NIAGARA M0flAWK POWER CORPORATION NINE MILE POINT NUCLEAR STATION UNIT #1 NARRATIVE OF OPERATING EXPERIENCE I
The station operated during the month of September 1985 with a Unit f
Availability Factor of 100.0 and a Net Design Electrical Capacity Factor of 93.2.
There were 0 challenges to Electromatic Relief Valves. Reductions in Capacity Factor were due to high circulating water temperatures and control rod sequence exchange.
CLASS I WORK - MECHANICAL MAINTENANCE - SEPTEMBER 1985 hRV 34515 44-10-39 CRD Hyd Cont Unit foot valve removed and replaced packing l
and 'O' rings.
72-146 Rx Bldg. Serv. H O drag valve - installed straps on 2
=
hR# 34517 support and 2 studs and plates.
hR# 34516 94-01 #11 Inst air comp - replaced oil scraper rings.
l hR# 34318 201.1, 23, 24 - removed beam clamp left by contractor from support and taken from gated area. Not needed to support pipe.
hR# 34534 93 wiped up oil on operator.
l hR# 34535 93 wiped up oil on operator.
hR# 34536 93 wiped up oil on operator.
i hR# 34533 93 wiped up oil on operator.
hR# 34763
- 11 foot valve on CRD 34 replaced packing and 'O' rings.
hR# 33007
- 12 Inst air com - open, insp. and rebuilt compressor.
Installed new pistons HP and LP and push rods.
hR# 21234
- 93 cont. spray raw water pump - rebuilt.
hR# 31816 44-10-39 foot valve - replaced packing.
2 i
WR# 33667 44-38-35 CRD accumulator - replaced packing.
L CLASS I KORK - ELECTRICAL MAINTENANCE - SEPTEMBER 1985 I
No Class I, Safety Related, Corrective Maintenance performed this month.
CLASS I WORK - INSTRUMENTATION 6 CONTROL - SEPTEMBER 1985 hR# 34247 CAD monitor System #11 gives downscale oxygen reading when not in test / calibration mode.
(adjusted zero) hR# 34446 Containment spray raw water pump #122 Flow indicator shows elevated flow reading when pump is off.
(Static on meter face) hR# 33786 Diesel fire pump hoses frayed (reattached new braided hose and replaced old reinforced rubber oil lines).
hR# 33663 Instrument air compressor #12 loading solednoids leaking j
(installed normally opened SOV's),
i l
1 l
TCPl l
8510180236 850930 l/
DR ADOCK 05000220 PDR
OPERATING DATA REPORT DOCKET NO. 50-220 10/4/85 d DATE C0%IPLETED llY TWRoman30
/
TELEPHONE 110_?3??
OPERATING STATUS i
- 1. Unit Name:
Nine Mile Point Unit I Notes
- 2. Reporting Feriod:
9/1/85 to 9/30/85 1850
- 3. Licensed Thennal Power (MWt):
640
- 4. Namepiste Rating (Gross MWe):
620
- 5. Dengn Electncal Rating (Net MWe):
630
- 6. Maximum Dependable Capacity (Gross MWe):
610
- 7. Maximum Dependable Capacity (Net MWe):
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Give Reasons:
1 I
- 9. Power Level To which Restricted,if Any (Net MWe):
- 10. Reasons For Restrictions.lf Any:
I This Month Yr. to-Date Cumularise I1. Hours In Reporting Period 720 6531 147,147,2
- 12. Number Of Hours Reactor Was Critical 720 6494 99,209.7
- 13. Reactor Reserve Shutdown Hours 0
0 1,204.2
- 14. Hours Generator On-Line 720 6469 96,274.3
- 15. Unit Reserve Shutdown Hours 0
0 20.4
- 16. Gross Thermal Energy Generated (MWH) 1.304.559 11.672.912 160,962,362
- 17. Gross Electrical Energy Generated (MWH) 429,269 _, 3.908.145 53.288.933
- 18. Net Electrical Energy Generated (MWH) 416,007_
3,789,857 51,619,851
- 19. Unit Service Factor 100.0 99.1 70.6
- 20. Unit Availability Factor 100.0 99.1 71.4
- 21. Unit Capacity Factor (Using MDC Netl' 94.7 94.8 60.2
- 22. Unit Capacity Factor (Using DER Net) 93.2 93.3 59.2
- 23. Unit Forced Outage Rate 0.0 1.3 15.6
- 24. Shutdowns Scheduled Over Next 6 Months (Type. Date, and Duration of Each t:
- 25. If Shut Down At End Of Report Period. Estimated Date of Startup:
- 26. Units In Test Status (Prior to Commercial Operation):
Forecast Achieved INITIAL CRITICALITY INITIA L ELECTRICITY COMMERCIAL OPERATION go/77i
b AVER \\GE D ALLY UNIT POhER LEVEL DOCKET NO.
50-220 L'NI T _NMP-1 DATE 10/4/85 TW Roman k
/
l CO\\1PLETED BY TELEPIIONE f315)349-2422 SiONTH September 1985 DAY AVERACE DAILY POWER LEVEL DAY AVER ACE DAILY POWER LEVEL IMhe Net)
(MWe-Net )
600 588 g-594 is 590 3
605 59 586 4
582
- o 585 5
581 21 400 6
583 508 7
518 556 23 8
577 24 584 9
580 25 588 10 583 26 585 11 599 583 53 600
- S 58o 13 601 586 29 g4 M96 30 581 IS 588 3
16 592 INSTRUCTIONS Ori this for:nst.hst the aserage dat!) unit power lesel tii \\lWe-Net for exh das in ilie rep. iting in.. nth. C..nipute io the nearest whole megawatt.
goi ;3
.a 50-220 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.
UNIT NAME NMP-1 DATE 10/4/85 7 )
REPORT MON fit Sept. 1985 COMPLETED BY TW 12nm inn-/
TELEPHONE f41 O tao _')a f?
"t
.5 g 3
Yh Licensee
$w, k
Cause & Correceive h'E No.
Daic g
3g s
js&
Event p
Action to fI u
j p, g Report a vs V j'
Prevent Recurrence H
d 850920 S
69.25 11 4
Control Rod Sequence Exchange I
I 2
3 4
F: Forced Reason:
Method:
Exhibit G - Instructions S. Scheduleil A-Equipment Failure (Explain) 1 -Manual for Preparation oI Data B-Maintenance of Test 2 Manual Scram.
Entry Sheets for Licensee C Refueling 3 Automatic Scram.
Event Report (LER) File (NUREG-D Regulatory Restriction 4 Other (Explain) 0161)
L-Opeutor Training & License Examination F-Adnunistrative 5
G Operatiosul E ror (Explain)
Exlubit i. Same Source 08/77)
Il Othes (E xplain)
NktP-14536 b
NIAGARA MOHAWK POWER CORPORATION NI AG A R A MOHAWK 300 ERIE BOULEV ARD WEST SVRACUSE.N Y.13202 Octobe1 4, 1985 DLtector Office of Inspection and Enforcemerl U.S. Nuclea.1 Regulatory Commbsion Wasitington, DC 20555 Attn:
Document and Conttol Desk Re: Docket No. 50-220 DPR-63
Dear S4t:
Subotitted herewitit is the Report of Operating Statistics and shutdown fo.1 Septembcr 1985 fo.1 the Nine blite Point Nacicar Station Unit *1.
Also included b a na.trative report af Operating Experience f0.1 September 1985.
Vety ttaly yours, 6%i f '
i av.L Thomas E. Lenpges Vice President Nuclear Generation TEL/tg Attachments cc: 04tecto.1, Office of I6E (10 copies) h V