Proposed Tech Spec Table 2.2-1 Re Reactor Trip Instrumentation Trip Setpoints
ML20129A255
Person / Time
Site: Wolf Creek 
Issue date: 05/31/1985
From:
KANSAS GAS & ELECTRIC CO.
To:
Shared Package
ML19344B955 List:
References
TAC-57896, NUDOCS 8506040513
Download: ML20129A255 (4)


Text

- _ - _, _ _ _ -_ __ - _ - - - - -

i TABLE 2.2-1

-6 REACTOR TRIP SYSTEM INSTRUMENTATION TRIP SETPOINTS

~

t;;

(

n SENSOR S

TOTAL ERROR 5

FUNCTIONAL UNIT ALLOWANCE (TA)

Z (S)

TRIP SETPOINT-ALLOWABLE VALUE 1.

Manual' Reactor Trip N.A.

N.A.

N.A.

N.A.

N.A.

z Z

2.

Power Range, Neutron' Flux

~

s a.

High Setpoint 7.5 4.56 0~

$109% of RTP*

$112.3% of RTP*

b.

Low Setpoint 8.3 4.56 0

125% of RTP*

528.3% of RTP*

3.

Power Range, Neutron Flux.

2.4

. 0. 5 0

14% of RTP* with 56.3% of RTP* with H'gh Positive Rate

a. time constant a time constant 12 seconds 12 seconds 4.

Power Range, Neutron Flux, 2.4 0.5 0

54% of RTP* with 16.3% of RTP* with High Negative Rate a time constant a time constant y

12 seconds 12 seconds s

5.

Intermediate Range, 17.0 8.41 0

$25% of RTP*

$35.3% of RTP*

Neutron Flux n@

6.

Source Range, Neutron Flux 17.0 10.01 0

$105 cps

$1.6 x 105 cps 9

1. 2.
1. 55 + 0 9 o

7.

Overtemperature AT

--Mr-3.76 4-M See Note 1 See Note 2 e 0.G7-h*

o.a s zu 8.

Overpower AT 5.5 1.43

-G-ifr See Note 3 See Note 4 j

on 9.

Pressurizer Pressure-Low 3.7 0.71 2.49 11875 psig 11866 psig 10.

Pressurizer Pressure-High 7.5 0.71 2.49 12385 psig 12400 psig n

11.

Pressurizer Water Level-High 8.0 2.18 1.96 592% of instrument 593.9% of instrument span span

  • RTP = RATED THERMAL POWER
    • Loop design flow = 95,700 gpm h) b

TABLE 2.2-1 (Continued) s~

~

{

REACTOR TRIP SYSTEM INSTRUMENTATION TRIP SETPOINTS O

SENSOR R

TOTAL ERROR-7 FUNCTIONAL UNIT ALLOWANCE (TA)

Z_

(S)

TRIP SETPOINT ALLOWABLE VALUE c-12.

Reactor Coolant Flow-Low 3.1 27

>90% of loop

>89.1% of loop 5

4 '9 O8 3esign flow **

3esign flow **

H

13. Steam Generator Water 23.5 21.18 2.51

>23.5% of narrow

>22.3% of narrow Level Low-Low range instrument range instrument span g

span 14.

Undervoltage - Reactor 7.5 1.3 0

>10578 Volts A.C.

>10355 Volts A.C.

Coolant Pumps 15.

Underfrequency - Reactor 3.3 0

0

>57.2 Hz

>57.1 Hz Coolant Pumps 7

16.

Turbine Trip w

a.

Low Fluid Oil Pressure N.A.

N.A.

N.A.

>590.00 psig

>534.20 psig b.

Turbine Stop Valve N.A.

N.A.

N.A.

>1% open

>1% open-Closure 17.

Safety Injection Input N.A.

N.A.

N.A.

N.A.

N.A.

from ESF I

TABLE 2.2-1 (Continued) 8 TABLE NOTATIONS (Continued) n.

(

4 2

NOTE 1:

(Continued)

N 7

T' 5 588.5"F (Nominal T,yg at RATED THERMAL POWER);

E K

=

3 0.000671; I

Z f

P

=

Pressurizer pressure, psig;-

P'

=

2235 psig (Nominal RCS operating pressure);

'N.

S

=

Laplace transform operator, s.2; and f (AI) is a function of the indicated difference between top and bottom detectors of the i

i power-range neutron ion chambers;.with gains to be selected based on measured instrument-response during plant STARTUP tests such that:

7 (i) for q 9 between -35% and + 7%, f (AI) = 0, where q and q are percent t

b t

t b

C RATED THERMAL POWER in the top and bc ttom halves of the core respectively, and g

+g is g

b total THERMAL POWER in percent of RATED THERMAL POWER;.

1 j

(ii) for each percent that the magnitude of q 9 exceeds -35%, the AT Trip Setpoint t

b

)

shall be automatically reduced by 1.26% of its value at RATED THERMAL POWER; and l

(iii) for each percent that the magnitude of qt 9 exceeds.+7%, the AT Trip Setpoint b

shall be automatically reduced by 1.05% of its value at RATED THERMAL POWER.

I i

NOTE 2:

The channel's maximum Trip Setpoint shall not exceed its computed Trip Setpoint by more than.

I

-G-i# of AT span.

2.W.

I l

h b

)

k b

TABLE 2.2-1 (Continued)

c

(

TABLE NOTATIONS (Continued) 9 NOTE 3:

(Continued)

N 7

Ks 0.00128/*F for T > T" and Ks = 0 for T 5 T";

=

' E T

Average temperature, F;

=

f s

T" Indicated T,yg at RATED THERMAL POWER (Calibration temperature for AT

=

instrumentation, 5 588.5 F);

\\

Laplace transform operator, s 1; and S

=

f (al) 0 for all AI.

=

2 NOTE 4:

The channel's maximum Trip Setpoint shall not exceed its computed Trip Setpoint by more than

--4-Wr of AT span.