LER-1996-003, Forwards LER 96-003-01 Re Concurrent Inoperability of Edgs. Rev Submitted to Provide Addl Info Re Troubleshooting of Components Removed from EDG 1A |
| Event date: |
|
|---|
| Report date: |
|
|---|
| Reporting criterion: |
10 CFR 50.73(a)(2)(v), Loss of Safety Function |
|---|
| 3691996003R01 - NRC Website |
|
text
^
ll l
\\
Duke keer Cornpany T. C Mchirms AkCuire Nudear Genemtion Deparonen!
Vice President 12700Hagers FerryRoad(MG0lVP)
(704)8754800
('704)8754809 Fax DUKEPOWER
[
DATE:
November 7, 1996 l.
1 I
U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.. 20555
Subject:
McGuire Nuclear Station, Unit 1 Docket No.'50-369 Licensee Event Report 369/96-03, Revision 1 l
Problem Investigation Process No.:
0-M96-1753 Gentlemen:
Pursuant to 10 CFR 50.73 Sections (a) (1) and (d), attached is Licensee Event Report 369/96-03, Revision 1, concerning concurrent inoperability l
of both Unit 1 Emergency Diesel Generators.
This report is being subenitted in accordance with 10 CFR 50.73 (a) (2) (v).
This report also
. satisfies the Special Reporting requirements of Technical-Specification 3.8.1.1.
This revision is being submitted to provide additional information with regard to troubleshooting of the components removed from Emergency Diesel Generator 1A.
Also, it has now been determined that the failure of components associated with Emergency Diesel Generator 1A in this event is not Nuclear Plant Reliability Data System (NPRDS) reportable.
This event is considered to be of no significance with respect to the health and safety of the public.
Very truly yours, NJi
. c. Nc
.un JWP/bcb l
Attachment cca Mr.
S.D. Ebneter INPO Records Center Administrator, Region II Suite 1500 U.S. Nuclear Regulatory Commission 1100 circle 75 PrArkway 101 Marietta St., NW, Suite 2900 Atlanta, GA 30?39 Atlanta, GA 30323 Mr. Victor Norses Mr. Scott Schaeffer U.S. Nuclear Regulatory Commissic,n NRC Resident Inspector Office of Nuclear Reactor Regulation McGuire Nuclear Station Washington, D.C.. 20555 I
9611190261 961107 PDR ADOCK 05000369.
8 PDR
. -. -. - ~... - -... - -.
_ ~
bxc
- 3. L. Walch (EC11C)
E. L. T ylor (CNS)
,(
Q. A. Copp (EC050)
J. I. Glenn (MG02ME)
P. R. Herran (MG01VP)
C. B. Davis (MG01CP)
J.-E. Burchfield (ONS Reg Compliance)
G. H.
Savage (EC06E)
G. B. Swindlehurst (EC11-0842)
C. M. Misenheimer (EC08I)
R. F. Cole (EC05N)
J. M. Frye (EC05N)
T. G. Becker (PB02L) i P. M. Abraham (EC08I)
R. B. White (MG01VP)
L. V. Wilkie (ONO3SR)
D. P. Kimball (CNOSSR) l K.
L. Crane (MG01RC)
R.
N. Casler (EC05N)
NSRB Support Staff (EC05N)
?
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000369/LER-1996-001-01, Forwards LER 96-001-01 Re Manual Reactor Trip.Rev Due to Determination That Event Not NPRDS Reportable & Not Considered Significant Re Public Health & Safety | Forwards LER 96-001-01 Re Manual Reactor Trip.Rev Due to Determination That Event Not NPRDS Reportable & Not Considered Significant Re Public Health & Safety | 10 CFR 50.73(a)(2)(iv), System Actuation | | 05000369/LER-1996-001, :on 960203,manual Reactor Tripped When 1A RCP Upper Thrust Bearing Reached Administrative Limit of 195 Degrees.Caused by Unknown Equipment Failure.Associated Sys & Components Evaluated/Tested.Unit Returned to Svc on 960205 |
- on 960203,manual Reactor Tripped When 1A RCP Upper Thrust Bearing Reached Administrative Limit of 195 Degrees.Caused by Unknown Equipment Failure.Associated Sys & Components Evaluated/Tested.Unit Returned to Svc on 960205
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000369/LER-1996-002-01, :on 960204,inadvertent Manual Initiation of Unit 1 FW Isolation Occurred Due to Inappropriate Action. OPS Mgt Evaluated Depressing & Holding Train a & B CF Isolation |
- on 960204,inadvertent Manual Initiation of Unit 1 FW Isolation Occurred Due to Inappropriate Action. OPS Mgt Evaluated Depressing & Holding Train a & B CF Isolation
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(B) | | 05000369/LER-1996-003-01, Forwards LER 96-003-01 Re Concurrent Inoperability of Edgs. Rev Submitted to Provide Addl Info Re Troubleshooting of Components Removed from EDG 1A | Forwards LER 96-003-01 Re Concurrent Inoperability of Edgs. Rev Submitted to Provide Addl Info Re Troubleshooting of Components Removed from EDG 1A | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | | 05000369/LER-1996-003-03, :on 960618,concurrent Inoperability of Both Unit 1 Emergency Diesel Generators.Caused by Possible Equipment Failure/Malfunction.Shutdown of EDGs & Replaced Failed Components |
- on 960618,concurrent Inoperability of Both Unit 1 Emergency Diesel Generators.Caused by Possible Equipment Failure/Malfunction.Shutdown of EDGs & Replaced Failed Components
| | | 05000369/LER-1996-003, :on 960618,during Scheduled Operability Test of EDG 1A,EDG Declared Inoperable.Caused by Equipment Failure/ Malfuction of EDG 1A & Equipment Failure & Mfg Process Deficiency of EDG 1B.EDGs SD & Failed Components Replaced |
- on 960618,during Scheduled Operability Test of EDG 1A,EDG Declared Inoperable.Caused by Equipment Failure/ Malfuction of EDG 1A & Equipment Failure & Mfg Process Deficiency of EDG 1B.EDGs SD & Failed Components Replaced
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000369/LER-1996-004, :on 961010,incorrectly Calibrated Rcl Loss of Flow Reactor Trip Bistables Identified.Caused by Procedural/ Technical Inaccuracy.All Affected Procedures Were Changed & Instruments Calibrated within TS Limits |
- on 961010,incorrectly Calibrated Rcl Loss of Flow Reactor Trip Bistables Identified.Caused by Procedural/ Technical Inaccuracy.All Affected Procedures Were Changed & Instruments Calibrated within TS Limits
| 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) | | 05000369/LER-1996-004-05, :on 961010,incorrectly Calibrated Reactor Coolant Loop Loss of Flow Reactor Trip Bistables Identified. Caused by Procedure Technical Inaccuracy.All Affected Procedures Were Changed |
- on 961010,incorrectly Calibrated Reactor Coolant Loop Loss of Flow Reactor Trip Bistables Identified. Caused by Procedure Technical Inaccuracy.All Affected Procedures Were Changed
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(1) | | 05000369/LER-1996-005-01, :on 961101,TS Required Shutdown of Both Units Due to Failed Surveillance Test of Vital Battery Evcc.Caused Is Unknown.Replaced & Retested Vital Battery Bank Evcc |
- on 961101,TS Required Shutdown of Both Units Due to Failed Surveillance Test of Vital Battery Evcc.Caused Is Unknown.Replaced & Retested Vital Battery Bank Evcc
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(x) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(1) | | 05000369/LER-1996-005, Forwards Suppl Info Re LER 96-005,rev 1 Re TS Required Shutdown of Both Units Due to Failed Surveillance Test of Vital Battery Bank Evcc.Rev Changes Commitment Re Vital Battery Vank Evcc | Forwards Suppl Info Re LER 96-005,rev 1 Re TS Required Shutdown of Both Units Due to Failed Surveillance Test of Vital Battery Bank Evcc.Rev Changes Commitment Re Vital Battery Vank Evcc | | | 05000369/LER-1996-005-04, :on 961101,TS Required Shutdown of Both Units Occurred Due to Failed Surveillance Test of Vital Battery Evcc.All Vital Battery Banks Will Be Replaced with Conventional Batteries by End of 2EOC11 Outage |
- on 961101,TS Required Shutdown of Both Units Occurred Due to Failed Surveillance Test of Vital Battery Evcc.All Vital Battery Banks Will Be Replaced with Conventional Batteries by End of 2EOC11 Outage
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(1) | | 05000369/LER-1996-006, :on 961109,actuation of Both Unit 1 Motor Driven Feedwater Pumps Were Manually Initiated Due to Loss of Auxiliary Steam Supply to Main Feedwater Pump Turbine. Pump Has Been Repaired |
- on 961109,actuation of Both Unit 1 Motor Driven Feedwater Pumps Were Manually Initiated Due to Loss of Auxiliary Steam Supply to Main Feedwater Pump Turbine. Pump Has Been Repaired
| 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(1) | | 05000369/LER-1996-006-03, :on 961109,manually Initiated Actuation of Unit 1 Driven AFW Pumps Occurred Due to Loss of as Supply to MFW Pump Turbine.Caused by Insufficient Lubrication.No Corrective Actions Right Now |
- on 961109,manually Initiated Actuation of Unit 1 Driven AFW Pumps Occurred Due to Loss of as Supply to MFW Pump Turbine.Caused by Insufficient Lubrication.No Corrective Actions Right Now
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(1) | | 05000369/LER-1996-007-02, :on 961107,mode Related Missed TS Surveillance on Containment Integrity Discovered Due to Technical Inaccuracy.Pm/Pt Database Corrected & TS Surveillance Quality Improvement Team Formed |
- on 961107,mode Related Missed TS Surveillance on Containment Integrity Discovered Due to Technical Inaccuracy.Pm/Pt Database Corrected & TS Surveillance Quality Improvement Team Formed
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(1) |
|