5 N=

TABLF 3.3.4-2 E

Q REACTOR CORE ISOLATION COOLING SYSTEM ACTUATION INSTRUMENTATION IJ ALLOWABLE FUNCTIONAL UNITS TRIP SETPOINT VALUE a.

Reactor Vessel Water Level - Low Low (Level 2) 2-55 inches

  • 2 -55 inches
  • b.

Condensate Storage Tank Level - Low 20 inches **

& 0 inches **

c.

Suppression Pool Water Level-High

$ 151 inches

$ 151 inches

  • See Bases Figure B 3/4 3-1
    • Equivalent to 10,000 gallons of water in the CST.