3

-Q

\\

SOUTH CAROLINA ELECTRIC & GAS COMPANY POST OFFICE 764 cotuualA, south CAROUNA 29218 O. w. Onnon. Jn.

vC. p..S.o*"'

June 12, 1985 g

NUCLEAR OPERATIONS j

Q Dr.

J. Ne ls on Grace a

M Regional Administrator U.S. Nuclear Regulatory Commission c.o Region II, Suite 2900 W

101 Marietta Street, N.W.

Atlanta, Georgia 30323

SUBJECT:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. N P F-12 Response to Notice of Violation NRC Inspection Report 85-19

Dear Dr. Grace:

Attached:is South Carolina Electric and Gas Company's response for the Violation as addressed in Enclosure 1 of NRC Inspection Report 85-19.

If.there are any questions, please call us at your convenience.

Very truly y rs, O.

W. Dixon, Jr.

CJM:0WD/ led Attachment C.

L.

Ligon ( NS RC) ec:

V.

C.

Summer T.

C.

Nichols, Jr./0.

W.

Dixon, Jr.

K.

E.

Nodland E.

H.

Crews, Jr.

R.

A.

S t ou gh G.

Pe r c iva l E.

C.

R ob e r t s W.

A. Williams, Jr.

C.

W.

Hehl J.

B.

Knotts, Jr.

D.

A.

Nauman S.

D.

Hogge Group Managers I &E (Washington)

O.

S.

Bradham NPCF C.

A.

Price File S.

R.

Hunt f'

J O

.7~E o/ r I

o i

P

-e s

b

-ENCLOSURE 1 RESPONSE TO NOTICE OF-VIOLATION INSPECTION REPORT 85-19 I.'

ADMISSION OR DENIAL OF THE ALLEGED VIOLATION

' South Carolina Electric and-Gas Company (SCE&G) is in agreement with-the alleged violation.

II.

REASON FOR THE VIOLATION The; violation is a t trib ut ed -to inadequate' procedure guidance.

The two (2) examples cited in the violation have been eva lu a t ed, and it has been verified that the f ailure to meet

-the Lower Limit of Detection (LLD) for Xe-138 had no me a su r ab le impact upon gaseous e f fluent projections or instantaneous concentration limitations.

III.

CORRECTIVE STEPS TAKEN AND RESULTS ACHIEVED Calculations : and trial runs have been performed on the detectors and cou n t ing geometries used for gaseous releases.

As-a! result of this-~ testing, Health Ph ys ic s Procedure (HPP) 808, " Sample Ana lys is," was revised on June 4, 1985.

The procedure now specifies a maximum time period of 45 minutes between the times of sampling and ana lys is.

The 45 minute limitation will ensure that all LLD's for Technical Specification isotopes are consistently met.

IV.

CORRECTIVE ACTION TAKEN TO AVOID FURTHER VIOLATION The revision to HPP-808 is c on s id e r ed to be adequate correc tive action to pr'even t lfu tur e: violation s.

V.

DATE OF FULL COMPLIANCE SCE&G was in fu ll compliance on June 4, 1985.