Text
T.
NEW NIAGARA HOMAWK POWER CORPORATION /:.0O ERIE BOULEVARD WEST. SYRACUSE. N Y.13202/ TELEPHONE (315) 474-1511 January 2, 1986 (NMP2L 0572)
M. R. W. Starostecki, Director U.S. Nuclear Regulatory Commission Region I Division of Project and Resident Programs 631 Park Avenue King of Prussia, PA 19406 Re: Nine Mlle Point Unit 2 Docket No. 50-410
Dear Mr. Starostecki:
Enclosed is a final report in accordance with 10CTR50.55(e) for the problem concerning electrical panelboards mounting configuration. This problem was reported via telecon to J. Linville of your staff on August 30, 1985, and an interim report was transmitted on October 1, 1985.
Very truly yours,
(_cA1&bfd4\\
C. V. Manga Senior Vice President GG:ja 1205G Enclosure xc: Director of Inspection and Enforcement U.S. Nuclear Regulatory Comission Washington, DC 20555 R. A. Gram, Resident Inspector Project File (2) o
/
,\\s-_
r-1 l
i NIAGARA MOHA* POWER CORPORATION NINE MILE POINT - UNIT 2 DOCKET NO. 50-410 Final Report for a Problem Concerning Electrical Pane 1 boards Field Versus Seismic Test Mounting Configuration (55(e)-85-26)
Description of the Problem Quality Assurance Category I distribution panelboards, as identified in Nonconfomance and Disposition Report No. D032, were installed in a mounting configuration which was not representative of the configuration used for seismic qualification by the vendor.
This problem was identified during the seismic qualification walkdown of electrical distribution panelboard EJS*PNL100A.
Analysis of Safety Imolication A seismic retesting of prototype panelboards was successfully completed and witnessed by Stone & Webster Engineers. The final test report has been issued by the vendor for Stone & Webster's approval to confirm test results data.
Therefore, the installed panelboards do not have a seismic Qualification deficiency.
4
-