Limirick Gsnrrating St: tion y
R eeco ree<ovcomneev
~
PO Box 2300 A UNIT of PECO ENrecy Sanatoga, PA 19464-0920 T.S.6.9.1.6 March 12,1997 Docket Nos. 50-352 50-353 License Nos. NPF-39
]
NPF-85 1
U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555
Subject:
Limerick Generating Station Monthly Operating Report For Units 1 and 2 Enclosed are the monthly operating reports for Limerick Units 1 and 2 for the month of February 1997 forwarded pursuant to Technical Specification 6.9.1.6.
Very truly yours, Edward F. Sproat, III' Director - Site Engineering drh Enclosuret cc:
H. J. Miller, Administrator, Region I, USNRC N. S. Perry, USNRC Senior Resident Inspector LGS
/[
W. G. MacFarland, Vice President, LGS all p
9703130239 970228 PDR ADOCK 05000352
$,$Eg,g,ggg R
N
Dock t No. 50-352 Attachm:nt to Monthly Operating Report for February 1997 Limerick Generating Station Unit 1 February 1 through February 28,1997 1.
Narrative Summary of Operatina Experiences Unit 1 began the month of February 1997 at a nominal 100% rated thermal power (RTP).
On February 7,1997 at 2350 hours0.0272 days <br />0.653 hours <br />0.00389 weeks <br />8.94175e-4 months <br />, power was reduced to 98% RTP for main turbine valve testing. Power was restored to 100% RTP on February 8,1997 at 0151 hours0.00175 days <br />0.0419 hours <br />2.496693e-4 weeks <br />5.74555e-5 months <br />.
On February 13,1997 at 2215 hours0.0256 days <br />0.615 hours <br />0.00366 weeks <br />8.428075e-4 months <br />, power was reduced to 91% RTP for main turbine valve testing and rod pattern adjustment. Power was restored to 100% RTP at 2323 hours0.0269 days <br />0.645 hours <br />0.00384 weeks <br />8.839015e-4 months <br />.
On February 16,1997 at 0041 hours4.74537e-4 days <br />0.0114 hours <br />6.779101e-5 weeks <br />1.56005e-5 months <br />, power was reduced to 93% RTP for main steam isolation valve testing. Power was restored to 100% RTP at 0528 hours0.00611 days <br />0.147 hours <br />8.730159e-4 weeks <br />2.00904e-4 months <br />.
On February 22,1997 at 1122 hours0.013 days <br />0.312 hours <br />0.00186 weeks <br />4.26921e-4 months <br />, power was reduced to 98% RTP for main turbine valve testing. Power was restored to 100% RTP at 1718 hours0.0199 days <br />0.477 hours <br />0.00284 weeks <br />6.53699e-4 months <br />.
Unit 1 ended this month operating at 100% RTP.
II.
Challences to Main Steam Safety Relief Valves There were no challenges to the Main Steam Safety Relief Valves during the month of February.
n-
. ~ -. - ~.. -
-... - -..... -. -.. ~..-.
.. ~........- _.
... -.I AVERAGE DAILY POWER LEVEL DOCKET NO. 50-352 UNIT LIMERICKUNIT1 DATE MARCH 10,1997 COMPANY PECO ENERGY COMPANY
- r
'tOBERT A BAXLEY REPORTS ENGINEER i
SITE ENGINEERING LIMERICK GENERATING STATION TELEPHONE (610)7183767 MONTH FEBRUARY,1997 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWE-NET)
(MNE-NET) 1 1111 17 1120 2
1120 18 1111 3
1111 19 1119 4
1120 20 1103 5
1111 21 1104 j
6 1120 22 1095 7
1120 23 1110 t
t 4
8 1112 24 1112 9
1122 25 1117 to 1121 26 1109 11 1121 27 1097 12 1118 28 1109 13 1118 14 1116 15 1119 16 1103 b
I b
-u.-
. -.. ~.. -... -. - _. -
OPERATING DATA REPORT t
l DOCKET NO. 50 -352 DATE MARCH 10,1997 -
COMPLETED BY PECO INERGY COMPANY ROBERT A. BAXLEY REPORTS ENGINEER
.l SITE ENGINEERING j
LIMERICK GENERATING STATION TELEPHONE (610) 718-3767
. OPERATING STATUS t
- 1. UNIT NAME:
LIM _E..R. I.C. K...U...N.._I.T 1
- 2. REPORTING PERIOD:
FEBRUARY,1997~~~
GREATER THAN 20% THIS MONTH.
~~
i
- 3. UCENSED THERMAL POWER (MWT) 3458 1
1180
- 4. NAMEPLATE RATING (GROSS MWE):
1105
- 5. DESIGN ELECTRICAL RATING (NET MWE):
- 6. MAXIMUM DEPU4DABLE CAPACITY (GROSS MWE):
1145
- 7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):
1105
- 8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THROUGH 7 ) SINCE LAST REPORT, GIVE REASONS:
I
- 9. POWER LEVEL TO WHICH RESTRICTED,IF ANY (NET MWE):
i
- 10. REASONS FOR RESTRICTIONS,IF ANY:
j C
THIS MONTH YR-TO-DATE CUMULATIVE
[
- 11. HOURS IN REPORTING PERIOD 672 1,41 6 97,104
- 12. NUMBER OF HOURS REACTOR V!AS CRITICAL 672.0 1,416.0 81,543.4
' O.0 0.0 0.0
- 13. REACTOR RESERVE SHUTDOWN HOURS tF2.0 1,416.0 80,176.0
- 14. HOURS GENERATOR ON-LINE
{
- 15. UNIT RESERVE SHUTDOWN HOURS 0.7 0.0 0.0 2',645,972 A
- 16. GROSS THERMAL ENERGY GENERATED (MWH) 2,321,1N 4,891,809
- 17. GROSS ELECTRICAL ENERGY GENERATED (MWH)
- 774,000 1,634,300 81,706,080
- 18. NET ELECTRICAL ENERGY GENERATED (MWH) 748,102 1,581,345 78,514.442 3
t 5
PAGE 1 OF 2
?
=
OPERATING DATA REPORT (CONTINUED) -
DOCKET NO.
50 - 352
~
DATE MARCH 10,1997 THIS MONTH YR-TO-DATE CUMULATIVE
- 19. UNIT SERVICE FACTOR 100.0 %
100.0 %
82.6 %
- 20. UNIT AVAILABILITY FACTOR 100.0 %
100.0 %
82.6 %
- 21. UNIT CAPACITY FACTOR (USING MDC NET) 100.7 %
101.1 %
76.2 %
- 22. UNIT CAPACITY FACTOR (USING DER NET) 100.7 %
101.1 %
76 2 %
- 23. UNIT FORCED OUTAGE RATE
.0 %
.0 %
4.1 %
- 24. SHUTDOWNS SCHEDUI ED OVER THE NEXT 6 MONTHS (TYPE, DATE AND DURATIOld OF EACH):
- 25. IF SHUTDOWN AT THE END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATIONS):
FORECAST ACHIEVED INITIAL CRITICALITY 12/19/84 12/22/B4 INITIAL ELECTRICITY MID APRIL 85 04/13/65 COMMERCIAL OPERATION 1ST QTR 86 0201/86 i
=
' PAGE 2 OF 2 r
..1_,
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-352 UNITNAME UMERICKUNIT1 DATE MARCH 10,1997 COMPLETED BY PECO ENERGY COMPANY ROBERT A. BAXLEY REPORTS ENGINEFR SITE ENGINEERING LIMERICK GENERAThNG STATION REPORT MONTH FEBRUARY 1997 TELEPHONE (610)71ELT167 I
METHOD OF UCENSEE SYSTEM COMPONENT CAUSE AND CORRECTIVE TYPE
' DURATION REASON SHUTTING DOWN EVENT CODE CODE ACTION TO NO.
DATE (1)
(HL **S)
(2)
REACTOR (3)
REPORT #
(4)
(5)
PREVENT RECURRENCE 177 970207 S
B 4
N/A HA VALVEX REACTOR POWER WAS REDUCED TO 98% DUE TO MAIN TURBINE VALVE TESTING.
178 970213 S
B 4
N/A HA VALVEX ttEACTOR POWER WAS REDUCED TO 91% DUE TO MAIN TURBINE VALVE TESTING AND CONTROL ROD PATTERN ADJUSTMENT.
179 970216 S
B 4
N/A CD VALVEX REACTOR POWER WAS REDUCED TO 93% DUE TO MAIN STEAM ISOLATION VALVE TESTING.
180 970222 S
B 4
N/A HA VALVEX REACTOR POWER WAS REDUCED TO 98% DUE TO MAIN TURBINE VALVE TESTING.
TOTAL HOURS
[
F (1)
(2)
(3)
(4)
F-FORCED REASON METHOD EXHIBIT G -INSTRUCTIONS S-SCHEDULED A-EQUIPMENT FAILURE (EXPLAIN) 1 - MANUAL FOR PREPARATION OF DATA B -MAINTENANCE OR TEST 2-MANUALSCRAM ENTRY SHEETS FOR UCENSEE C - REFUELING 3 - AUTOMATIC SCRAM EVENT REPORT (LER)
D-REGULATORY RESTRICTION 4-OTHER (EXPLAIN)
FILE (NUREG4161) i E - OPERATOR TRAINING + UCENSE EXAMINATION F - ADMINISTRATIVE (5)
G-OPERATIONAL ERROR (EXPLAIN)
EXHIBIT I-SAME SOURCE H - OTHER (EXPLAIN)
{
i
~...
~
Dockst No. 50-353 i
Attachm:nt to Monthly Operating Report for l
February 1997 Limerick Generating Station Unit 2 February 1 through February 28,1997 l
l.
Narrative Summary of Operatina Experiences
. Unit 2 began the month of February 1997 at 0% rated thermal power (RTP) shutdown for a refueling outage I
On February 26,1997 at 0356 hours0.00412 days <br />0.0989 hours <br />5.886243e-4 weeks <br />1.35458e-4 months <br />, the mode switch was moved to start up. The reactor was taken critical at 0714 hours0.00826 days <br />0.198 hours <br />0.00118 weeks <br />2.71677e-4 months <br />.
On February 27,1997 at 0939 hours0.0109 days <br />0.261 hours <br />0.00155 weeks <br />3.572895e-4 months <br />, the mode switch was put in run.
On February 28,1997 at 0616 hours0.00713 days <br />0.171 hours <br />0.00102 weeks <br />2.34388e-4 months <br /> the main generator was syncronized to the grid for a three hour thermal soak period. The generator was tripped during a planned turbine valve tightness test at approximately 0915 hours0.0106 days <br />0.254 hours <br />0.00151 weeks <br />3.481575e-4 months <br />. At 1026 hours0.0119 days <br />0.285 hours <br />0.0017 weeks <br />3.90393e-4 months <br /> the turbine was syncronized to
~ the grid ending the refuel outage.
Unit 2 ended this operating period at 23% of RTP.
II.
Challenoes to Main Steam Safety Relief Valves i
There were no challenges to the Main Steam Safety Relief Valves during the month of February.
...... ~_._.
.. ~....
.. -. ~~ ~.
~
AVERAGE DAILY POWER LEVEL -
DOCKET NO. 50-353 UNIT LIMERICKUNIT2 DATE MARCH 10,1997 COMPANY PECO ENERGY COMPANY.
ROBERT A. BAXLEY REPORTS ENGINEER SITE ENGINEERING LIMERICK GENERATING STATION t
TELEPHONE (610)718-3767 MONTH FEBRUARY,1997 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWE-NET)
(MWE-NET) 1 0
17 0
2 0
18 0
t 3
0 19 0
4 0
20 0
5 0
21 0
6 0
22 0
i 7
0 23 0
8 0
24 0
9 0
25 0
to 0
26 0
11 0
27 0
12 0
28 94 13 0
14 0
15 0
t 16 0
u wc-m
-+
1
-e
< ~
_..m.-
m. _. _. -
-.m.
. =,... _. - -
b OPERATING DATA REPORT DOCKET NO. 50 -353 DATE MARCH 10,1997 p
COMPLETED BY PECO ENERGY COMPANY 1
i ROBERT A. BAXLEY REPORTS ENGINEER -
SITE ENGINEERING LIMERICK GENERATING STATION i
TELEPHONE (610)718-3767 OPERATING STATUS 1.- UNIT NAME:
LIMERICK _ UNIT,2 NOTES: THERE WAS ONE LOAD DROP
- 2. REPORTING PERIOD:
FEBRUARY,1997 1
GREATER THAN 20% THIS MONTH
- 3. LICENSED THERMAL POWER (MWT) 3458 ASSOCIATED WITH 2R04.
1163
- 4. NAMEPLATE RATING (GROSS MWE):
t 1115
- 5. DESIGN ELECTRICAL RATING (NET MWE):
- 6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):
1155
- 7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):
1115_
- 8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THROUGH 7 ) SINCE LAST REPORT, GIVE REASONS:
l
- 9. POWER LEVEL TO WHICH RESTRICTED,IF ANY (NET MWE):
- 10. REASONS FOR RESTRICTIONS,IF ANY:
?
THIS MONTH YR-TO-DATE CUMULATlVE y
672 1,41 6 62,616
- 11. HOURS IN REPORTING PERIOD 63.8 775.8 56,803.0
- 12. NUMBER OF HOURS REACTOR WAS CRITICAL 0.0 0.0 0.0
- 13. REACTOR RESERVE SHUTDOWN HGURS 16.6 727.6 55,686.7
- 14. HOURS GENERATOR ON-LINE 1
?
0.0 0.0 0.0
- 15. UNIT RESERVE SHUTDOWN HOURS i
16.~ GROSS THERMAL ENERGY GENERATED (MWH) 26,568 1,984,140 178,408,884 i
i
- 17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 2,000 640,800 50,031.080
-389 612,446 56,917,177
- 18. NET ELECTRICAL ENERGY GENERATED (MWH)
E r
PAGE 1 OF 2 i
. OPERATING DATA REPORT (CONTINUED)
DOCKET NO. '
50 -353 l
DATE MARCH 10,1997 -
THIS MONTH YR-TO-DATE CUMULATIVE 2.5 %
S1.4 %
88.9 % -
- 19. UNIT SERVICE FACTOR 2.5 %
51.4 %
88.9 % '
- 20. UNIT AVAILABluTY FACTOR
.1 %
38.8 %
84.7 %
- 21. UNIT CAPACITY FACTOR (USING MDC NET)
.1 %.
38.8 %
84.7 %
- 22. UNIT CAPACITY FACTOR (USING DER NET)
.0 #i
.D %
3.5 %
- 23. UNIT FORCED OUTAGE RATE
- 24. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE, DATE ANO DURATION Of EACHL
- 25. IF SHUTDOWN AT THE END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP; FORECAST ACHIEVED
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATIONS):
INITIAL CRITICAUTY 08/12/89 08/12/89 INITIAL ELECTRICITY 0001/89 0001/89 COMMERCIAL OPERATION 02/01/90 01A)S/90 PAGE 2 OF 2
=. -
- _ - _ ~.. ~
.. _. ~ ~. -
.- ~.
. - ~ -.-....- -.... -.
~n UNIT SHUTDOWNS AND POWER REDUCTIONS I
DOCKET NO. 50-353 UNITNAME LIMERICKUNIT2 DATE MARCH 10.1997 COMPLETED BY PECO ENERGY COMPANY ROBERT A. BAXLEY REPORTS ENGINEER SITE ENGINEER;NG t
t UMERICK GENERATING STATION REPORT MONTH FEBRUARY.1997 TELEPHONE (610)7183767
- t METHOD OF UCENSEE SYSTEM COMPONENT CAUSE AND CORRECTIVE TYPE DURATION REASON SHUTTING DOWN EVENT CODE CODE ACTION TO NO.
DATE (1?
(HOURS)
(2)
REACTOR (3)
REPORTS (4)
(S)
PRE'KNT RECURRENCE l
i i
186 970201 S
655.4 C
4 N/A RC FUELXX REACTOR WAS SHUTDOWN FROM PREVIOUS REPORTING PERIOD DUE TO 2R04 REFUEUNG
[
OUTAGE.
i TOTAL HOURS 655.4 i
L i
i a
v I
I p
I i
k 4
(1)
(2)
(3)
(4) t F-FORCED REASON METHOD EXHIBIT G -INSTRUCTIONS S - SCHEDULED A-EQUlPMENT FAILURE (EXPLAIN) 1 - MANUAL FOR PREPARATION OF DATA B - MAINTENANCE OR TEST 2-MANUAL SCRAM ENTRY SHEETS FOR UCENSEE C-REFUEUNG 3-AUTOMATIC SCRAM EVENT REPORT (LER)
D - REGULATORY RESTRICTION 4-OTHER (EXPLAIN)
FILE (NUREG-0161)
E - OPERATOR TRAINING + UCENSE EXAMINATION (5)
F-ADMfNISTRATIVE EXHIBIT I-SAME SOURCE G-OPERATIONAL ERROR (EXPLA N)
H -OTHER (EXPLAIN) i L
.