-H-2 SS Pipe to SS Elbow 2-B32-12"-BR-H-3 SS Elbow to SS Pipe 2-B32-12"-BR-H-4 SS Pipe to SS Safe End 2-B32-12"-BR-3-1

. SS Sweepolet to SS Pipe 2-B32-12"-BR-3-2 SS Pipe to SS Elbow 2-B32-12"-BR-3 SS Elbow to SS Pipe 2-B32-12"-BR-3-4

. SS Pipe to SS Safe End 2-B32-12"-BR-K-1 SS Sweepolet to SS Pipe 2-B32-12"-BR-K-2 SS Pipe to SS Elbow 2-B32-12"-BR-K-3 SS Elbow to SS Pipe 2-B32-12"-BR-K-4 SS Pipe to SS Safe End 2-B32-4"-A-BYPASS-1 SS Pipe to SS Weldolet 2-B32-4"-A-BYPASS-11 SS Pipe to SS Weldolet eB32-4"-B-BYPASS-1.

SS Pipe to SS Weldolet 2-B32-4"-B-BYPASS-11 SS Pipe to SS Weldolet 2-B32-28"-A-9BC-1 SS Branch 2-B32-28"-A-12BC SS Weldolet 2-B32-28"-A-15BC-1 SS Weldolet

~ 2-B32-28"-B-9BC SS Branch 2-B32-28"-B-12BC-1 SS Weldolet 2-B32-28"-B-15BC-l.

SS Weldolet 2-El l-RHR-20"-A-SUCT-l SS Tee to SS Pipe 2-E l l-RHR-20"-A-SUCT-l BC SS Sweepolet E11-RHR-20"-A'-SUCT-2 SS Pipe to CS Valve 2-El l-RHR-24"-A-DISCH-12 SS Tee to CS Valve

. 2-E11-RHR-24"-B-DISCH-12 SS Tee to CS Valve (3057 MAT /ccc )

TABLE 2 PRELIMINARY LIST OF WELDS TO BE REPLACED DURING THE BRUNSWICK-2 RELOAD 6 OUTAGE 2-G31-RWCU-6"-l SS Tee to SS Pipe 2-G31-RWCU-6"-1 A SS Pipe to SS Pipe 2-G31-RWCU-6"-2 SS Pipe to SS Valve 2-G31-RWCU-6"-3 SS Pipe to SS Pipe 2-G31-RWCU-6"-3A SS Pipe to SS Pipe

2-G31-RWCU-6"-4B SS Pipe to SS Elbow G31-RWCU-6"-5B

-SS Elbow to SS Pipe 2-G31-RWCU-6"-5A

~SS Pipe to SS Pipe 2-G31-RWCU-6"-6 SS Pipe to SS Elbow 2-G31-RWCU-6"-7 SS Elbow to SS Pipe 2-G 31-RWC U-6" SS Pipe to SS Elbow 2-G31-RWCU-6"-9 SS Elbow to SS Pipe 2-G31-RWCU-6"-10 SS Pipe to SS Elbow 2-G31-RWCU-6"-I l SS Elbow to SS Pipe 2-G31-RWCU-6"-12 SS Pipe to SS Valve 2-G31-RWCU-6"-13 '

SS Valve to SS Pipe 2-G31-RWCU-6" SS Pipe to SS Elbow 2-G 31-RWCU-6"-15 SS Elbow to SS Pipe

' 2-G 31-RWCU-6"-16 SS Pipe to SS' Pent 2-G 31-RWC U-6"-17.

SS Pent to SS Elbow 2-G 3 l-RWCU-6" SS Elbow to SS Pipe 2-G 31-RWCU-6"-19 SS Pipe to SS Valve --

(3057 MAT /ccc) m