E O 9 ENCLOSURE TO SERIAL NO. NLS-85-267 PROPOSED BRUNSWICK-2 TECHNICAL SPECIFICATION PAGE l

l l

8507180184 850712 PDR ADOCK 05000324 P

PDR

SUMMARY

LIST OF REVISIONS Page Description of Change 3/46-8 1.

Footnote allowing temporary increase in primary containment average air temperature limit added to Section 3.6.1.6.

2.

" CONDITIONS" changed to " OPERATIONAL CONDITIONS".

f I

i l

t L

l L..

(BSEP-2-67)

CONTAINMENT SYSTEMS PRIMARY CONTAINMENT AVERACE AIR TEMPERATURE LIMITING CONDITION FOR OPERATION 3.6.1.6 Primary containment average air temperature shall not exceed 135 F.*

l APPLICABILITY: OPERATIONAL CONDITIONS 1, 2, and 3.

l ACTION:

With the primary containment average air temperature > 135 F*,

reduce the l

average air temperature to within the limit within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.6.1.6 The primary containment average air temperature shall be the volumetric average of the temperatures at the following locations and shall be determined at least once per 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />s:

Location a.

Below 5' elevation, b.

Between 10' and 23' elevation, c.

Between 28' and 45' elevation, d.

Between 70' and 80' elevation, and e.

Above 90' elevation.

  • The primary containment average air temperature limit may be increased to 140*F until August 15, 1985, at which time the limit will be returned to 135'F.

BRUNSWICK - UNIT 2 3/4 6-8 Amendment No.