ML20133B403

From kanterella
Jump to navigation Jump to search
First Interim Deficiency Rept Re Intake Pumping Station Electrical Equipment Room Exhaust Fans & Dampers Not Meeting IEEE Requirements.Initially Reported on 850823.Next Rept Expected by 880131
ML20133B403
Person / Time
Site: Bellefonte  
Issue date: 09/19/1985
From: Hufham J
TENNESSEE VALLEY AUTHORITY
To: Grace J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
NUDOCS 8510030273
Download: ML20133B403 (3)


Text

P TENNESSEE VALLEY AUTHORITY CH ATTANOOGA, TENNESSEE 37401 400 Chestnut'Str6et fower II A

Off. g September 19, 1985 BLRD-50-438/85-26 BLRD-50-439/85-23 U.S. Nuclear Regulatory Commission Region II Attn:

Dr. J. Nelson Grace, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323

Dear Dr. Grace:

BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - INTAKE PUMPING STATION ELECTRICAL EQUIPMENT ROOM EXHAUST FANS AND DAMPERS DO NOT MEET IEEE REQUIREMENTS -

BLRD-50-438/85-26. BLRD-50-439/85 FIRST INTERIM REPORT The subject deficiency was initially reported to NRC-OIE Inspector Al Ignatonis on August 23, 1985 in accordance with 10 CFR 50.55(e) as Significant Condition heport (SCR) BLN EEB 8511.. Enclosed is our first interim report. We expect to submit our next report on or about January 31, 1988.

If you have any questions, please get in touch with R. II. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY fyytL{

. W. Hufham, Manager Licensing and Risk Protection Enclosure cc:

Mr. James Taylor, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Records Center (Enclosure)

Institute of Nuclear Power Operations i

I 1100 circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 i

1 s

S 1

An Equal Opportunity Employer l

gg

N-ENCLOSURE BELLEFWTE NUCLEAR PLANT UNITS-1 AND 2 INTAKE PUMPING STATION ELECTRICAL EQUIPENT ROOM EXHAUST FANS AND DAEEE DO NOT EET IEEE REQUIREENTS BLRD-50-438/85-26, BLRD-50-439/85-23 SCR BLN EEB 8511 10 T R 50. 55(e )

FIET INTERIM EPORT i

Description of Deficiercl During the developnent of mrrective action for nonconforuanoe report (Nm )

BLN EB 8405 ( BLRD-50 -43 8/83 -31 ; B LRD-50 -43 9/83 -27) to configure the intake pumping statton electrical equipnent rooms ventilation aysten for a tomado,

it was dismvered that the heating, ventilating, and airi-conditioning (HI AC) exhaust farn and dampers for the intake pumping station were being f ed f ran and controlled by trained class 1E power, but the compnents were not IEEE class 1E qualified. The desis does not grovide IEEE 3 94 -1977-appro ved electrical isolation as is reg 2 ired when non-1E loads are powered f rom 1E power supplles.

The early desip of thts systen was basal upon a misintertretatl1on of Bel 1ermte Nuclear P lant (BLN) Desiy C riteria N4-VP-UT40.

Tht_s eriteria excludes the exhamt compnents from the saf ety-relatei portions lof the syst en. However, desis drawing stow this eglitment as.being trained (s af et y rel at ed ). The origiral issm of the desim criteria muld have been intergreted as assiming the ventilaticn syst en as a wtole to a saf ety f m eti on. A later revisico of the desim criteria more clearly di ff ere nti at ed the saf et y and nons af et y por ti ons of thi s syst en.

Interim P reg ress Corrective action is being talen to mp1 ace the presently irntalled cireuit brealers feeding the exhaust fans and dampers with circuit treakers having a l

shunt trip mechanism which will actate upn an engineered safety f eature l

actmticn (ESFAS) sipal. ThLs will open the circuit-downstream of the brealer during an accident and elimitate any potential interaction origLnating in the non-class 1E com;nnents. All desis documents wLil be revised to be in agreement with BLN Desig Criteria N4-VP-UT40.

Since thi s defi ct ency aros e f run a misi nt er pret ati on of D esi m C rt teri a N4 -

VP-UT40, and since thLs desip criteria has been revised to more clearly differentiate the saf ety and nonsafety portions of the systen, additional action to grevent recurrenm is not reg 11 red.

I i

i i

- _