OC'IOBER 28, 1996
Florida Power Corporation
Crystal River Energy Complex
Mr. P. M. Beard, Jr. (SA2A)
Sr. VP, Nuclear Operations
ATTN: Mgr., Licensing
15760 Wes Power Line Street
Crystal River, FL 34428-6708
SUBJECT:
NRC SPECIAL INSPECTION REPORT 50-302/96-13
Dear Mr. Beard:
On October 9,1996, the NRC completed a specialinspection involving a potential component
tampering event at your Crystal River facility. The endosv.ed report presents the results of
that inspection.
This special inspection was conducted to review the adequacy of an investigation by the
licensee of a potential tampering event involving a coin (penny) found in an oil strainer
housing on September 19,1996. The penny had obstructed the flow of oil to cooling fan
gears for Crystal River emergency diesel generator 1A. The licensee's investigation
concluded that the penny most likely became lodged in a strainer element when the element
,
was in a mechanic's pocket and that the penny was inadvertently introduced into the strainer
housing when the element was installed. Thus the licensee concluded that tampering did not
occur. The NRC inspection supports this conclusion. Other equipment was inspected by the
NRC and the licensee for evidence of tampering and none was found. The NRC inspection
concluded that the licensee's investigation was adequate, the emergency diesel generator
was restored to an operable condition, and that tampering most likely did not occur.
Within the scope of the inspection, violations or deviations were not identified.
In accordance with 10 CFR 2.790, of the NRC's " Rules of Practice," a copy of this letter will
be placed in the NRC Public Document Room.
Should you have any questions concerning this letter, please contact us.
Sincerely,
ORIGINAL SIGNED BY
ALBERT F. GIBSON
9611040209 961028
gDR
ADOCK 0500
2
Albert F. Gibson, Director
Division of Reactor Safety
Docket No. 50-302
License No. DPR-72
Ia
Enclosure: Inspection Report 50-302/96-13
04000%cl:
cc w/
(See page 2)
.2Te1
-
'.
<
2
cc w/ encl:
Gary L. Boldt, Vice President
Nuclear Production (SA2C)
Florida Power Corporation
Crystal River Energy Complex
15760 West Power Line Street
Crystal Piver, FL 34428-6708
B. J. Hickle, Director
Nuclear Plant Operations (NA2C)
Florida Power Corporation
Crystal River Energy Complex
15760 West Power Line Street
Crystal River, FL 34428-6708
L. C. Kelley, Director (SA2A)
Nuclear Operations Site Support
Florida Power Corporation
Crystal River Energy Complex
15760 West Power Line Street
Crystal River, FL 34428-6708
Rodney E. Gaddy
Corporate Counsel
Florida Power Corporation
MAC - ASA
P. O. Box 14042
St. Petersburg, FL 33733
Attorney General
Department of Legal Affairs
Tne Capitol
Tallahassee, FL 32304
Bill Passetti
Office of Radiation Control
Department of Health and
Rehabilitative Services
1317 Winewood Boulevard
,
Tallahassee, FL 32399-0700
cc w/ encl: (Cont'd on page 3)
.
~,
,
.
3
(cc w/ encl: cont'd)
Joe Myers, Director
Division of Emergency Preparedness
Department of Community Affairs
2740 Centerview Drive
Tallahassee, FL 32399-2100
Chairman
Board of County Commissioners
Citrus County
110 N. Apopka Avenue
inverness, FL 34450-4245
Robert B. Borsum
Framatome Technologies
1700 Rockville Pike, Suite 525
,
l
Rockville, MD 20852-1631
Distribution w/ encl:
K. Landis, Ril
L. Raghavan, NRR
B. R. Crowley, Ril
G. Hopper, Rll
G. A. Hallstrom, Ril
l
PUBLIC
l
NRC Resident inspector
U.S. Nuclear Regulatory Comm:ssion
l
6745 N. Tallahassee Road
Crystal River, FL 34428
!
pit .nco . O
pi t -rids
MON
orricr
o!!.nps
oli nos
ott-egs
kW
fricson
- "##
C.iVW
'
,
c,
ppMM
Btr
y
L ratton
PFr
Klan
'r
"
1{/
IMlh / 96
10 / @ / 96
10 /
/ 96
D
/ 96
10 / 2.2-r 9L
10 /() / 96
OATE
COPY?
DES)
NO
[YES)
NO
YES
/NO)
[E)
NO
M
NO
YES
(NO)
,
OF r ICIAL EORD COP t
70LUMtNi NAMt: F:\\CkLAyf
y
.