Monthly Operating Repts for Nov 1996 for Braidwood Nuclear Power Station,Unit 1 & 2
ML20132B951
Person / Time
Site: Braidwood  
Issue date: 11/30/1996
From: Eliakis T, Pershey C, Tulon T
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
BW-96-0095, BW-96-95, NUDOCS 9612180030
Download: ML20132B951 (10)


Text

'

4 Commonwealth litiwn Company liraidwood Generating Station Route 01,11ox Hi a

litaces ille, II. 60 407 Axil 9 Tel H15-45R2801 December 5,1996 BW/96-0095 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555-0001

Subject:

Monthly Operating Report for November,1996 Braidwood Nuclear Power Station, Units I and 2 Facility Operating Licenses NPF-72 and NPF-77 NRC Docket Nos. 50-456 and 50-457 Ladies and Gentlemen:

In accordance with Technical Specification 6.9.1.8, enclosed you will find the Monthly Operating Report for Commonwealth Edison Company's (Comed's) Braidwood Nuclear Power Station, Units I and 2, covering the penod November 1,1996 through November 30, 1996.

Please address any comments or questions regarding this matter to Chris Pershey at (815) 458-2801, extension 2173.

Very truly yours, T

'ulon tion Manager

\\

l Braidwood Nuclear Station h&

TJT/CP/bl O:\\CORREsPZCSTECif BW96 0095 Enclosures cc:

A. B. Beach, Regional Administrator - RIII R. R. Assa, Braidwood Project Manager - NRR C. J. Phillips, Senior Resident inspector - Braidwood T. J. Esper, IDNS Resident Inspector - Braidwood Office of Nuclear Facility Safety - IDNS 9612180030 961130 PDR ADOCK 05000456 R

PDR H70038 A l'nicom Compan)

BRAIDWOOD NUCLEAR POWER STATION UNIT I AND UNIT 2 MONTHLY PERFORMANCE REPORT Comed NRC DOCKET NO. 050-456, LICENSE NO. NPF-72 NRC DOCKET NO. 050-457, LICENSE NO. NPF-77 i

i

~

I i

A. OPERATING DATA REPORT Docket No: 50 - 456 Unit: Braidwood 1 Date: 12/05/1996 Completed by: Chris Pershey Telephone: 815-458-2801 4

OPERATING STATUS

1) Reporting Period: November 1996 Gross Hours:

720

2) Currently Authorized Power Level (MWt):

3411 Design Electrical Rating (MWe-gross):

1175 Design Electrical Rating (MWe-net):

1120 Max Dependable Capacity (MWe-gross):

1175 Max Dependable Capacity (MWe-net):

1120

3) Power level to which restricted (if Any):

None i

4) Reasons for restrictions (If Any):

None This Mo.

Yr to Date Cumulative

5) Report Period Hours:

720 8040 73113

6) Hours Reactor Critical:

0.0 6,356.1 57,334.0

7) RX Reserve Shutdown Hours:

0.0 0.0 0.0

)

8) Hours Generator on Line:

0.0 6,339.1 56,519.8

9) Unit Reserve Shutdown Hours:

0.0 0.0 0.0 10 Gross Thermal Energy (MWHt):

0 20,923,111 179,407,927 11 Gross Elect. Energy (MWH):

0 7,219,784 60,610,104 12 Net Elect. Energy (MWH):

10,010 6,934,041 58,061,401 13 Reactor Service Factor:

0.0 79.1 78.4 14 Reactor Availability Factor 0.0 79.1 78.4 15 Unit Service Factor:

0.0 78.8 77.3 16 Unit Availability Factor:

0.0 78.8 77.3 17 Unit Capacity Factor (MDC NET):

-1.2 77.0 70.9 18 Unit Capacity Factor (DER NET):

-1.2 77.0 70.9 19 Unit Forced Outage Rate:

0.0 7.3 7.7 20 Unit Forced Outage Hours:

0.0 499.9 4,714.4 21 Shutdown Schedule Over Next 6 Months:

22 If Shutdown at End of Reporting Period, Estimated Date of Startup:

12/2/96

+

B. AVERAGE DAILY UNIT NET POWER LEVEL LOG Docket No: 50 - 456 Unit: Braidwood 1 Date: 12/05/1996 Completed by: Chris Pershey Telephone: 815-458-2801 MONTH: November 1996 p_ay MWe-net Qay MWe-net a

1)

-13 16)

-14 2)

-13 17)

-14 3)

-13 18)

-14 4)

-13 19)

-14 5)

-13 20)

-14 6)

-13 21)

-14 7)

-13 22)

-14 8)

-13 23)

-14 9)

-13 24)

-14 10)

-13 25)

-14 11)

-14 26)

-14 12)

-14 27)

-14 13)

-13 28)

-14 j

14)

-14 29)

-14 15)

-13 30)

-15

  • Due to condenser efficiency

C.

UNIT SHUTDOWNS / REDUCTIONS Docket No.:

50- 456 Unit:

Braidwood 1 Date: 12/05/96 Completed by:

Chris Pershey Telephone:

815-458-2801 REPORT PERIOD:

November 1996 LER Cause & Corrective Action h

Date Type Hours Reason Method Number System Component to Prevent Recurrence 6

961101 S

720.0 8

4 N/A RC TBG Continuation of scheduled maintenance outage to allow inspection of steam generator tubing.

SUMMARY

Unit 1 entered the month of November in a scheduled maintenance outage to inspect the steam generator tubing. The unit remained shutdown through the end of the month.

TYPE REASON METHOD SYSTEM & COMPONENT F - Forced A - Equipment Failure Maint or Test 1 - Manual S - Scheduled B - Maint or Test 2 - Manual Scram Exhibit F & Instructions for C - Refueling 3 - Auto Scram Preparation of Data Entry Sheet D - Regulatory Restriction 4 - Continued Licensee Event Report (LER) File E - Operator Training & Licensee Examination 5 - Reduced Load (NUREG-0161).

F - Administration G - Operator Error H - Other

D.

SAFETY / RELIEF VALVE OPERATIONS Docket No.:

50 - 456 Unit:

Braidwood 1 Date: 12/05/96 Completed by:

Ted Eliakis Telephone:

815-458-2801 Valves No. & Type Plant Date Actuated Actuation Condition Description of Event None

j.*

A. OPERATING DATA REPORT Docket No: 50- 457 Unit: Braidwood 2 Date: 12/05/1996 Completed by: Chris Pershey Telephone: 815-458-2801 OPERATING STATUS

1) Reporting Period: November 1996 Gross Hours:

720

2) Currently Authorized Power Level (MWt):

3411 Design Electrical Rating (MWe-gross):

1175

)

Design Electrical Rating (MWe-net):

1120 l

Max Dependable Capacity (MWe-gross):

1175 Max Dependable Capacity (MWe-net):

1120

3) Power level to which restricted (If Any):

None

4) Reasons for restrictions (if Any):

None This Mo.

Yr to Date Cumulative l

5) Report Period Hours:

720 8040 71195 i

6) Hours Reactor Critical:

720.0 6,623.7 60,045.1

)

7) RX Reserve Shutdown Hours:

0.0 0.0 0.0

8) Hours Generator on Lins:

720.0 6,606.0 59,632.1

9) Unit Reserve Shutdown Hours:

0.0 0.0 0.0 10 Gross Thermal Energy (MWHt):

2,441,614 21,865,063 192,648,518 11 Gross Elect. Energy (MWH):

838,346 7,458,788 63,364,575 q

12 Net Elect. Energy (MWH):

811,755 7,168,353 60,804,121 13 Reactor Service Factor 100.0 82.4 84.3 14 Reactor Availability Factor:

100.0 82.4 84.3 15 Unit Service Factor:

100.0 82.2 83.8 16 Unit Availability Factor:

100.0 82.2 83.8 17 Unit Capacity Factor (MDC NET):

100.7 79.6 76.3 18 Unit Capacity Factor (DER NET):

100.7 79.6 76.3 19 Unit Forced Outage Rate:

0.0 0.0 4.7 20 Unit Forced Outage Hours:

0.0 0.0 2,947.6 21 Shutdown Schedule Over Next 6 Months:

22 If Shutdown at end of Reporting Period, Estimated Date of Startup:

B. AVERAGE DAILY UNIT NET POWER LEVEL LOG Docket No: 50 - 457 Unit: Braidwood 2 Date: 12/05/1996 Completed by: Chris Pershey Telephone: 815-458-2801 MONTH: November 1996 Ray MWe-net Day plWe-net 1

1) 1130

  • 16) 1132
  • 2) 1134
  • 17) 1129
  • 3) 1135
  • 18) 1129
  • 4) 1136
  • 19) 1129
  • 5) 1136
  • 20) 1129
  • 6) 1135
  • 21) 1131
  • 7) 1135
  • 22) 1131
  • 8) 1135
  • 23) 1131
  • 9) 1135
  • 24) 1066 10) 1135
  • 25) 1119 1

11) 1134

  • 26) 1117 12) 1135
  • 27) 1119 13) 1133
  • 28) 1117 14) 1133
  • 29) 1107 15) 1135
  • 30) 1105 l

l l

~.

t C.

UNIT SHUTDOWNS / REDUCTIONS Docket No.:

50 - 457 Unit:

Braidwood 2 Date: 12/05/96 Completed by:

Chris Pershey Telephone:

815-458-2801 REPORT PERIOD:

November 1996 LER Cause & Corrective Action h

Date Type Hours Reason Method Number System Component to Prevent Recurrence l

None i

t s

      • S U MMARY***

Unit 2 entered the month of October 1996 at 100% capability and operated routinely the entire month.

TYPE REASON METHOD SYSTEM & COMPONENT F - Forced A - Equipment Failure Maint or Test 1 - Manual i

S - Scheduled B - Maint or Test 2 - Manual Scram Exhibit F & Instructions for j

C - Refueling 3 - Auto Scram Preparation of Data Entry Sheet D - Regulatory Restriction 4 - Continued Licensee Event Report (LER) File l

E - Operator Training & Licensee Examination 5 - Reduced Load (NUREG-0161).

i F - Administration G - Operator Error l

H - Other i

D.

SAFETY / RELIEF VALVE OPERATIONS Docket No.:

50- 457 Unit:

Braidwood 2 Date: 12/05/96 Completed by:

Ted Eliakis Telephone:

815-458-2801 Valves No. & Type Plant Date Actuated Actuation Condition Description of Event None i

.