May 20, 1985 Decket Nos. 50-325/324 Mr. E. E. Utley Executive Vice President Carolina Power & Light Company Post Office Box 1551 Raleigh, North Carolina 27602

Dear Mr. Utley:

SUBJECT:

CONTAINMENT PURGE AND VENT Re:

Brunswick Steam Electric Plant, Units 1 and 2 By letter dated December 21, 1984, as supplemented April 26, 1985, you proposed to consider the limitation of the opening angle for purge and vent valves as a design feature and to incorporate the change into the Final Safety Analysis Report (FSAR) with appropriate bases. We have reviewed your proposal and find that the design of the mechanical stops with lock nuts is such that the setting will not change. Therefore, we conclude that surveillance requirements would not serve a useful purpose.

In addition some of the valves are inaccessible during power operation or are located in high radiation areas and thus unnecessary entry is not consistent with ALARA guidelines. Since the mechanical stop is a design feature which is permanent, that is, not removed or altered for any reason during all modes of operation, based on our review of your proposal, we find that the surveillance Technical Specification for these valves are not necessary.

Sincerely, Original signed by RAHermann for/

Domenic B. Vassallo, Chief Operating Peactors Branch #2 Division of Licensing cc:

See next page

. DISTRIBUTION

[DocketFiler SNorris Gray File NRC POR'

~

MGrotenhuis SVarga

~

local PDR ELJordan VNoonan ORB #2 Reading JPartlow EReeves HThomnson 8 Grimes RWright OELD '

ACRS(10)

  • Please see previous concurrence pace.

(l @ b DL$j'h DL:0RB#2 DL:0RB#2 DL:0RB#1 DE:EQB SNoMs MGrotenhuis*

SVarga*

VNoonan DVhs lo 05/l-l/85 05/16/85 05/16/85 05/2o/85 05

/85 8506070061 850520 PDR ADOCK 05000324 P

PDR

c -_

Mr. E. E. Utley Carolina Power & Light Company Brunswick _ Steam Electric Plant; Units 1..and 2 cc:

Richard E. Jones, Esquire J. Nelson Grace Carolina Power & Light Company Regional Administrator 336 Fayetteville Street Region II Office Raleigh, Nnrth Carolina 27602 U. S. Nuclear Regulatory Commission 101 Marietta Street, Suite 3100 George F. Trowbridge, Esquire Atlanta, Georgia 30303 Shaw, Pittman, Potts and Trowbridge 1800 M Street, N. W.

Dayne H. Brown, Chief Washington, D. C.

20036 Radiation Protection Branch Division of Facility Services Mr. Charles R. Dietz Department of Human Resources Plant Manager Post Office Box 12200 Post Office Box 458 Raleigh, North Carolina 27605 Southport, North Carolina 28461 Mr. Franky Thomas, Chairman Board of Commissioners Post Office Box 249 Bolivia, North Carolina 28422 Mrs. Chrys Baggett State Clearinghouse Budget and Management 116 West Jones Street i

Raleigh, North Carolina 27603 Resident Inspector i

U. S. Nuclear Regulatory Commission Star Route 1 Post Office Box 208 Southport, North Carolina 28461 B

e i

I e

-