Text
. _. - -
.(
nu h
UNITED STATES g
j NUCLEAR REGULATORY COMMISSION j
e WASHINGTON, D.C. 3000H001 i
\\*****/
l DUKE POWER COMPANY i
NORTH CAROLINA ELECTRIC MEMBERSHIP CORPORATION
)
SALUDA RIVER ELECTRIC COOPERATIVE. INC.
DOCKET NO. 50-413 CATAWBA NUCLEAR STATION. UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE I
Amendment No.157 License No. NPF-35 i
l 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the Catawba Nuclear Station,
)
Unit 1 (the facility) Facility Operating License No. NPF-35 filed by the Duke Power Company, acting for itself, North Carolina Electric Membership Corporation and Saluda River Electric Cooperative, Inc.-(licensees), dated November 4, 1996, and j
supplemented by letter dated February 5,1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as i
amended (the Act), and the Commission's rules and regulations as i
set forth in 10 CFR Chapter I; 4
i B.
The facility will operate in conformity with the application, the i
provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangsring the lealth and safety of the public, and (ii) that such activities wt be 3
conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and escurity or to the health and safety of the public; j
and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable i
requirements slave been satisfied.
a 4
9703180087 970313 i
PDR ADOCK 05000413 G
PDR l
1 j
i j 4 i
i 2.
Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachment to this license 4
j amendment, and Paragraph 2.C.(2) of Facility Operating License No.
l i
NPF-35 is hereby amended to read as follows:
l i
(2)
Technical Soecifications i
i The Technical Specifications contained in Appendix A, as i
revised through Amendment No. 157. which are attached i
hereto, are hereby incorporated into this license. Duke Power Company shall operate the facility in accordance with j
the Technical Specifications.
3.
This license amendment is effective as of its date of issuance and shall l
be implemented within 30 days from the date of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION i
Herbert N. Berkow, Director Project Directorate 11-2 Division of Reactor Projects - I/II j
Office of Nuclear Reactor Regulation i
Attachment:
Technical Specification j
Changes
)
Date of Issuance:
March 13, 1997 a
i i
f l
i
)
4 i
4 4
i ATTACHMENT TO LICENSE AMENDMENT NO.157 FACILITY OPERATING LICENSE NO. NPF-35 DOCKET NO. 50-413 Replace the followin the enclosed pages. g pages of the Appendix "A" Technical Specifications with The revised pages are identified by Amendment number and contain vertical lines indicating the areas of change.
l Remove Insert 3/4 7-32 3/4 7-32 l
I 6
e,.e
PLANT SYSTEMS 3/4.7.13 STANDBY SHUTDOWN SYSTEM
_ LIMITING CONDITION FOR OPERATION l
3.7.13 The Standby Shutdown System (SSS) shall be OPERABLE.
APPLICABILITY: MODES 1, 2, and 3.
El1QH:
(Units 1 and 2) l l
a.
With the Standby Shutdown System inoperable, restore the inoperable j
equipment to OPERABLE status within 7 days or be in at least HOT i
STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in at least HOT SHUTDOWN within l
the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
4 b.
With the total leakage from UNIDENTIFIED LEAKAGE, IDENTIFIED LEAKAGE and reactor coolant pump seal leakage greater than 26 gps, declare j
the Standby Makeup Pump inoperable and take ACTION a., above.
i c.
The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
t i
SURVEILLANCE REQUIREMENTS i
4.7.13.1 The Standby Shutdown System diesel generator shall be demonstrated OPERABLE:
i a.
At least once per 31 days by verifying:
I 1)
The fuel level in the fuel storage tank is greater than or l
equal to 67 inches, and 2)
The diesel starts from ambient conditions and operates for at j
least 30 minutes at greater than or equal to 700 kW.
b.
At least once per 92 days by verifying that a sample of diesel fuel
{
from the fuel storage tank, obtained in accordance with ASTM-D270-1975, is within the acceptable limits specified in Table 1 of ASTM-l D975-1977 when checked for viscosity and water and sediment; and a
c.
At least once per 18 months by subjecting the diesel to an l
inspection in accordance with procedures prepared in conjunction j
with its manufacturer's recommendations for the class of service.
(
i i
i 4
4 CATAWBA - UNIT 1 3/4 7-32 Amendment No.157 i
ng J:
i g
k UNITED STATE 8 s
NUCLEAR REGULATORY COMMISSION i
WASHINGTON, D.C. 30006 40tH l
i j
DUKE POWER COMPANY l
NORTH CAROLINA MUNICIPAL POWER AGENCY NO. 1 l
PIEDMONT MUNICIPAL POWER AGENCY j
DOCKET N0. 50-414 l
CATAWBA NUCLEAR STATION. UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE i
i Amendment No. 149 l
License No. NPF-52 l
1.
The Nuclear Regulatory Commission (the Connission) has found that:
A.
The application for amendment to the Catawba Nuclear Station, i
Unit 2 (the facility) Facility Operating License No. NPF-52 filed i
by the Duke Power Company, acting for itself, North Carolina l
Municipal Power Agency No. I and Piedmont Municipal Power Agency (licensees), dated November 4,1996, and supplemented by letter dated February 5, 1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations as set forth in i
10 CFR Chapter I; 8.
The facility will operate in confomity with the application, the provisions of the Act, and the rules and regulations of the i
Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health i
and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set
{
forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; f
and E.
The issuance of this amendment is in accordance with 10 CFR j
Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
3 l
, 2.
Accordingly, the license is hereby amerided by page changes'to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Facility Operating License No.
NPF-52 is hereby amended to read as follows:
(2) Technical Snecifications The Technical Specifications contained in Ap>endix A, as revised through Amendment No. 149, which are attacied hereto, are hereby incorporated into this license. Duke Power Company shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of its date' of issuance and shall be implemented within 30 days from the date of issuance.
FOR THE NUCLEAR REGULATORY COP 911SSION i
Y Herbert N. Berkow, irector Project Directorate II-2 Division of Reactor Projects - I/II l
Office of Nuclear Reactor Regulation
Attachment:
Technical Specification l
Changes Date of Issuance:
March 13,1997 l
i i
ATTACMENT TO LICENSE AMENDMENT NO.149 FACILITY OPERATING LICENSE NO. NPF-52 l
DOCKET NO. 50-414 i
Replace the following pages of the Appendix "A" Technical Specifications with l
the enclosed pages. The revised pages are identified by Amendment number and j
contain vertical lines indicating the areas of change.
~
Remove Insert 3/4 7-33 3/4 7-33 4
5 l
i I
,l J
1 i
1 i
i
~
i PLANT SYSTEMS 3/4.7.I3 STANDBY SHUTDOWN SYSTEM LIMITING CONDITION FOR OPERATION l
3.7.13 The Standby Shutdown System (SSS) shall be OPERABLE.
APPLICABILITY: MODES 1, 2, and 3.
l EIl08:
(Units 1 and 2) 1 a.
With the Standby Shutdown System inoperable, restore the inoperable equipment to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in at least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
b.
With the total leakage from UNIDENTIFIED LEAKAGE, IDENTIFIED LEAXAGE and reactor coolant pump seal leakage greater than 26 gpm, declare i
the Standby Makeup Pump inoperable and take ACTION a., above, i
c.
The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 4.7.13.1 The Standby Shutdown System diese'l generator shall be demonstrated j
OPERABLE:
a.
At least once per 31 days by verifying:
1)
The fuel level in the fuel storage tank is greater than or i
equal to 67 inches, and 2)
The diesel starts from ambient conditions and operates for at least 30 minutes at greater than or equal to 700 kW.
b.
At least once per 92 days by verifying that a sample of diesel fuel from the fuel storage tank, obtained in accordance with ASTM-D270-4 l
1975, is within the acceptable limits specified in Table 1 of ASTM-D975-1977 when checked for viscosity and water and sediment; and
?
c.
At least once per 18 months by subjecting the diesel to an I
ins >ection in accordance with procedures prepared in conjunction wit) its manufacturer's recommendations for the class of service.
l.
i i
I CATAWBA - UNIT 2 3/4 7-33 Amendment No.149
.-