s

,,-

,-

ENCLOSURE 2 NOTICE OF DEVIATION Florida Power Corporation Docket No. 50-302 Crystal River Unit 3 License No. DPR-72 The following deviation was identified during an inspection conducted on April 26 - May 24, 1985.

Final Safety Analysis Report (FSAR) section 8.2.3.1 describes the operation of the emergency diesel generator air start system and specifies that the air start system will provide starting air at 225 - 250 psig and that sufficient air is stored in the air reservoirs for six successive start attempts.

Contrary to the above:

Procedures SP-301 (Shutdown Daily Surveillance Log), SP-300 (Operating

-

Daily Surveillance Log) and SP-354A/B (Emergency Diesel Generator Monthly Test) allow emergency diesel generator air start system pressure to be a minimum'of 215 psig; On March 29, 1985, the air start system pressure for the "A" Emergency

-

Diesel Generator (EDG-3A) was observed to be at approximately 200 psig; and,

-

The licensee is unable to provide justification that six successive start attempts could be accomplished at these reduced air start system pressures.

Please provide, in writing within 30 days of the date of this Notice, a description of corrective actions regarding this deviation, actions taken to avoid further deviations, and the dates when these actions were or will be completed.

Security or safeguards information should be submitted as an enclosure to facilitate withholding it from public disclosure as required by 10 CFR 2.790(d)

or 10 CFR 73.21.

Date:

8507100551 850621 PDR ADOCK 05000302 O

PDR

- - _ __

.

,

^

JUN 21 1985

.

,,

.,,

Florida Power Corporation

Enclosures:

1.

Notice of Violation 2..

Notice of Deviation 3.

Inspection Report No. 50-302/85-21 cc w/encls:

E. M. Howard, Director Site Nuclear Operations P. F. McKee, Nuclear Plant Manager G. R. Westafer, Manager Nuclear Operations Licensing and Fuel Management bec w/encls:

NRC Resident Inspector Document Control Desk State of Florida

,

/

.R ll:sa V. ':iera V o niee Je 06//4/85 06g/85 06/ 1/85 06// 7/85 l

-..

.

.,, -

m

-

e n

a---s

-