g TABLE 4.3-2 (Continued)

ENGINEERED SAFEGUARDS SYSTEM INSTRUMENTATION SURVEILLANCE REQUIREMENTS

~

CHANNEL MODES IN WHICH CHANNEL CHANNEL FUNCTIONAL SURVEILLANCE FUNCTIONAL UNIT CHECK CALIBRATION TEST REQUIRED 2.

CONTAINMENT ISOLATION (Continued) c.

Actuation Channel B S

NA M(4) 1, 2, 3, 4, 5*

1)

High Containment S

R(3)

M(3) 1, 2, 3, 4, 5

  • Pressure Sensor 2)

Safety Injection (All Safety Injection Surveillance Requirements)

U 3.

MAIN STEAM ISOLATION Y

1a.

Low Steam Line Pressure S

R(3)

M(3) 1, 2 b.

Automatic Trip Logic NA NA Q

1,

  • 2 c.

Manual Initiation NA NA R

1, 2 d.

High Containment Pressure 10(

NA R

1, 2 4.

LOSS OF POWER' 480 Volt Emergency Bus NA R

M(5) 1, 2, 3 c.

Degraded Voltage 5

E

?

gDR510220059 851016 l

ADOCM 05000029 p

PDR m

__. _.,__=.__.___

TABLE 4.3-2 (Continued)

TABLE NOTATION (1) When shut down with main coolant pressure < 1000 psig, if not performed within the previous 31 days.

(2) When shut down longer than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, if not performed in the previous 31 days.

I (3) The test shall include exercising the sensor by applying either a vacuum or pressure to the appropriate side of the sensor.

(4) When in COLD SHUTDOWN with main coolant pressure < 300 psis, if not performed within the previous 31 days.

(5) Monthly surveillance shall be performed on the degraded voltage protection only.

Surveillance of loss of voltage protection shall be performed at least once per 18 months.

Not required in this MODE with main coolant pressure < 300 psig.

I Not required in this MODE with main coolant pressure < 1700 psig.

4 4

3 i

1 i

k f

f i

I i

l i

AmendmentNo.jP[JM(

YANKEE-ROWE 3/4 3-16 i

.