ML20129A231

From kanterella
Jump to navigation Jump to search
Rev 24 to AR-303, ESC Annunciator Response
ML20129A231
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 09/06/1996
From:
FLORIDA POWER CORP.
To:
References
AR-303, NUDOCS 9609180047
Download: ML20129A231 (92)


Text

_. _ _ _ . - _. ._. -

1 s 6. i e .a

' Document Transmittal #: 50716 Date: 9/12/96 l Tc: NRC (DC DESK) MAC: N/A  ;

Destination:

Description:

l Copy Copy Totals Document: Revision: Comment: # INFO CNTL MSTR )

AR0303 24 24 1 0 0 l

4 J

I i

4 l

l I

s 1

1 1

I i

l Instructions to the Addressee:

Pisase verify the document (s) received agrees with the above information. Be sure to destroy document (s) or portions of document (s) superseded by the above.

Tha signature indicates acknowledgment of receipt of the above document (s). Retum signed and dated

. trcnsmittal to Document Control within 20 days at mail code:

NA1C Florida Power Corporation Document Control, NA1C

}

Crystal River Energy Complex 15760 W. Power Line St.

/

Crystal River, FL 34428-6708 Signature of Addressee: Date:

Independent Verification: Date:

(Control Room documents only) 9609180047 960906 PDR ADOCK 05000302

~F PDR

Rev. 24 Effective Date /-

( m.rutnent Sect'P1 p c necanu vnu a li . _ , _ _

C. 9. J -

- - ~ ~ ~ " = -

A C_

ANNUNCIATOR RESPONSE AR-303 FLORIDA POWER CORPORATION

- CRYSTAL RIVER UNIT 3 ESC ANNUNCIATOR RESPONSE O

APPROVED BY: Interpretati n Cont t h k/w /j.b & ,( x k m f (SIjNATUREON' FILE)

{

DATE: ,

fo/76 INTERPRETATION CONTACT: Manager, Nuclear Operations Support j

, _ _ .__ . . ._ _ .. ._ _ ~_ _ _ . __

e ,

I

, TABLE OF CONTENTS SECTION EAE l 1.0 PURPOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  ;

2.0 REFERENCES

.......................... 1 2.1 INPLENENTING REFERENCES . . . . . . . . . . . . . . . 1 2.2 DEVELOPNENTAL REFERENCES .............. 1 3.0 PERSONNEL INDOCTRINATION ................... 2 4.0 INSTRUCTIONS ......................... 2 5.0 FOLLOW-UP ACTIONS . . . . . . . . . . . . ......... 2 ENCLOSURE 1 Annunciator Response .. .................. 3

- i l

l

)

I l

I l

i 1

1 1

1 l

l 1

i l

l l

l AR-303 Rev. 24 Page i 1

i j

a .

p 1.0 PURPOSE a

1.1 Establish a reference document for each Annunciator Window on the ESAB-A Lampbox.

1.2 Establish operator actions for valid Annunciator alarms on the ESAB-A Lampbox.

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the ESAB-A Lampbox.

~

2.0 REFERENCES

2.1 IMPLEMENTING REFERENCES 2.1.1 E0P, Emergency Operating Procedure 2.1.2 AP-330, Loss of Nuclear Services Water 2.1.3 AP-470, Loss of Instrument Air 2.1.4 AP-961, Earthquake 2.1.5 OP-700C,120/240 Volt AC Distribution Panels 2.1.6 OP-301, Operation of the Reactor Coolant System 2.1.7 OP-416, Domestic Water Supply System 2.1.8 SP-317, RC System Water Inventory Balance 2.2 DEVELOPMENTAL REFERENCES 2.2.1 INP0 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-048 2.2.3 MAR 88-05-25-05, FCN #19, SW Isolation to RC Pumps 4

2.2.4 MAR 92-09-08-01, Annunciator Window Relocation and Rewire 2.2.5 MAR 92-10-24-01, ES Status Light Color Change

'O

^R-303 - Rev. 24 Page 1

a .

3.0 PERSONNEL INDOCTRINATION .

3.1 The Annunciator System is powered from VBDP-5 Breaker 28.

4.0 INSTRUCTIONS 4.1 Respond to alarms on the ESAB-A Lampbox as indicated on Enclosure 1, Annunciator Response.

5.0 FOLLOW-UP ACTIONS None ,

O l

O AR-303 Rev. 24 Page 2

e s ENCLOSURE 1 (Page 1 of 87)

ESAB-A ANNUNCIATOR RES00NSE ESAB-A-01-01 C-01-01 RZ l I I I l l RC-1 I I HIGH PRESS BISTABLE TRIP l l l l l l l l l l EVENT POINT 0937 I I I I INDICATED CONDITION:

o RCS PRESSURE < 1500 PSIG ,

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: 1

}

o ES STATUS LIGHT RC-1 ' BISTABLE TRIPPED' IS LIT.

o ACTUATION CHANNEL CABINET #1 BISTABLE OUTPUT STATE LIGHT ' BRIGHT'.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO E0P.

1 DISCUSSION:

THIS ALARM INDICATES ONE CHANNEL TRIPPED IN A 2 OUT OF 3 HPI LOGIC.

REFERENCES:

DRAWING 208-028 SHEET ESA-24 I SENSING ELEMENT: BT-1 ES ACTUATION RELAY ,

AR-303 Rev. 24 Page 3

ENCLOSURE 1 (Page 2 of 87)

/~'N ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-02 C-01-02 V

RC-4 LOVV PRESS BISTABLE TRIP EVENT POINT 0940 INDICATED CONDITION:

o RCS PRESSURE <500 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

() o ES STATUS LIGHT RC-4 ' BISTABLE TRIPPED' IS LIT.

o ACTUATION CHANNEL CABINET #1 BISTABLE OUTPUT STATE LIGHT ' BRIGHT'.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO E0P 4

DISCUSSION:

THIS ALARM INDICATES ONE CHANNEL TRIPPED IN A 2 OUT OF 3 LPI LOGIC.

REFERENCES:

ORAWING 208-028 SHEET ESB-39 SENSING ELEMENT: BT-7 ES ACTUATION RELAY O

AR-303 Rev. 24 Page 4

ENCLOSURE 1 (Page 3 of 87)

O o

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-03 C-01-03 a

SW BP A/B TRIP l

EVENT POINT 1831 INDICATED CONDITION:

- 0 SWP-2A MOTOR NOT ENERGIZED WITH CONTROL SWITCW IN NORMAL AFTER START POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT WITH A RED FLAG ON CONTROL STATION.

o SWP-2B AUTO START.

O SW BP A/B FLOW LOW ALARM.

o CRDM COMPUTER HIGH TEMP ALARM (S).

OPERATOR ACTION FOR A VALID ALARM:

o ENSURE SWP-2B STARTS.

o INVESTIGATE CAUSE OF PUMP TRIP.

DISCUSSION:

1

REFERENCES:

DRAWING 208-056 SHEET SW-04 SENSING ELEMENT: SWP-2A CONTROL SWITCH CONTACTS CS/SC, CS/0 AR-303 Rev. 24 Page 5

~ '

ENCLOSURE 1 (Page 4 of 87)

( ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-03 C-01-03 SW BP A/B TRIP ,

4 EVENT POINT 1833 INDICATED CONDITION:

o SWP-2B MOTOR NOT ENERGIZED W.ITH CONTROL SWITCH IN NORMAL AFTER START POSITION.

i REDUNDANT INDICATION WHICH WILL VERIFY ALAJM:

o GREEN LIGHT WITH A RED FLAG ON CONTROL STATION.

O SWP-2A AUTO START.

O SW BP A/B FLOW LOW ALARM.

O CRDM HIGH TEMP COMPUTER ALARM (S).

OPERATOR ACTION FOR A VALID ALARM:

o ENSURE SWP-2A STARTS. ,

0 INVESTIGATE CAUSE OF PUMP TRIP.

DISCUSSION:

REFERENCES:

DRAWING 208-056 SHEET SW-05 SENSING ELEMENT: SWP-2B CONTROL SWITCH CONTACTS CS/SC, CS/0 AR-303 Rev. 24 Page 6 l

j

ENCLOSURE 1 (Page 5 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-04 C-01-04

(}

SW BP A/B FLOW LC)VV EVENT POINT 1830 INDICATED CONDITION:

o CRDM B00 STER PUMP FLOW <140 GPM FOR >5 SEC AS SENSED BY SW-91-FS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

[O~l o SW BP A/B TRIP ALARM.

o SW BP A/B AUTO START ALARM.

OPERATOR ACTION FOR A VALID ALARM:

o ENSURE STANDBY NUCLEAR SERVICES B0OSTER PUMP IS RUNNING.

O CHECK CRDM FILTER AP,IF HIGH PLACE STANDBY FILTER IN SERVICE.

O CHECK NUCLEAR SERVICES FLOWPATH.

DISCUSSION:

4 ALTERNATE NUCLEAR SERVICE B00 STER PUMP STARTS IF <140 GPM FOR >2 SEC.

1 IF TWO PUMPS ARE RUNNING AND ONE PUMP WILL PROVIDE SUFFICIENT FLOW, THEN ONE PUMP SHOULD BE SECURED.

REFERENCES:

DRAWING 208-056 SHEET SW-04

-~ SENSING ELEMENT: SW-91-FS h)

AR-303 Rev. 24 Page 7

ENCLOSURE 1 (Page 6 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-06 C-01-06 b(

-- SW BP A/B AUTO START EVENT POINT 1832 INDICATED CONDITION:

o SWP-2A MOTOR ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER STOP

, POSITION.

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT WITH A GREEN FLAG ON CONTROL STATION.

O SW BP A/B LOW FLOW ALARM.

OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE CAUSE OF B0OSTER PUMP AUTO START.

o INVESTIGATE CAUSE OF PUMP TRIP.

O CHECK FILTER AP.

DISCUSSION:

WITH A DECREASING FLOW THE ALTERNATE NUCLEAR SERVICES B0OSTER PUMP WILL START WHEN FLOW IS <140 GPM FOR >2 SEC.

REFERENCES:

DRAk'ING 208-056 SHEET SW-04

'O(_,/ SENSING ELEMENT: SWP-2A CONTROL SWITCH CONTACTS CS/SC, CS/0 i AR-303 Rev. 24 . Page 8 i

)

l ENCLOSURE 1 (Page 7 of 87)

() ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-06 C-01-06

-- SW BP AIB AUTO START EVENT POINT 1834 INDICATED CONDITION:

o SWP-2B MOTOR ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER STOP POSITION.

l

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT WITH A GREEN FLAG ON CONTROL STATION.

O SW BP A/B LOW FLOW ALARM.

OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE CAUSE OF B00 STER PUMP AUTO START.

o INVESTIGATE CAUSE OF PUMP TRIP.

o CHECK FILTER AP.

DISCUSSION:

WITH A DECREASING FLOW THE ALTERNATE NUCLEAR SERVICES B0OSTER PUMP WILL START WHEN FLOW IS <140 GPM FOR >2 SEC.

REFERENCES:

DRAWING 208-056 SHEET SW-05

')

\_, SENSING ELEMENT: SWP-2B CONTROL SWITCH CONTACTS CS/SC, CS/0 AR-303 Rev. 24 Page 9

1 ENCLOSURE 1 1 (Page 8 of 87)

ESAB-A-01-08 C-01-08

(]

v ESAB-A ANNUNCIATOR RESPONSE SW SURGE TANK LEVEL HIGH/ LOW EVENT POINT 1835 INDICATED CONDITION:

o SW SURGE TANK LEVEL >10'0" AS SENSED BY SW-137-LS.

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH NITROGEN PRESSURE ALARM.

o RML-3 RADIATION ALARM.

O SWV-277 OPEN INDICATION. /

o COMPUTER POINT, X333.

OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH LEVEL ALARM.

O REFER TO OP-301 IF RCS LEAK.

DISCUSSION:

AN INCREASING SW SURGE TANK LEVEL MAY INDICATE LEAKAGE FROM ANY OF THE LETDOWN COOLERS OR RCP SEAL PACKAGE COOLERS. ADDITIONALLY, A RISE IN SW SYSTEM TEMPERATURE AS A RESULT OF A LOCA OR COMPONENT FAILURE COULD RAISE TANK LEVEL.

REFERENCES:

DRAWING 208-056 SHEET SW-31 SENSING ELEMENT: SW-137-LS AR-303 Rev. 24 Page 10

ENCLOSURE 1

- (Page 9 of 87) i ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-08 C-01-08

(~'/

w SW SURGE TANK LEVEL HIGH/ LOW EVENT POINT 1836 INDICATED CONDITION:

o SW SURGE TANK LEVEL <8'6" AS SENSED BY SW-137-LS.

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

4 o LOW NITROGEN PRESSURE ALARM.

, o SW SYSTEM PRESSURE LOW ALARM.

O COMPUTER POINT, X333.  !

I OPERATOR ACTION FOR A VALID ALARM:

o FILL SW SURGE TANK AS NECESSARY.

o INVESTIGATE CAUSE OF LOW TANK LEVEL.

O REFER TO AP-330.

o IE A 4# RBIC ACTUATION HAS OCCURRED AND IS BYPASSED, 4 IBEN CLOSE THE SW ISOLATION VALVES TO THE RCP'S, SWV-79 THROUGH SWV-86.

1 DISCUSSION:

A DECREASING SW SURGE TANK LEVEL MAY INDICATE POSSIBLE LEAKAGE FROM SYSTEM RELIEF VALVES. IF RUNNING MORE THAN 1 SW PUMP THEN SYSTEM PRESSURE MAY BE HIGH CAUSING THIS LEAKAGE.

REFERENCES:

DRAWING 208-056 SHEET SW-31

() SENSING ELEMENT: SW-137-LS AR-303 Rev. 24 Page 11

ENCLOSURE 1 (Page 10 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-09 C-01-09 SW SURGE TANK PRESS HIGH/ LOW EVENT POINT 1837 4

INDICATED CONDITION

o SW SURGE TANK PRESSURE >90 PSI,G AS SENSED BY SW-134-PSI.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH INDICATED TANK PRESSURE.

o HIGH SW SURGE TANK LEVEL.

OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH PRESSURE.

o CHECK NITR0 GEN SUPPLY ISOLATION VALVE CLOSED.

o IF PRESSURE ALARM CAUSED BY HIGH LEVEL, RESTORE LEVEL TO NORMAL BAND.

DISCUSSION:

THIS ALARM COULD BE CAUSED BY RISING TANK LEVEL DUE TO IN LEAKAGE FROM A LETDOWN COOLER OR RCP SEAL PACKAGE COOLER, OR A RISE IN SW SYSTEM ,

TEMPERATURE DUE TO A LOCA OR COMPONENT FAILURE.

IF NECESSARY TO REDUCE TANK PRESSURE A MANUAL VENT VALVE (SWV-198) IS AVAILABLE TO VENT THE EXCESS PRESSURE TO THE AB VENTILATION SYSTEM.

REFERENCES:

DRAWING 208-056 SHEET SW-31 r~ SENSING ELEMENT: SW-134-PSI L)

AR-303 Rev. 24 Page 12

s' 5 ENCLOSURE 1 (Page 11 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-09 C-01-09 l

SW SURGE TANK PRESS HIGH/ LOW EVENT POINT 1838 INDICATED CONDITION:

o SW SURGE TANK PRESSURE <77 PSIG AS SENSED BY SW-134-PS. ,

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOW INDICATED TANK PRESSURE.

o LOW SW SURGE TANK LEVEL.

O SW SYSTEM PRESS LOW.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-330.

O CHECK FOR TANK GAS SPACE LEAKS.

o CHECK TANK PRESSURE CONTROL BYPASS VALVE (SWV-198) CLOSED.

O CHECK TANK PRESSURE CONTROL VALVE, ISOLATION VALVE (SWV-282) IS CLOSED.

o IF PRESSURE ALARM CAUSED BY LOW LEVEL, RESTORE LEVEL TO NORMAL BAND.

o IF LEVEL IS SATISFACTORILY, ADD N2 DISCUSSION:

REFERENCES:

DRAWING 208-056 SHEET SW-31 SENSING ELEMENT: SW-134-PS2 AR-303 Rev. 24 Page 13

. i ENCLOSURE 1 (Page 12 of 87) l ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-11 C-01-ll (J)

l l

l l RB FAN A/B/C I l CLG WTR FLOW I I LOW l l I I

- . EVENT POINT 1843 l

I I l I l INDICATED CONDITION:

o SW OR CI FLOW FROM AIR HANDLING UNIT 1A <400 GPM AS SENSED BY SW-47-FS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR BUILDING SW SYSTEM LEAK ALARM.

(~')

\- - O COMPUTER POINT S348.

o SW OUTLET VALVE (SWV-41) CLOSED INDICATION.

OPERATOR ACTION FOR A VALID ALARM:

o IF ADDITIONAL COOLING WATER FLOW IS REQUIRED, START SWP-1A OR SWP-1B

~

AND ENSURE THE FAN IS ALIGNED TO SW. .

o.IF SW LEAKAGE IS INDICATED, ISOLATE COOLING WATER TO AHF-1A.

l DISCUSSION: l THIS ALARM IS AN EXPECTED ALARM AFTER AIR HANDLING UNIT TRIPS OFF. (TIME .

DELAY OF =60 SECONDS CLOSES SWV-41.)

THIS ALARM WILL NOT COME IN, OR WILL CLEAR, IF CONTROL SWITCH IS SELECTED TO 0FF.

4

REFERENCES:

DRAWING 208-056 SHEET SW-31 IT

(_ ,/ SENSING ELEMENT: SW-47-FS i

AR-303 Rev. 24 Page 14

1 ENCLOSURE 1 (Page 13 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-11 C-01-ll l l l l l l l l RB FAN A/B/C l l CLG WTR FLOW I I LOW I I I I EVENT POINT 1844 I I I I INDICATED CONDITION:

o SW OR CI FLOW FROM AIR HANDLING UNIT 1B <400 GPM AS SENSED BY SW-51-FS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

CT o REACTOR BUILDING SW SYSTEM LEAK ALARM.

b/ o COMPUTER POINT S376.

o SW OUTLET VALVE (SWV-43) CLOSED INDICATION.

OPERATOR ACTION FOR A VALID ALARM:

o IF ADDITIONAL COOLING WATER FLOW IS REQUIRED, START SWP-1A OR SWP-1B AND ENSURE THE FAN IS ALIGNED TO SW.

o IF SW LEAKAGE IS INDICATED, ISOLATE COOLING WATER TO AHF-18.

DISCUSSION:

THIS ALARM IS AN EXPECTED ALARM AFTER AIR HANDLING UNIT TRIPS OFF. (TIME DELAY OF =60 SECONDS CLOSES SWV-43.)

THIS ALARM WILL NOT COME IN, OR WILL CLEAR, IF CONTROL SWITCH IS SELECTED TO OFF.

REFERENCES:

DRAWING 208-056 SHEET SW-31 SENSING ELEMENT: SW-51-FS AR-303 Rev. 24 Page 15

ENCLOSURE 1 (Page 14 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-ll C-01-11 l

l l

l l l RB FAN A/B/C l CLG WTR FLOW )

I LOW l

l EVENT POINT 1845 I

I INDICATED CONDITION: .

o SW OR CI FLOW FROM AIR HANDLING UNIT IC <400 GPM AS SENSED BY SW-55-FS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR BUILDING SW SYSTEM LEAK ALARM.

O)

( o COMPUTER POINT S387.

o SW OUTLET VALVE (SWV-45) CLOSED INDICATION.

OPERATOR ACTION FOR A VALID ALARM:

o IF ADDITIONAL COOLING WATER FLOW IS REQUIRED, START SWP-1A OR SWP-1B AND ENSURE THE FAN IS ALIGNED TO SW.

o IF SW LEAKAGE IS INDICATED, ISOLATE COOLING WATER TO AHF-lC.

DISCUSSION:

THIS ALARM IS AN EXPECTED ALARM AFTER AIR HANDLING UNIT TRIPS OFF. (TIME DELAY OF =60 SECONDS CLOSES SWV-45.)

THIS ALARM WILL NOT COME IN, OR WILL CLEAR, IF CONTROL SWITCH IS SELECTED TO 0FF.

REFERENCES:

DRAWING 208-056 SHEET SW-31 SENSING ELEMENT: SW-55-FS AR-303 Rev. 24 Page 16

- ENCLOSURE 1 (Page 15 of 87)

ESAB-A-01-12 C-01-12

(~')

%j ESAB-A ANNUNCIATOR RESPONSE l l l l l l l l l l REACTOR BLDG I I SW SYSTEM LEAK l l I I l l EVENT POINT 1840

~

I l INDICATED CONDITION:

o DIFF FLOW TO AIR HANDLING UNIT 1A >90 GPM AS SENSED BY SW-46-FS.

,- s REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RB FAN A/B/C CLG WTR FLOW LOW ALARM.

o DECREASING LEVEL IN SW SURGE TANK.

O HIGH TEMP ALARM ON AFFECTED COMP 0NENT.

1 OPERATOR ACTION FOR A VALID ALARM:

o REFER'TO AP-330.

o ISOLATE THE AFFECTED COMP 0NENT, AND PLACE BACKUP IN SERVICE IF REQUIRED.

O FILL SW SURGE TANK AS NECESSARY.

DISCUSSION:

REFERENCES:

DRAWING 208-056 SHEET SW-31

() SENSING ELEMENT: SW-46-FS AR-303 Rev. 24 Page 17

ENCLOSURE 1 (Page 16 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-12 C-01-12 l l l l I I I I l l REACTOR BLDG 1 1 SW SYSTEM I I LEAK I I l l

_ EVENT POINT 1841 l l

~

INDICATED CONDITION:

O DIFF FLOW TO AIR HANDLING UNIT 18 >90 GPM AS SENSED BY SW-50-FS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

/

V o RB FAN A/B/C CLG WTR FLOW LOW ALARM.

O DECREASING LEVEL IN SW SURGE TANK.

o HIGH TEMP ALARM ON AFFECTED COMPONENT. l 1

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-330.

o ISOLATE THE AFFECTED COMPONENT, AND PLACE BACKUP IN SERVICE IF REQUIRED.

O FILL SW SURGE TANK AS NECESSARY.

l DISCUSSION: )

I l

l

REFERENCES:

DRAWING 208-056 SHEET SW-31

_( SENSING ELEMENT: SW-50-FS AR-303 Rev. 24 Page 18 1

r ENCLOSURE 1 (Page 17 of u7)

G ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-12 C-01-12 C/

I I I I I I l l REACTOR BLDG l l SW SYSTEM I I LEAK I I I I

- l l

- EVENT POINT 1842

'l l INDICATED CONDITION:

o DIFF FLOW TO AIR HANDLING UNIT 10 >90 GPM AS SENSED BY SW-54-FS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

(  %

o RB FAN A/8/C CLG WTR FLOW LOW ALARM.

't o DECREASING LEVEL IN SW SURGE TANK.

O HIGH TEMP ALARM ON AFFECTED COMPONENT.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-330.

o ISOLATE THE AFFECTED COMP 0NENT, AND PLACE BACKUP IN SERVICE IF REQUIRED.

o FILL SW SURGE TANK AS NECESSARY.

DISCUSSION:

REFERENCES:

DRAWING 208-056 SHEET SW-31 m SENSING ELEMENT: SW-54-FS h

AR-303 Rev. 24 Page 19

a p ENCLOSURE 1 (Page 18 of 87)

<O ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-12 C-01-12 V

I I i l i I I

I I l l REACTOR BLDG I I SW SYSTEM I I l l EVENT POINT 1846 l I INDICATED CONDITION:

o DIFF FLOW TO LD COOLER A AND C >50 GPM AS SENSED BY SW-42-FS.

O

, L,]

REDUNDANT INDICATION WHICH WILL VERIFY TLARM:

o DECREASING LEVEL IN SW SURGE TANK.

O HIGH TEMP ALARM ON AFFECTED COMPONENT.

l OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-330.

o ISOLATE THE AFFECTED COMP 0NENT, AND PLACE BACKUP IN SERVICE IF REQUIRED.

O FILL SW SURGE TANK AS NECESSARY.

DISCUSSION:

REFERENCES:

DRAWING 208-056 SHEET SW-31 O

SENSING ELEMENT: SW-42-FS

()

AR-303 Rev. 24 Page 20

. . l ENCLOSURE 1  :

(Page 19 of 87)

Ci V

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-12 C-01-12 1 l

l l l

l l REACTOR BLDG  ;

I SW SYSTEM LEAK l '

l l l EVENT POINT 1847 l l l

l INDICATED CONDITION:

o DIFF FLOW TO LD COOLER B >50 GPM AS SENSED BY S,W-43-FS.

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DECREASING LEVEL IN SW SURGE TANK.

o HIGH TEMP ALARM ON AFFECTED COMPONENT.  !

l OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-330. l 0 ISOLATE THE AFFECTED COMPONENT, AND PLACE BACKUP IN SERVICE IF REQUIRED.  !

O FILL SW SURGE TANK AS NECESSARY.

}

DISCUSSION:

f 1

REFERENCES:

DRAWING 208-056 SHEET SW-31 SENSING ELEMENT: SW-43-FS AR-303 Rev. 24 Page 21

ENCLOSURE 1 (Page 20 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-12 C-01-12 l l l 1 I I I I l l REACTOR BLDG I I SW SYSTEM

. l l i l i I I Z EVENT POINT 1848-l l 3

INDICATED CONDITION:

o DIFF FLOW TO CRDM'S >10 GPM AS SENSED BY SW-90-FS. ,

i

,q

, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DECREASING LEVEL IN SW SURGE TANK.

o INCREASING TEMPS ON CRDM'S.

o COMPUTER GROUP 15 OR POINTS X-211 TO X-279.

t OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-330.

o FILL SW SURGE TANK AS NECESSARY.

4 DISCUSSION:

REFERENCES:

DRAWING 208-056 SHEET SW-31 SENSING ELEMENT: SW-90-FS AR-303 Rev. 24 Page 22

_ .- - - ~_ .

ENCLOSURE 1 (Page 21 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-12 C-01-12 lv I l l l l l l l l l REACTOR BLDG I I SW SYSTEM LEAK l l I I l l 1

) Z EVENT POINT 1849 I I INDICATED CONDITION:

o DIFF FLOW TO RCP-1A >20 GPM AS SENSED BY SW-107-FS.

e

, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

I o DECREASING LEVEL IN SW SURGE TANK.

O INCREASING TEMPS ON RCP A.

O COMPUTER GROUP 78.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-330.

O FILL SW SURGE TANK AS NECESSARY.

'I DISCUSSION:

REFERENCES:

DRAWING 208-056 SHEET SW-31 SENSING ELEMENT: SW-107-FS AR-303 Rev. 24 . Page 23

~ '

. ENCLOSURE 1  ;

(Page 22 of 87) f ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-12 C-01-12 ll l l l 1 I J l l l l REACTOR BLDG I I SW SYSTEM LEAK j

l l I I l l Z EVENT POINT 1850 l I e INDICATED CONDITION: J o DIFF FLOW TO RCP-1B >20 GPM AS SENSED BY SW-113-FS.

't

- REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

(d o DECREASING LEVEL IN SW SURGE TANK.

O INCREASING TEMPS ON RCP B.

o COMPUTER GROUP 79.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-330.

O FILL SW SURGE TANK AS NECESSARY.  !

.l DISCUSSION:

REFERENCES:

DRAWING 208-056 SHEET SW-31

\ SENSING ELEMENT: SW-113-FS AR-303 Rev. 24 Page 24

ENCLOSURE 1 (Page 23 of G7)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-12 C-01-12 l

l l

l l REACTOR BLDG I SW SYSTEM LEAK l

i I l Z EVENT POINT 1851 1 I INDICATED CONDITION:

o DIFF FLOW TO RCP-1C >20 GPM AS SENSED BY SW-95-FS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

b o DECREASING LEVEL IN SW SURGE TANK. l 0 INCREASING TEMPS ON RCP C. l 0 COMPUTER GROUP 80.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-330.

O FILL SW SURGE TANK AS NECESSARY.

l DISCUSSION:

1

REFERENCES:

DRAWING 208-056 SHEET SW-31 i SENSING ELEMENT: SW-95-FS AR-303 Rev. 24 Page 25

ENCLOSURE 1 (Page 24 of 87) J A ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-12 C-01-12 l

l l l

l \

l REACTOR BLDG I SW SYSTEM i LEAK l

I l

EVENT POINT 1852 I

INDICATED CONDITION:

o DIFF FLOW TO RCP-ID >20 GPM AS SENSED BY SW-101-FS.

1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DECREASING LEVEL IN SW SURGE TANK.

O INCREASING TEMPS ON RCP D.

O COMPUTER GROUP 81.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-330.

O FILL SW SURGE TANK AS NECESSARY.

1 DISCUSSION:

REFERENCES:

DRAWING 208-056 SHEET SW-31 SENSING ELEMENT: SW-101-FS AR-303 Rev. 24 Page 26

ENCLOSURE 1 1 (Page 25 of 87) l ESAB-A ANNUNCIATOR RESPONSE ESAB-A-01-14 C-01-14 l

1 l

\

l ES CAB l FAN ,

FAILURE l

I I l I

l EVENT POINT 1232 INDICATED CONDITION:

o LOW CABINET AIR FLOW AS SENSED BY INDIVIDUAL CABINET FAN FLOW SWITCH.

I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o ' FAN RUNNING' LIGHT EXTINGUISHED l

,/

OPERATOR ACTION FOR A VALID ALARM:

o VERIFY COOLING FAN IN OPERATION.

DISCUSSION:

I&C SHOP PERIODICALLY REPLACES THE DOOR FILTERS PER SCMEDULED PM'S. IF THE ALARM BECOMES A NUISANCE BECAUSE OF DIRTY FILTERS, GENERATE A WORK REQUEST TO REPLACE THE FILTERS. SOMETIMES A LIGHT VACUUMING WILL HELP UNTIL REPLACEMENT.

REFERENCES:

. DRAWING 208-028 SHEET ESAB-5 SENSING ELEMENT: FSBFX (ES ACTUATION CABINET INDIVIDUAL FAN FLOW SWITCH)

AR-303 Rev. 24 Page 27

( e .

ENCLOSURE 1 (Page 26 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-01 C-02-01 i

l RC-2

< HIGH PRESS BISTABLE TRIP l l

EVENT POINT 0938  ;

i INDICATED CONDITION:

o RCS PRESSURE <1500 PSIG

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ES STATUS LIGHT RC-2 ' BISTABLE TRIPPED' IS LIT.

O ACTUATION CHANNEL CABINET #2 BISTABLE OUTPUT STATE LIGHT ' BRIGHT'.

OPERATOR ACTION FOR A VALID ALARM:

l o REFER TO E0P l

i l

DISCUSSION:

THIS ALARM INDICATES ONE CHANNEL TRIPPED IN A 2 OUT OF 3 HPI LOGIC.

REFERENCES:

DRAWING 208-028 SHEET ESA-24 SENSING ELEMENT: BT-2 ES ACTUATION RELAY AR-303 Rev. 24 Page 28

8 e ENCLOSURE 1 (Page 27 of 87)

ESAB-A-02-02 C-02-02 fv^) ESAB-A ANNUNCIATOR RESPONSE RC-5 LOW PRESS BISTABLE TRIP EVENT POINT 0925 INDICATED CONDITION:

o RCS PRESSURE <500 PSIG ,

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ES STATUS LIGHT RC-5 ' BISTABLE TRIPPED' IS LIT.

o ACTUATION CHANNEL CABINET #2 BISTABLE OUTPUT STATE LIGHT ' BRIGHT'.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO E0P DISCUSSION:

THIS ALARM INDICATES ONE CHANNEL TRIPPED IN A 2 OUT OF 3 LPI LOGIC.

REFERENCES:

DRAWING 208-028 SHEET ESB-39

() SENSING ELEMENT: BT-8 ES ALTUATION RELAY AR-303 Rev. 24 Page 29

ENCLOSURE 1 (Page 28 of 87) l ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-03 C-02-03

~

SW PUMP C TRIP EVENT POINT 1821  ;

)

i INDICATED CONDITION:

o SWP-1C BREAKER OPEN WITH CONTROL SWITCH IN NORMAL AFTER START POSIT:0N.  !

REDUNDANT INDICATION WHICH'WILL VERIFY ALARM: ,

i o GREEN LIGHT WITH A RED FLAG ON CONTROL STATION.

O SWP-1B AUTO START ALARM.

o SW SYSTEM PRESS LOW ALARM.

OPERATOR ACTION FOR A VALID ALARM:

o ENSURE EMERGENCY NUCLEAR SERVICES PUMP SWP-1B OR SWP-1A AUTO START.

o INVESTIGATE CAUSE OF PUMP TRIP.

DISCUSSION:

$WP-1B STARTS 2 SEC AFTER PRESS DECREASES TO <110 PSIG. IF SWP-1B FAILS TO START, OR IS TAGGED OUT, SWP-1A WILL START 10 SEC AFTER PRESS DECREASES TO <110 PSIG. NO AUTO START ALARM I-S CURRENTLY INSTALLED FOR SWP-1A.

THIS IS AN EXPECTED ALARM FROM AN ES ACTUATION.

REFERENCES:

DRAWING 208-056 SHEET SW-01 SWP-lC CONTROL SWITCH CONTACTS CS/SC, CS/0 JENSINGELEMENT:

AD-303 Rev. 24 Page 30

l ENCLOSURE 1 (Page 29 of 87) l I

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-04 C-02-04 1

SWPC l

MOTOR l OVERLOAD l EVENT POINT 1822 INDICATED CONDITION:

o SWP-1C MOTOR AMPS >115% RATED LOAD.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH MOTOR AMPS.

O SWP-1C TRIP.

o GREEN LIGHT ON WITH A RED FLAG ON SWP-1C CONTROL STATION.

O SW SYSTEM PRESS LOW SW-2-PI. i l

l OPERATOR ACTION FOR A VALID ALARM:

i o START SWP-1A OR SWP-1B, SECURE SWP-1C, INVESTIGATE CAUSE OF OVERLOAD. l l

DISCUSSION-THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANE0US OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANE0US OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP. ,

l

REFERENCES:

DRAWING 208-056 SHEET SW-01 SENSING ELEMENT: 51 RELAY (INSIDE 4160V BREAKER CUBICLE) i I

AR-303 Rev. 24 Page 31  ;

l

\

ENCLOSURE 1 (Page 30 of 87)

() ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-05 C-02-05 Z Z SW SYSTEM PRESS LC)VV EVENT POINT 1823 INDICATED CONDITION:

o SW SYSTEM HEADER PRESSURE <110 PSIG AS SENSED BY SW-151-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

g-~)

# o SWP TRIP ALARM ON RUNNING SW PUMP.

o HIGH MOTOR AMPS ON RUNNING SW PUMP.

O SW SURGE TANK PRESS LOW.

OPERATOR ACTION FOR A VALID ALARM:

0 ENSURE SWP-1B OR SWP-1A HAS STARTED.

o MONITOR SW SURGE TANK LEVEL FOR ADEQUATE INVENTORY.

O CHECK SW SYSTEM FOR LEAKS.

O CHECK FOR PROPER VALVE ALIGNMENT FOR RUNNING SW PUMP.

O CHECK FOR BACKFLOW PAST CHECK VALVE ON IDLE SW PUMPS.

DISCUSSION:

REFERENCES:

DRAWING 208-056 SHEET SW-03

/7 SW-151-PS

( ,/ SENSING ELEMENT:

AR-303 Rev. 24 . Page 32

1

. , i ENCLOSURE 1 (Page 31 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-06 C-02-06

}

SW SYSTEM l

_ _ TEMP HIGH l

l EVENT POINT 1839 INDICATED CONDITION:

o SW PUMP SUCTION TEMP >105'F AS SENSED BY SW-5-TS.

~s REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

\d o SCREEN WASH TROUBLE.

o RW PUMP TRIP, OR ABNORMAL CURRENT.

O SW PUMP TRIP, OR ABNORMAL CURRENT OPERATOR ACTION FOR A VALID ALARM:

O REFER TO AP-330.

O PLACE ALL SW HEAT EXCHANGERS IN SERVICE IF REQUIRED.

O CHECK INTAKE SCREENS AND RWP'S TO ENSURE RAW WATER FLOW TO HEAT EXCHANGERS.

O MINIMIZE HEAT LOADS ON SW SYSTEM.

o CHECK SW HEAT EXCHANGERS DIFFERENTIAL TEMPERATURES FOR INDICATIONS OF FOULING.

o CHECK FOR PROPER VALVE ALIGNMENT FOR RUNNING SW PUMP AND SW HEAT EXCHANGERS.

o CHECK FOR BACKFLOW PAST CHECK VALVE ON IDLE SW PUMPS.

DISCUSSION:

DRAWING 208-056 SHEET SW-31

REFERENCES:

SENSING ELEMENT: SW-5-TS 4 f~'T s_ / l A!!-303 Rev. 24 Page 33

ENCLOSURE 1 (Page 32 of 87)

[ ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-08 C-02-08 BWST LEVEL HIGH/ LOW EVENT POINT 0157 INDICATED CONDITION:

l o BWST LEVEL <45.5' AS SENSED BY DH-11-LS .

f~

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DH-7-LI o DH-37-LI '

o DH-7-LIR o COMPUTER POINT X335 OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE CAUSE OF DECREASING LEVEL.

DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

=

REFERENCES:

DRAWING 208-021 SHEET DH-22 Cs SENSING ELEMENT: DH-11-LS AR-303 Rev. 24 Page 34

S 4

ENCLOSURE 1 (Page 33 of 87)

O V

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-08 C-02-08 swsT LEVEL HIGH/ LOW EVENT POINT 0233 INDICATED CONDITION:

I l o BWST LEVEL >46.5' AS SENSED BY DH-11-LS.

A

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l o DH-7-LI o DH-37-LI o DH-7-LIR o COMPUTER POINT X335 OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE CAUSE OF INCREASING LEVEL.

I DISCUSSION:

REFERENCES:

DRAWING 208-021 SHEET DH-22 SENSING ELEMENT: DH-ll-LS AR-303 Rev. 24 Page 35

. . 1 ENCLOSURE 1 (Page 34 of 87)

(}

V ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-08 C-02-08 swsT LEVEL HIGH/ LOW EVENT POINT 0234 INDICATED CONDITION:

o BWST LEVEL <15' AS SENSED BY DH-7-LSI.

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DH-7-LI o DH-37-LI o DH-7-LIR o COMPUTER POINT X335 OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE CAUSE OF DECREASING LEVEL.

o BEGIN SWAP OVER TO RB SUMP IF A VALID ES ACTUATION HAS OCCURRED.

REFER TO DIRECTING EMERGENCY OPERATING PROCEDURE.

DISCUSSION:

o REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

o SWAP OVER TO RB SUMP FOR LONG TERM RECIRCULATION MODE IS REQUIRED TO BE COMPLETE BEFORE BWST REACHES 7' INDICATED LEVEL TO PREVENT EQUIPMENT DAMAGE. ,

REFERENCES:

DRAWING 208-021 SHEET DH-24 ,

SENSING ELEMENT: DH-7-LS1 AR-303 Rev. 24 Page 36

ENCLOSURE 1 (Page 35 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-08 C-02-08 BWST l LEVEL l HIGH/ LOW EVENT POINT 0235 1

INDICATED CONDITION:

o BWST LEVEL <7' AS SENSED BY DH-7-LSI. -

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DH-7-LI

o DH-37-LI o DH-7-LIR o COMPUTER POINT X335 OPERATOR ACTION FOR A VALID ALARM

o INVESTIGATE CAUSE OF DECREASING LEVEL.

O ENSURE SWAP OVER TO RB SUMP IS COMPLETED AS S00N AS POSSIBLE DURING VALID ES ACTUATION S0 AS TO PRECLUDE DAMAGE TO ECCS EQUIPMENT.

DISCUSSION:

o REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

o UNDER FULL FLOW ECCS CONDITIONS VORTEXING COULD OCCUR IN THE BWST AT INDICATED LEVEL OF < 7' (5' PLUS INSTRUMENT ERROR)

REFERENCES:

DRAWING 208-021 SHEET DH-24 SENSING ELEMENT: DH-7-LS1 O

AR-303 Rev. 24 Page 37

ENCL 0SURE 1 (Page 36 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-09 C-02-09

(

'l BWST TEMP Z Z HIGH/ LOW

f. VENT POINT 0236 INDICATED CONDITION:

l o BWST TEMPERATURE x110*F AS SENSED BY DH-9-TTS.

'A

'() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DH-10-TI o DH-9-TI o COMPUTER POINT X336 OPERATOR ACTION FOR A VALID ALARM: ,

o INVESTIGATE CAUSE OF INCREASING TEMPERATURE.

O ENSURE BWST HEATER (S) NOT IN OPERATION.

DISCUSSION:

REFERENCES:

DRAWING 208-02I SHEET DH-22 SENSING ELEMENT: DH-9-TTS AR-303 Rev. 24 Page 38

. . l ENCLOSURE 1 l (Page 37 of 87) l ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-09 C-02-09 l

BWST TEMP HIGH/ LOW EVENT POINT 0237 l I!

INDICATED CONDITION:

I o BWST TEMPERATURE < 60*F AS SENSED BY DH-10-TTS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DH-10-TI o DH-9-TI o COMPUTER POINT X336 OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE CAUSE OF DECREASING TEMPERATURE. 1 o ENSURE BWST HEATER (S) IN OPERATION.

l DISCUSSION:

REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS. ,

REFERENCES:

DRAWING 208-021 SHEET DH-22 SENSING ELEMENT: DH-10-TTS AR-303 Rev. 24 Page 39 i

l ENCLOSURE 1 (Page 38 of 87)

O v

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-11 C-02-11 I I -

1 I l

I I l l REACTOR BLDG I I FLOOD LEVEL I I HIGH I I I I l

EVENT POINT 1510 l l I l I l l

INDICATED CONDITION:

o REACTOR BUILDING WATER LEVEL >3'6" ABOVE RB FLOOR (>98'6" elevation)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH RB WATER LEVEL AS INDICATED ON WD-303-LI AND WD-304-LI.

o HIGH SUMP WATER LEVEL ON WD-222-LI.

o HIGH SUMP WATER LEVEL ON BS-93-PIR.

OPERATOR ACTION FOR A VALID ALARM: I o REFER TO E0P-07 OR E0P-08 TO SWAP DHP/BSP SUCTION TO RB SUMP DURING A l L.0.C.A.

DISCUSSION:

ALARM SETPOINT IS BASED ON WATER LEVEL IN REACTOR BUILDING FOR DHP AND BSP NPSH TO PERMIT SWAP OVER TO SUMP DURING A L.0.C.A. PER E.0.P.S.

SWAP OVER TO SUMP SHOULD BE BASED ON BWST WATER LEVEL AND NOT SUMP LEVEL.

REFERENCES:

DRAWING 208-060 SHEET WD-137 SENSING ELEMENT: WD-303-LY,WD-304-LY LEVEL TRANSMITTERS O

AR-303 Rev. 24 Page 40

. ENCLOSURE 1 (Page 39 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-l2 C-02-12 l l 1 I I I I I l l REACTOR BLDG I I SUMP LEVEL HIGH l l I I I I EVENT POINT 1509 I I INDICATED CONDITION:

o REACTOR BUILDING SUMP LEVEL >4' AB0VE SUMP BOTTOM (>88'6" elevation).

n REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

\') o HIGH SUMP WATER LEVEL ON WD-222-LI.

o HIGH SUMP WATER LEVEL ON BS-93-PIR.

OPERATOR ACTION FOR A VALID ALARM:

o CHECK FOR INDICATIONS OF RCS LEAKAGE.

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE.

o REFER TO E0P.

DISCUSSION:

LEAKAGE INTO SUMP MAY BE FROM ONE OR MORE OF THE FOLLOWING: REACTOR COOLANT SYSTEM, SECONDARY SYSTEM, RC PUMP OIL, DEMIN WATER, SW LEAKS, COOLING WATER -

LINES CONDENSING HUMID AIR, REFUELING CANAL DRAINS.

I REFER TO SP-317 AND OP-301 TO DETERMINE IF RCS WATER IS BEING LOST TO THE RB SUMP.

ENSURE ANY RECENT CHANGES TO SYSTEM LINEUPS THAT MAY HAVE CAUSED THIS HIGH LEVEL CONDITION ARE INVESTIGATED.  ;

1

REFERENCES:

DRAWING 208-060 SHEET WD-137 l SENSING ELEMENT: WD-301-LY,WD-302-LY LEVEL TRANSMITTERS AR-303 Rev. 24 Page 41 l

ENCLOSURE 1 (Page 40 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-13 C-02-13

. l l l l l l l I I I REACTOR BLDG I I SUMP PUMP TROUBLE l l I I l l l l EVENT POINT 1585 INDICATED CONDITION:

o RB SUMP PUMP A OR B AUTO START AT 12". (IF SELECTED TO ' LEAD')

o RB SUMP PUMP A OR B TRIP.

o RB SUMP LEVEL >18".

m o WASTE DISPOSAL PANEL FAN FAILURE.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RBS PUMP C/S GREEN LIGHT ON AND SWITCH IN NORM AFTER START.

O HIGH SUMP LEVEL ON WD-222-LI.

O HIGH SUMP WATER LEVEL ON BS-93-PIR.

OPERATOR ACTION FOR A VALID ALARM:

o IF PUMP AUTO START, OBSERVE LEVEL DECREASE.

o IF PUMP TRIP, INVESTIGATE REASON FOR PUMP TRIP.

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE FAN FAILURE AT WASTE.

DISPOSAL PANEL, AND SELECT ALTERNATE FAN IF REQUIRED.

DISCUSSION:

THIS ALARM SHOULD CLEAR WHEN AUTO PUMP SHUTDOWN OCCURS AT 2".

REFERENCES:

DRAWING 208-060 SHEET WD-07, WD-134, WD-148 SENSING ELEMENT: WD-222-LS O

AR-303 Rev. 24 Page 42

e e ENCLOSURE 1 (Page 41 of 87) l ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 J

l I I I I I l l l l SW ISO VALVE I I AIR FAILURE l l I l l l I I

, l l EVENT POINT 0530 INDICATED CONDITION:

O SUPPLY AIR PRESSURE TO CIV-34 <80 PSIG AS SENSED BY CI-411-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW. l 0 CIV-34 VALVE POSITION INDICATING MID POSITION. I OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO CIV-34.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-077 SHEET Cl-20 SENSING ELEMENT: CI-411-PS AR-303 Rev. 24 Page 43

ENCLOSURE 1 (Page 42 of 87)

() ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 i

SW ISO VALVE

/UR I FAILURE EVENT POINT 0531

!Z INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO CIV-35 <80 PSIG AS SENSED BY CI-412-PS.

l

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

0 INSTRUMENT AIR PRESSURE INDICATING LOW.

o CIV-35 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO CIV-35.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-077 SHEET CI-21

() SENSING ELEMENT: CI-412-PS AR-303 Rev. 24 Page 44

. 1 ENCLOSURE 1 (Page 43 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 1

SW ISO VALVE I I

AIR FAILURE 1

l EVENT POINT 0532 EZ INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO CIV-40 <80 PSIG AS SENSED BY CI-413-PS.

I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

O CIV-40 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

, o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO CIV-40, i

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-077 SHEET CI-22 m

d SENSING ELEMENT: CI-413-PS AR-303 Rev. 24 Page 45

4 #

ENCLOSURE 1 (Page 44 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14

('"N

(

SW ISO VALVE AIR FAILURE EVENT POINT 0533 Z EZ INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO CIV-41 <80 PSIG AS SENSED BY Cl-414-PS.

l l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

[}

o INSTRUMENT AIR PRESSURE INDICATING LOW.

o CIV-41 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO CIV-41.

i DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-077 SHEET CI-23

() SENSING ELEMENT: CI-414-PS AR-303 Rev. 24 Page 46 i

ENCLOSURE 1 (Page 45 of 87) ,

i ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14  !

II. i SW ISO VALVE AIR FAILURE l

I I

I I EVENT POINT 1855 Z l INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-12 <80 PSIG AS SENSED BY SWV-12-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

o SWV-12 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-12.

l DISCUSSION:

- ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-06 SENSING ELEMENT: SWV-12-PS AR-303 Rev. 24 . Page 47

ENCLOSURE I (Page 46 of 87) l O ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 V

l I

I I

I SW ISO VALVE I AIR i FAILURE l

I I I I  ;

l EVENT POINT 1856 l 1

, INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-35 <80 PSIG AS SENSED BY SWV-35-PS.

I l

,9 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

V o INSTRUMENT AIR PRESSURE INDICATING LOW.

o SWV-35 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

, o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-35. l DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-06 SWV-35-PS

( SENSING ELEMENT:

AR-303 Rev. 24 Page 48

ENCLOSURE I (Page 47 of 87)

( ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 l

l l

l l SW ISO VALVE I AIR FAILURE l

I l

l l EVENT POINT 1857

~

INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-37 <80 PSIG AS SENSED BY SWV-37-PS.

t REDUNDANT INDICATION f;!ICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

o SWV-37 VALVE POSITION INDICATING MID POSITION.

1 OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-37.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-07 SENSING ELEMENT: SWV-37-PS

. AR-303 Rev. 24 Page 49

ENCLOSURE 1 (Page 48 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 I

I I

I I SW ISO VALVE I AIR FAILURE l

I l

l l EVENT POINT 1858 2 l INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-39 <80 PSIG AS SENSED BY SWV-39-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.  ;

o SWV-39 VALVE POSITION INDICATING MID POSITION. l OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-39.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET CW-07

( SENSING ELEMENT: SWV-39-PS AR-303 Rev. 24 Page 50

ENCLOSURE 1 (Page 49 of 87)

[ ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 I

I

. I I

I SW ISO VALVE I AIR FAILURE l

I l

l l EVENT POINT 1859 i

INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-41 <80 PSIG AS SENSED BY SWV-41-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

1 o SWV-41 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-41.

! DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-08 SENSING ELEMENT: SWV-41-PS AR-303 Rev. 24 Page 51

ENCLOSURE 1 (Page 50 of 87)

ESAB-A ANNUNCIATOR RESPONt. ESAB-A-02-14 C-02-14 4

(}

SW ISO VALVE AIR FAILURE EVENT POINT 1860 EZ

, INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-43 <80 PSIG AS SENSED BY SWV-43-PS. ,

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

O SWV-43 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-43.

d DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-08

() SENSING ELEMENT: SWV-43-PS AR-303 Rev. 24 Page 52

ENCLOSURE 1 (Page 51 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14

(

l l

I I I I i l I I I SW ISO VALVE I I - AIR FAILURE l l I I I I I I I I EVENT POINT 1861 4

M INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-45 <80 PSIG AS SENSED BY SWV-45-PS.

1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

(

o INSTRUMENT AIR PRESSURE INDICATING LOW.

o SWV-45 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-45.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-09

( SENSING ELEMENT: SWV-45-PS AR-303 Rev. 24 Page 53

ENCLOSURE 1 (Page 52 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 I I l 1 I I I I l l SW ISO VALVE ,

I I AIR I FAILURE l l I i l l l I l l EVENT POINT 1862 l

INDICATED CONDITION:

o SUPPLY AIR PRESSURE,TO SWV-79 <80 PSIG AS SENSED BY SWV-79-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

O SWV-79 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-79.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-14

( SENSING ELEMENT: SWV-79-PS AR-303 Rev. 24 Page 54

j ENCLOSURE 1 l

(Page 53 of 87)

ESAB-A-02-14 C-02-14

(]

kJ ESAB-A ANNUNCIATOR RESPONSE SW ISO VALVE AIR FAILURE

~

EVENT POINT 1863 EZ INDICATED CONDITION: l 0 SUPPLY AIR PRESSURE TO SWV-80 <80 PSIG AS SENSED BY SWV-80-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: i o INSTRUMENT AIR PRESSURE INDICATING LOW.

o SWV-80 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-80.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-15

( SENSING ELEMENT: SWV-80-PS AR-303 Rev. 24 Page 55

ENCLOSURE I (Page 54 of 87)

O ESAB-A ANNUNCIAT00 RESPONSE ESAB-A-02-14 C-02-14 V

I I

I I I l l SW ISO VALVE l l AIR I I FAILURE I I I I

-l . . .

l l EVENT POINT 1864 INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-81 <80 PSIG AS SENSED BY SWV-81-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW. I c SWV-81 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-81.

1 l

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-16 SENSING ELEMENT: SWV-81-PS AR-303 Rev. 24 Page 56

ENCLOSURE 1 (Page 55 of 87)

, ESA8-AANNUNCIATORSESPONSE ESA8-A-02-14 C-02-14 l l .

I I I I I I I I SW ISO VALVE I I AIR FAILURE l l I l l l l l l l EVENT POINT 1865 INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-82 <80 PSIG AS SENSED BY SWV-82-PS.

hl w

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

0 INSTRUMENT AIR PRESSURE INDICATING LOW.

o SWV-82 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-82.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-17 SENSING ELEMENT: SWV-82-PS AR-303 Rev. 24 Page 57

ENCLOSURE _1 (Page 56 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14

}

l SW ISO VALVE  !

JUR FAILURE EVENT POINT 1866 INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-83 <80 PSIG AS SENSED BY SWV-83-PS.

(' ) REDUNDANT INDICATION WHICH WILL VERIFY ALARM

o INSTRUMENT AIR PRESSURE INDICATING LOW.

O SWV-83 VALVE POSITION INDICATING MID POSITION.

/

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-83.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-0S6 SHEET SW-18

() SENSING ELEMENT: SWV-83-PS AR-303 Rev. 24 Page 58

l

. 1 ENCLOSURE 1 i (Page 57 of 87) j l

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 l l I I I I I I I I I SW ISO VALVE  !

I I AIR FAILURE l l '

I l l l l l l l l l EVENT POINT 1867 INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-84 <80 PSIG AS SENSED BY SWV-84-PS. )

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

O SWV-84 VALVE POSITION INDICATING HID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-84.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-19 SENSING ELEMENT: SWV-84-PS AR-303 Rev. 24 Page 59

ENCLOSURE 1 (Page 58 of 87)

Og ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 O

l l l l l l l l 1 I $W ISO VALVE I I AIR FAILURE l l I I I I I I l l EVENT POINT 1868 INDICATED CONDITION:

o SUPPLY AIR PRESSURE 10 SWV-85 <80 PSIG AS SENSED BY SWV-85-PS. .

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

o SWV-85 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-85.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-20 SENSING ELEMENT: SWV-85-PS AR-303 Rev. 24 Page 60

ENCLOSURE I (Page 59 of 87)

O ESAB-A-02-14 C-02-14

(> ESAB-A ANNUNCIATOR RESPONSE l l l l l l l l l l SW ISO VALVE I I AIR FAILURE

, l l I l l l l l l l EVENT POINT 1869 INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-86 <80 PSIG AS SENSED BY SWV-86-PS. ,

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

o SWV-86 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-86.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-21 SENSING ELEMENT: SWV-86-PS AR-303 Rev. 24 Page 61

^

I l . ,

l ENCLOSURE 1 (Page 60 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 (O) l I I I I I I I I I SW ISO VALVE I I AIR FAILURE l l I I l l l l '

l l EVENT POINT 1870 l

INDICATED C0i3ITION:

o SUPPLY AIR PRESSURE TO SWV-109 <80 PSIG AS SENSED BY SWV-109-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

I o INSTRUMENT AIR PRESSURE INDICATING LOW.

o SWV-109 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-109.

l l

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-22 SENSING ELEMENT: SWV-109-PS AR-303 Rev. 24 Page 62

ENCLOSURE 1 (Page 61 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 l l l l l l l l 1 i SW ISO VALVE I I AIR FAILURE l l I I l l l l l -l EVENT POINT 1871 INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-110 <80 PSIG AS SENSED BY SWV-110-PS.

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW. i o SWV-110 VALVE POSITION INDICATING MID POSITION. l l

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-110.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-23

) SENSING ELEMENT: SWV-110-PS AR-303 Rev. 24 Page 63

  • s ENCLOSURE 1 (Page 62 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 I .

I I

I l SW ISO VALVE I AIR FAILURE l

I l

l l EVENT POINT 1872

~

INDICATED CONDITION: 1 l

o SUPPLY AIR PRESSURE TO SWV-353 <80 PSIG AS SENSED BY SWV-353-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

O SWV-353 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-353.

l DISCUSSION:

ENCLOSURE I 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-24

( SENSING ELEMENT: SWV-353-PS AR-303 Rev. 24 Page 64

- ENCLOSURE 1 (Page 63 of 91) l 1

ESAB-A ANNUNCIATOR RESPONSE ESAB-A'02-14 C-02-14 l l l l l I l t

i I l I SW ISO VALVE I I AIR i FAILURE l l i

I I l l

- \

l I l l EVENT POINT 1873 1

INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-354 <80 PSIG AS SENSED BY SWV-354-PS.

I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW. i o SWV-354 VALVE POSITION INDICATING MID POSITION.  !

l OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-354.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-25 SENSING ELEMENT: SWV-354-PS AR-303 Rev. 24 Page 65

ENCLOSURE 1 (Page 64 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14

. l l

l l

l SW ISO VALVE I AIR FAILURE l

I I

I i l EVENT POINT 1874

~

INDICATED CONDITION:

i o SUPPLY AIR PRESSURE TO SWV-355 <80 PSIG AS SENSED BY SWV-355-PS. j O

d REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

O SWV-355 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-355.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-26 I SENSING ELEMENT: SWV-355-PS AR-303 Rev. 24 Page 66

ENCLOSURE 1 (Page 65 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14 SW ISO VALVE AIR FAILURE EVENT POINT 1875 INDICATED CONDITION:

o SUPPLY AIR PRESSURE TO SWV-151 <80 PSIG AS SENSED BY SWV-151-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

o SWV-151 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.  ;

i o INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-151.

4 l

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-29 SENSING ELEMENT: SWV-151-PS AR-303 Rev. 24 Page 67

ENCLOSURE 1 (Page 66 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-02-14 C-02-14

(

l fl l

. l ,,

SW ISO VALVE I ' AIR FAILURE l l I I I I I I l l EVENT POINT 1876 INDICATED CONDITION:

, o SUPPLY AIR PRESSURE TO SWV-152 <80 PSIG AS SENSED BY SWV-152-PS.

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATING LOW.

. o SWV-152 VALVE POSITION INDICATING MID POSITION.

OPERATOR ACTION FOR A VALID ALARM:

o REFER TO AP-470.

O INVESTIGATE CAUSE OF LOW PRESSURE TO SWV-152.

DISCUSSION:

ENCLOSURE 1 0F AP-470 LISTS AIR OPERATED VALVES AND THEIR FAILED POSITION.

REFERENCES:

DRAWING 208-056 SHEET SW-30 SENSING ELEMENT: SWV-152-PS AR-303 Rev. 24 Page 68

ENCLOSURE 1 (Page 67 of 87) l ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-01 C-03-01 RC-3 HIGH PRESS BISTABLE TRIP EVENT POINT 0939 INDICATED CONDITION:

o RCS PRESSURE <1500 PSIG ,

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ES STATUS LIGHT RC-3 ' BISTABLE TRIPPED' IS LIT.

O ACTUATION CHANNEL CABINET #3 BISTABLE OUTPUT STATE LIGHT ' BRIGHT'.

OPERATOR ACTION FOR A VALID ALARM:

c REFER TO E0P .

1 J

DISCUSSION:

THIS ALARM INDICATES ONE CHANNEL TRIPPED IN A 2 OUT OF 3 HPI LOGIC.

REFERENCES:

DRAWING 208-028 SHEET ESA-24 SENSING ELEMENT: BT-3 ES ACTUATION RELAY l

AR-303 Rev. 24 Page 69

. _ - __ _ a

  • s ENCLOSURE 1 (Page 68 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-02 C-03-02 r( ';

RC-6 LOW PRESS BISTABLE TRIP EVENT POINT 0926 INDICATED CONDITION:

o RCS PRESSURE <500 PSIG ,

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

([ )

o ES STATUS LIGHT RC-6 ' BISTABLE TRIPPED' IS LIT.

O ACTUATION CHANNEL CABINET #3 BISTABLE OUTPUT STATE LIGHT ' BRIGHT'.

1 OPERATOR ACTION FOR A VALID ALARM: l o REFER TO E0P l l

l DISCUSSION:

THIS ALARM INDICATES ONE CHANNEL TRIPPED IN A 2 OUT OF 3 LPI LOGIC.

REFERENCES:

DRAWING 208-028 SHEET ESB-39

() SENSING ELEMENT: BT-9 ES ACTUATION RELAY AR-303 Rev. 24 Page 70

~

ENCLOSURE 1 (Page 69 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-03 C-03-03 RWP-1

. TRIP EVENT POINT 0001 INDICATED CONDITION:

1 o RWP-1 BREAKER IS OPEN WITH CONTROL HANDLE IN NORMAL AFTER START POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM
o Gr.EEN LIGHT ON WITH A RED FLAG ON CONTROL STATION.

O RWP-28 AUTO START.

O RW-23-PI SW RW SUPPLY PRESSURE LOW.

OPERATOR ACTION FOR A VALID ALARM:

, o ENSURE RWP-2B START.

o INVESTIGATE CAUSE OF PUMP TRIP.

O CHECK BREAKER FOR DROPPED RELAY TARGETS.

1 DISCUSSION:

RWP-2B STARTS ON DECREASING HEADER PRESSURE AT 7 PSIG.

REFERENCES:

DRAWING 208-050 SHEET RW-01 SENSING ELEMENT: RWP-1 CONTROL SWITCH CONTACTS CS/SC, CS/0, RW-63-PS1 I

AR-303 Rev. 24 . Page 71

. ENCLOSURE 1 (Page 70 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-04 C-03-04 SW RW PUMP MOTOR OVERLOAD EVENT POINT 0002 INDICATED CONDITION:

o RWP-1 MOTOR AMPS >115% RATED LOAD

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH MOTOR AMPS.

O RW-23-PI SW RW SUPPLY PRESSURE LOW.

OPERATOR ACTION FOR A VALID ALARM:

o START RWP-2A OR RWP-2B, SECURE RWP-I.

o INVESTIGATE CAUSE OF OVERLOAD.

4 DISCUSSION:

THIS ALARM INDICATES EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT RELAY ACTUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP. j

REFERENCES:

ORAWING 208-050 SHEET RW-01 I

, SENSING ELEMENT: 51 RELAY (INSIDE 4160V BREAKER CUBICLE)

AR-303 Rev. 24 Page 72

ENCLOSURE 1 (Page 71 of 87)

ESAB-A-03-05 C-03-05

.Cy ESAB-A ANNUNCIATOR RESPONSE

%J SW RW SYSTEM PRESS LOW EVENT POINT 0007 INDICATED CONDITION:

o NUCLEAR SERVICES RAW WATER HEADER PRESS <7 PSIG AS SENSED BY RW-63-PSI.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RWP-28 AUTO START. ,

o POSSIBLE RW PUMP TRIP. l OPERATOR ACTION FOR A VALID ALARM:

o ENSURE RWP-2B AUTO START.

o INVESTIGATE CAUSE OF LOW PRESSURE.

O CHECK INTAKE AREA AND INTAKE SCREENS FOR OBSTRUCTIONS TO FLOW. 1 0 CHECK FOR PROPER VALVE ALIGNMENT FOR RUNNING RW PUMP. l l

l i

DISCUSSION:  ;

I l

l

REFERENCES:

DRAWING 208-050 SHEET RW-03 l SENSING ELEMENT: RW-63-PS1 1

. AR-303 Rev. 24 Page 73

_j

  • a ENCLOSURE._1 (Page 72 of 87)
ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-06 C-03-06

-- RWP AND  ;

SW RW PP RUNNING EVENT POINT 0024 INDICATED CONDITION:

o RWP-1 AND RWP-2A AND/0R RWP-2B RUNNING AT THE SAME TIME.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INDICATION OF MORE THAN ONE PUMP RUNNING.

o RW SYSTEM HEADER PRESSURE HIGH.

O RWP-2B AUTO START ALARM.

OPERATOR ACTION FOR A VALID ALARM:

o SECURE RW PUMP (S) NOT REQUIRED.

DISCUSSION:

IF RWP-1 IS RUNNING WITH EITHER RWP-2A AND/0R RWP-2B, THEN RWP-1 WILL TRIP AFTER 15 SECONDS.

REFERENCES:

DRAWING 208-050 SHEET RW-01 SENSING ELEMENT: 52S/A RELAY (RWP-1 RWP-2A,RWP-2B 4160V BREAKER CUBICLES) l l

AR-303 Rev. 24 Page 74

. I ENCLOSURF__1 (Page 73 of 87) l

)

ESAB-A-03-07 C-03-07

,q ESAB-A ANNUNCIATOR RESPONSE O ,

1 l

1 SW RW  ;

1 __ TEMP ,

__ HIGH l EVENT POINT 0054 i

! INDICATED CONDITION:

o RAW WATER SUPPLY TO SW HEAT EXCHANGERS TEMPERATURE IS >91.5* F AS SENSED i BY RW-19-TS. l 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

, o RW TEMPERATURE INDICATION RW-19-TI OPERATOR ACTION FOR A VALID ALARM:

o NOTIFY AUXILIARY BUILDING OPERATOR TO SHUTDOWN RW PIT RECIRC BY FAILING

- CLOSED RWV-150 OR CLOSING RWV-149, o ENSURE SW RW TEMPERATURE CONTROL SURVEILLANCE KEY SWITCH IS IN THE l NORMAL POSITION.

DISCUSSION:

RWV-150 IS THE SW TEMPERATURE CONTROL VALVE AND RECIRCULATES "B" SIDE SW l RW BACK TO THE "B" SIDE RW PIT AS NECESSARY TO MAINTAIN SW SYSTEM TEMPERATURE AT 82* F (WHEN GULF 0F MEXIC0/ RAW WATER TEMPERATURE IS BELOW 80* F).

RWV-150 IS A SPRING CLOSE/ AIR TO OPEN CONTR01: VALVE AND FAILS CLOSED ON:

LOSS OF DC POWER TO CONTROL VALVE SOLEN 0ID, LOSS OF AIR SUPPLY PRESSURE, l AND RWP-2B AUTO START, RWP-3B AUTO START. j REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS. I

REFERENCES:

DRAWING 210-583, MAR 86-12-02-04 4

( SENSING ELEMENT: RW-19-TS AR-303 Rev. 24 Page 75

I ENCLOSURE 1 (Page 74 of 87)

ESAB-A-03-08 C-03-08 (x g ESAB-A ANNUNCIATOR RESPONSE

'w/

I l ,

i I I i l i I FLUSH WATER I I SYSTEM PRESS I I LOW l l l l EVENT POINT 1517 I I I I I li INDICATED CONDITION: )

o FLUSH WATER SYSTEM PRESSURE <75 PSIG AS SENSED BY D0-2-PS.

I (O,) REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-416 FOR ALTERNATE RWP FLUSH WATER SUPPLIES DISCUSSION:

~

THE RWP'S ARE CURRENTLY SUPPLIED WITH DEMIN WATER VIA D0V-128.

OP-416 LISTS TWO ALTERNATIVE SUPPLIES, DOMESTIC WATER VIA 1 0F 2 FILTERS AND PUMPS OR NUCLEAR SERVICES WATER VIA D0V-210 OR D0V-238. IF THE l FLUSH WATER PRESSURE DROPS BELOW RWP DISCHARGE PRESSURE, THEN THE RUNNING RWP'S WILL SUPPLY THEIR OWN FLUSH WATER FOR THE RUNNING RWP'S.

REFERENCES:

DRAWING 208-022-D0-13 k.J SENSING ELEMENT: D0-2-PS AR-303 Rev. 24 Page 76 I l

' ~

ENCLOSURE 1 (Page 75 of 87)

-g ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-09 C-03-09 I I I I I I I I FLUSH WATER I I PUMP I I TRIP I I EVENT POINT 1513 I I -

i j

1 I

INDICATED CONDITION:

o DOP-2A MOTOR NOT ENERGIZED WITH CONTROL SWITCH IN NORt:AL AFTER START POSITION.

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O GREEN LIGHT ON WITH A RED FLAG ON D0P-2A CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-416 ' DOMESTIC WATER SUPPLY SYSTEM' FOR ALTERNATE RWP FLUSH WATER SUPPLIES.

O INVESTIGATE CAUSE OF PUMP TRIP.

1 DISCUSSION:

REFERENCES:

DRAWING 208-022-00-02 SENSING ELEMENT: DOP-2A CONTROL SWITCH CONTACTS CS/SC, CS/0 AR-303 Rev. 24 Page 77

ENCLOSURE 1 (Page 76 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-Z-03-09 C-03-09 I I

. l l l l FLUSH WATER I I I PUMP I I TRIP I I I I i EVENT POINT 1515 l l l 1 I I  :

I I I I INDICATED CONDITION:

o DOP-2B HOTOR NOT ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER START POSITION.

. 1

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON DOP-2B CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-416 ' DOMESTIC WATER SUPPLY SYSTEM' FOR ALTERNATE RWP FLUSH '

WATER SUPPLIES.

o INVESTIGATE CAUSE OF PUMP TRIP.

DISCUSSION:

REFERENCES:

DRAWING 208-022-D0-03 SENSING ELEMENT: DOP-2B CONTROL SWITCH CONTACTS CS/SC, CS/0 O

AR-303 Rev. 24 Page 78

. =

ENCLOSURE 1 (Page 77 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-10 C-03-10 l I I I FLUSH WATER I I PUMP I I AUTO START

  • I I I I I I l l EVENT POINT 1514 l l l I I I INDICATED CONDITION:

o D0P-2A MOTOR ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER STOP POSITION.

iO U

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON D0P-2A CONTROL STATION.

OPERATOR ACTIONS FOR A' VALID ALARM:

o INVESTIGATE CAUSE OF PUMP AUTO START.

o REFER TO OP-416 ' DOMESTIC WATER SUPPLY SYSTEM' FOR ALTERNATE RWP FLUSH WATER SUPPLIES.

DISCUSSION:

REFERENCES:

DRAWING 208-022-D0-02 3

SENSING ELEMENT: 00P-2A CONTROL SWITCH CONTACTS CS/SC, CS/0 AR-303 Rev. 24 Page 79

ENCLOSURE I (Page 78 of 87)

I g ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-10 C-03-10 V  ;

l i I I I FLUSH WATER I I PUMP I I AUTO START I I I I I I I l l EVENT POINT 1516 l l l I I I I .

INDICATED CONDITION:

o 00P-28 MOTOR ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER STOP POSITION.

v REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON D0P-2B CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF PUMP AUTO START.

o REFER TO OP-416 ' DOMESTIC WATER SUPPLY SYSTEM' FOR ALTERNATE RWP FLUSH WATER SUPPLIES.

DISCUSSION: ,

REFERENCES:

DRAWING 208-022-00-03 I SENSING ELEMENT: D0P-2B CONTROL SWITCH CONTACTS CS/SC, CS/0 AR-303 fiev. 24 Page 80

ENCLOSURE 1 (Page 79 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-Il C-03-ll

(-].

LJ l I

'l l I I I I I I I I DH TO PZR l l SPRAY VALVE I l OPEN l I EVENT POINT 0240 l I I INDICATED CONDITION: ,

i o DHV-91 NOT FULL CLOSED AND RCS PRESSURE >284 PSIG AS SENSED BY  !

RC-3A-PS7.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DHV-91 VALVE POSITION INDICATION.

o RCS PRESSURE INDICATION.

OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE CAUSE OF INCREASING PRESSURE.

O CLOSE DHV-91 IF RCS PRESSURE >284 PSIG.

l DISCUSSION:

REFERENCES:

DRAWING 208-021 SHEET DH-16 SENSING ELEMENT: RC-3A-PS7 AR-303 Rev. 24 Page 81

,w -- -- -~ . - - - -

ENCLOSURE 1 (Page 80 of 87) p ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-ll C-03-11 O l l I I I I I I I I I I DH TO PZR l l SPRAY VALVE I I OPEN l l EVENT POINT 1316 I I l

l INDICATED CONDITION:

o RCV-53 NOT FULL CLOSED AND RCS PRESSURE >200 PSIG AS SENSED BY RC-3A-PS7.

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ,-

0 RCV-53 VALVE POSITION INDICATION.

O RCS PRESSURE INDICATION.

OPERATOR ACTION FOR A VALID ALARM: l 0 INVESTIGATE CAUSE OF INCREASING PRESSURE.

o CLOSE RCV-53 IF RCS PRESSURE >200 PSIG.

DISCllSSION:

REFERENCES:

DRAWING 208-047 SHEET RC-16 f SENSING ELEMENT: RC-3A-PS7 G

AR-303 Rev. 24 Page 82

ENCLOSURE 1 (Page 81 of 87) l ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-12 C-03-12 U -

I I

I I

I DH VALVE .

l ACISYSTEM l l i TROUBLE l l J

l _

EVENT POINT 1233 I I INDICATED CONDITION:

o ACI SUBSYSTEM 1 OR 2 BYPASS KEY IN BYPASS POSITION.

O O ACI SUBSYSTEM 1 OR 2 MODULE REMOVED.

o DHV-3 OR DHV-4 NOT FULL CLOSED AND RCS PRESSURE >284 PSIG.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DHV-3 VALVE POSITION INDICATION.

O DHV-4 VALVE POSITION INDICATION.

O RCS PRESSURE INDICATION.

OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE CAUSE OF INCREASING PRESSURE.

O CLOSE DHV-3 AND/0R DHV-4 IF RCS PRESSURE >2B4 PSIG.

DISCUSSION:

o DHV-3 ACI USES RC-147-PT FOR RCS PRESSURE AND CAN BE SEEN ON THE REMOTE l SHUTDOWN PANEL, OR SPDS o DHV-4 ACI USES RC-132-PT FOR RCS PRESSURE AND CAN BE SEEN IN ES CABINET #3.

REFERENCES:

DRAWING 208-028 SHEET ESAB-6 A

SENSING ELEMENT: BT-13.BT-14 ES ACTUATION RELAYS

(]

AR-303 Rev. 24 Page 83

ENCLOSURE 1 (Page 82 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-13 C-03-13 b,A l l l l 1 I I I I I I I DH DROPLINE l l VALVES j l l OPEN l l l l l l Z EVENT POINT 0214 i

INDICATED CONDITION,: ,

l o DHV-3 NOT CLOSED AND RCS PRESSURE >200 PSIG AS SENSED BY 3RC-3A-PS8.

REDUNDANT INDICATION WHICH WILL VERIFY AltRM:

o DHV-3 VALVE POSITION INDICATI0s:.

o RCS PRESSURE INDICATION.

l OPERATOR ACTION FOR A VALID ALARM:

o CLOSE DHV-3 IF RCS FRESSURE >284 PSIG.

DISCUSSION: .

REFERENCES:

DRAWING 208-021 SHEET DH-03

g l SENSING ELEMENT
3RC-3A-PS8

(

AR-303 Rev. 24 Page 84

= . _ . _ - _

ENCLOSURE 1 (Page 83 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-13 C-03-13

, b I I I I I I I I I I I I DH DROP LINE l l VALVES l I OPEN I I I I

~

EVENT POINT 0215 s

INDICATED CONDITION:

l

~

o DHV-4 NOT CLOSED AND RCS PRESSURE >200 PSIG AS SENSED BY 3RC-3A~-PS9.

r REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DHV-4 VALVE POSITION INDICATION.

o RCS PRESSURE INDICATION.

OPERATOR ACTION FOR A VALID ALARM:

o CLOSE DHV-4 IF RCS PRESSURE >284 PSIG.

t

DISCUSSION

REFERENCES:

DRAWING 208-021 SHEET DH-04 SENSING ELEMENT: 3RC-3A-PS9 AR-303 Rev. 24 Page 85

ENCLOSURE 1 (Page 84 of 87)

ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-13 C-03-13 I I I I I I I I I I I I DH DROP LINE l l VALVES I I OPEN l l l l Z EVENT POINT 0216 INDICATED CONDITION:

oDHV-41NdTCLOSEDANDRCSPRESSURE>200PSIGASSENSEDBY3RC-3A-PS4.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DHV-41 VALVE POSITION INDICATION. f o RCS PRESSURE INDICATION.

OPERATOR ACTION FOR A VALID ALARM:

I o CLOSE DHV-41 IF RCS PRESSURE >284 PSIG.

DISCUSSION:

REFERENCES:

DRAWING 208-021 SHEET DH-13

^

SENSING ELEMENT: 3RC-3A-PS4 AR 303 Rev. 24 Page 86

. u ENCLOSURE 1 l

- (Page 85 of 87) i ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-14 C-03-14

'v SEISMIC SYSTEM TROUBLE

_____ EVENT POINT 1709 INDICATED CONDITION:

'o SEISMIC EVENT OCCURRED i

p.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

.o INDICATION AT SEISMIC PANEL.

o NOTIFICATION OF SEISMIC EVENT.

OPERATOR ACTION FOR A VALID ALARM:

o CHECK SEISMIC PANEL FOR CAUSE OF ALARM. ,

o REFER TO AP-961.

4 DISCUSSION:  ;

I&C SHOP PERFORMS ALL SURVEILLANCE PROCEDURES AND MAGNETIC TAPE REPLACEMENT WHEN REQUIRED.

REFERENCES:

SENSING ELEMENT: SEISMIC INSTRUMENT PANEL.

l AR-303 Rev. 24 Page 87

4 u ENCLOSURE 1 (Page 86 of 87)

,- ESAB-A ANNUNCIATOR RESPONSE ESAB-A-03-14 C-03-14

(

l l l l l l l l l l I I SEISMIC l l SYSTEM l l TROUBLE l l l l l l EVENT POINT 1710 1

INDICATED CONDITION:

O SEISMIC PANEL LOSS OF POWER G

b REP 9NDANT INDICATION WHICH WILL VERIFY ALARM:

0 INDICATION AT SEISMIC PANEL.  !

l OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE SEISMIC PANEL FOR CAUSE OF LOSS OF POWER ALARM.

o REFER TO OP-700C.

DISCUSSION:

POWER SUPPLY IS ACDP-52 BREAKER 31 p

REFERENCES:

SENSING ELEMENT: SEISMIC INSTRUMENT PANEL.

AR-303 Rev. 24 Page 88

. > s.

ENCLOSURE 1

~~

(Page 87 of 87)

^ ESAB A ANNUNCIATOR RESPONSE ESAB-A-03-14 C-03-14 I I I I I I I I I I I I SEISMIC I I SYSTEM TROUBLE l l l l ~

l l I I EVENT POINT 1711 1 -

INDICATED CONDITION:

o SEISMIC RECORDER END OF TAPE.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INDICATION AT SEISMIC PANEL.

OPERATOR ACTION FOR A VALID ALARM:

o INVESTIGATE SEISMIC PANEL RECORDER, IF AT THE END OF TAPE, GENERATE A WORK REQUEST TO REPLACE MAGNETIC TAPE (S).

l DISCUSSION:

I&C SHOP PERFORMS ALL SURVEILLANCE PROCEDURES AND MAGNETIC TAPE REPLACEMENT WHEN REQUIRED.

REFERENCES:

t SENSING ELEMENT: SEISMIC INSTRUMENT PANEL.

AR-303 Rev. 24 Page 89 (LAST PAGE)