NUMOHAWK Y NIAGARA l

i NLAGARA MOHAWK POWER CORPORATION /304 ERLE BOULEVARD WEST. SYRACUSE. N Y.13202/ TELEPHONE (315) 474-1511 August 29, 1985 (NMP2L 0481)

Mr. R. W. Starostecki, Director U.S. Nuclear Regulatory Comission Region I Division of Reactor Pmjects 631 Part Avenue King of Prussia, PA 19 406 Re: Nine Mile Point - Unit 2 Docket No. 50-410

Dear Mr. Starosteckt:

Enclosed is an interim report in accordance with 10CFR50.55(e) for the problem concerning Yelan valve 2 MSS *MOVll2 body material qualification.

This problem was reported via tel-cral to 'J. Linville of your staff on July 30, 1985 Very truly yours, C. V. Mangan Senior Vice President CVM/GG/cla (1209H) xc: Director of Inspection and En' orc ment U.S. Nuclear Regulatory Comis fon Washington, DC 20555 R. A. Gramm, NRC Senior Resident 'ns, ector Project File (2) 8509260054 8 % 10 PDR ADOCK O PDR S

it p1

~

le NIAGARA M0 HAWK POWER CORPORATION 4

NINE MILE POINT - UNIT 2 00CKET NO. 50-410 Interim Report for a Problem Concerning Velan Valve 2 MSS *MOV112 Body Material Qualification (55(e)85-25)

Description of the Problem During a review of documentation it was observed that the certified material test reports provided -by the valve manufacturer did not document the test coupon heat treatment duration and temperature as required by ASME Section III, NB-2211.

A separate test forging.has been located that has the same heat lot number as the valve body.

Heat treatment and impact testing of test coupons will be perfonned and evaluated.

The matter is still being investigated and a final report will be submitted by December 20, 1985, i

I i

l l

.