Text
,
i
.p OPERATING DATA REPORT DOCKET NO.
50-369 DATE 15-85 COMPLETED BY cr.n. Raavis TELEPHONE 704-373-7567 OPERATING STATUS
- 1. Unit Name:
McGuire 1 Notes
- Nameplate Rating
- 2. Reporting Period: Anril 1.
1985-Anril an. 14gg (Gross MWe) calculated as
- 3. Licensed Thermal Power (MWr):
3411 1450.000 MVA x.90 power
- 4. Nameplate Rating (Gross MWe):
1305*
factor per Page a.ii, 1180 NUREG-0020.
- 5. Design Electrical Rating (Net MWe):
- 6. Maximum Dependable Capacity (Gross MWe):
- 7. Maximum Dependable Capacity (Net MWe):
11R0
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Give Reasons:
None
- 9. Power Level To Which Restricted,if Any (Net MWe):
None
- 10. Reasons For Restrictions.lf Any:
l This Month Yr.-to.Date Cumulative
- 11. Hours in Reporting Period 719.0 2 879.0 29 927.0
- 12. Number Of Hours Reactor Was Critical 432.9 2 514.9 20 678.5
- 13. Reactor Reserve Shutdown Hours
- 14. Hours Generator On.Line 418.2 2 494.3 20 456.8
- 15. Unit Reserve Shutdown Hours
- 16. Gross Thermal Energy Generated (MWH) 596 719 6 7'16 582 5'l 540 882
.' 17. Gross Electrical Energy Generated (MWH) 182 660 2 295 076 18 524 301
- 18. Net Electrical Energy Generated (MWH) 163 438 2 192 146 17 567 401
- 19. Unit Service Factor 58.2 86.6 68.4
- 20. Unit Availability Factor 58.2 86.6 68.4
- 21. Unit Capacity Factor (Using MDC Net) 19.3 64.5 49.8
- 22. Unit Capacity Factor (Using DER Net) 19.3 64.5 49.8
- 23. Unit Forced Outage Rate 5.9 4.2 14.9
- 24. Shutdowns Scheduled Over Next 6 Months (Type. Date.and Duration of Each):
Currently Refueling
- 25. If Shut Down At End Of Report Period. Estimated Date of Startup:
- 26. Units in Test Status iPrior to Commercial Operation):
Forecast Achieved i
INITIA L CRITICALITY -
INITIAL ELECTRICITY COMMERCIAL OPERATION i
8505290078 850430 e
PDR ADOCK 05000369 R
PDR (9/77 L
t
\\
. ~.
i AVERAGE DNI'LY UNIT. POWER LEVEL f.
DOCKET NO.
50-369' T
UNIT Mennire 1 DATE 05/15/85 COMPLETED BY J.A. Reavis TELEPHONE 704-373-7567 NONTH Anril. 1985 DAY.
AVERAGE DAILY POWER LEVEL DAY-AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Ne t) 1 669 17 300
'2 670 18 301 3-670 19 124
'4-672 20 5~
605 21 r
6
-345 22 L
7
-281 23
'8:
284 24'
^
, '9 32 25 i'
' 1!0 184 26 11_
302-
'27 1
[:
f12 305 28 i~
'13 304 L
29
.14 297.
30 15
~300 31 I_
-16 301
~'
l.
f..
lNSTRUCTIONS-t-
.p On this format, list the average ' daily unit power level in MWe-Net for each day in the reporting month.
Compute to the nearest whole megawatt.
i-l.
~,_--,_..m_
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.
50-369 UNIT NAME Mecuire 1 DATE 5/15/85 REPORT MONTH April 1985 COMPLETED BY J. A. Reavis TELEPHONE 704-373-7567 "s.
O gj License Cause & Corrective y
c S7 -
"c u." $
g a
h.o Action to No.
Date
% $5 8
.8 % e Event
~
g a;
n.
s-o e
o s a:
m N 55 E
E5S Report #
NO
$.o Prevent Recurrence 0
18-p.85-04-01 S
F ZZ ZZZZZZ Core conservation to prevent concurrent refueling outages.
3
!85-04-09 F
26.02 A
1 SF ACCUMU Cold Leg Accumulator Boron concentration out of specification.
19-p 85-04-10 S
F ZZ ZZZZZZ Core conservation to prevent concurrent j
refueling outages.
I' 4
85-04-19 S
274.80 C
A RC FUELXX End of Cycle 2 Refueling Outage l
l
~ ~. - - - - -
.__L 1
2 3
4 Reason:
Method:
Exhibit G - Instructions S
uled A-Equipment Failure (Explain) 1-Manual for Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3-Automatic Scram Event Report (LER)
D-Regulatory Restriction 4-Other (Explain)
File (NUREG-0161)
E-Operator Training 6 License Examination F-Adninistrative 5
G-Operational Error (Explain)
Exhibit I - Same Source Il-Other (Explain)
'(4/771
=
DOCKET NO:
50-369 UNIT:
McGuire 1 DATE:
5/15/85 NARRATIVE SUbefARY Month:
April 1985 The unit ~ operated at 62% at the beginning of the month. This was done to extend operation and' reduce the overlap of its refueling outage with respect to the l0conee 2 and McGuire 2 refueling outages. The unit was forced off-line when Boron concentration in a Cold Leg Accumulator fell below Tech Spec limit on April 9.
- The ' unit _ returned to service on April 10,' and increased power to 34% to further extend its operation. The unit shutdown for refuel'on April 19.-
L
MONTHLY REFUELING INFORMATION REQUEST j
McGuire Unit 1 1.
Facility name:
- 2. : Schedul'ed next refueling shutdown:
Currently Refueling t
3.
Scheduled restart following refueling:
4.
Will refueling or resumption of operation thereafter require a technical specification change or other license amendment?
Yes If yes, what will these be?
Technical Specification Revision If no, has reload design and core configuration been reviewed by Safety Review Committee regarding unreviewed safety questions?
N/A 5.
Scheduled date(s) for submitting proposed licensing action and supporting information:
N/A 6.
Important licensing considerations (new or different design or supplier, unreviewed design or performance analysis methods, significant changes in design or new operating procedures).
N/A J
193 7.
Number of fyel assemblies (a) in the core:
[
(b) in the spent fuel pool:
91 8.
Present licensed fuel pool capacity:
1463 Size of requested or planned increase:
9.
Projected date of last refueling which can be accommodated by present licensed capacity:
August 1991 DUKE POWER COMPANY Date:
May 15, 1985 i
Name of
Contact:
J. A. Reavis Phone:
704-373-7567 i
I
-_y
_, _ - -. - ~ _ _ _, _.,
OPERATING DATA REPORT DOCKET NO.
50-370 DATE 05-13-5)
COMPLETED BY
.T a. Raavis TELEPHONE 7n4-373-7567 OPERATING STATUS
- 1. Unit Name:
McGuire 2 Notes
- Nameplate Rating
- 2. Reporting Period: April
- 1. 1985-April 30. 1985 (Gross Mwe) calculated as
- 3. Licensed Thermal Power (MWt):
3411 1450.000 MVA x.90 power 1305*
factor per Page 111,
- 4. Nameplate Rating (Gross MWe):
1180 NUREG-0020.
- 5. Design Electrical Rating (Net MWe):
- 6. Maximum Dependable Capacity (Gross MWe):
- 7. Maximum Dependable Capacity (Net MWe):
11R0
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Give Reasons:
None
- 9. Power Level To which Restricted,If Any (Net MWe):
None
- 10. Reasons For Restrictions,if Any:
l' This Month Yr.-to-Date Cumulative
- 11. Hours in Reporting Period 719.0 2 879.0 10 223.0
- 12. Number Of Hours Reactor Was Critical 0.0 595.0 6 773.1
- 13. Reactor Reserve Shutdown Hours i
- 14. Hours Generator On-Line 0.0 594.9 6 686.0
- 15. Unit Reserve Shutdown Hours
- 16. Gross Thermal Energy Generated (MWH) 1 948 246 21 318 917
.17. Gross Electrical Energy Generated (MWH) 247 699 628 7 537 351
- 18. Net Electrical Energy Generated (MWH)
-6 627 658 081 7 215 881
- 19. Unit Service Factor 0.0 20.7 65.4
- 20. Unit Availability Factor 0.0 20.7-65.4
- 21. Unit Capacity Factor (Using MDC Net) 0.0 19.4 59.8
- 22. Unit Capacity Factor (Using DER Net) 0.0 19.4 59.8 23.- Unit Forced Outage Rate 0.0 0.0 14.9
- 24. Shutdowns Scheduled Over Next 6 Months (Type.Date and Duration of Each):
None l
l
- 25. If Shut Down At End Of Report Period, Estimated Date of Startup:
Y l-
- 26. Units in Test Status (Prior to Commercial Operation):
Forecast Achieved -
1 INITIAL CRITICALITY INITIAL ELECTRICITY CONIMERCIAL OPERATION i
P/77)
p' 1, :.
?.
AVERAGE DAILY UN!'T POWER LEVEL DOCKET NO.
50-370 UNIT _ McGuire 2 DATE 05/15/85 COMPLETED BY.
J.A. Reavis TELEPHONE 704-373-7567
- MONTHg. April, 1985-
- DAY-AVERAGE. DAILY' POWER LEVEL DAY AVERAGE DAILY POWER LEVEL-(MWe-Net)
(MWe-Ne t) 1 17 z2 18 23-19 4'
20
.5 21 6:
22 7
23
~8 24 9
25
.10 26 111 27 12z 28
.- 13:
29 14 30 15.
31 s
16 u
INSTRUCTIONS
.On this-format,' list the average daily unit power level in MW'e-Net for each day in the reporting month.- Compute to the nearest whole megawatt.
t I
r L
g
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.30-370 UNIT NAME McGuire 2 DATE-5/15/85 REPORT MONTH April 1985 COMPLETED BY J. A. Reavis TELEPHONE 704-373-7567 "s.
O gj License y'
Cause & Corrective c97 "c
o." &
g a
No.
Date
~.
%h 8
2yc Event h
g Action to 5E E
%5$
El BB F
o-e zmo Report #
Prevent Recurrence mo uo 1
85-04-01 S
719.00 C
1 RC FUELXX End of Cycle 1 Refueling Outage I
l a
1 2
3-4 Reason:
Method:
Exhibit G - Instructions S Sc e uled A-Equipment Failure (Explain) 1-Manual for Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3-Automatic Scram Event Report (LER)
D-Regulatory Restriction 4-Other (Explain)
File (NUREG-0161)
E-Operator Training f License Examination i
F-Administrative 5
. G-Operational Error (Explain)
Exhibit I - Same Source II-Other (Explain)
(9/771
7_..
DOCKET NO:
50-370 UNIT:
McGuire 2 DATE:
5/15/85 NARRATIVE
SUMMARY
Month:
April 1985 The unit's refueling outage continued throughout the month of April.
u
c MONTHLY REFUELING INFORMATION REQUEST 1.
Facility name:
McGuire Unit 2 A ril 1986 2.
Scheduled next refueling shutdown:
P 3.
Scheduled' restart following refueling:
June 1986 4.
Will refueling or resumption of operation thereafter require a technical specification change or other license amendment?
Yes If yes, what will these be?
Technical Specification Revision If no, has reload design and core configuration been reviewed by Safety Review Committee regarding unreviewed safety questions?
N/A
- 5. ' Scheduled date(s) for submitting proposed licensing action and supporting information:- N/A 6.
Important licensing considerations (new or different design or supplier, unreviewed design or performance analysis methods, significant changes in design or new operating procedures).
N/A 7.
Number of fuel assemblies (a) in the core:
193 (b) in the spent fuel pool:
60 8.
Present licensed fuel pool capacity:
1463 Size of requested or planned increase:
9.
Projected date of last refueling which can be accommodated by present licensed capacity:
Auenst 1991 DUKE POWER COMPANY Date:
May 15, 1985 Name of
Contact:
J. A. Reavis Phone: 704-373-7567
~ ~
a.
.,N' 6
McGUIRE NUCLEAR STATION Monthly Operating _ Status-Report
- 1... Personnel Expos'ure For the month of March, no individual (s) exceeded 10 percent of their allowable annual:radiationEdo'se limit.
2.'- The totalistation liquid -release _for March has :been compared with.the
-Technical._ Specifications maximum annual dose commitment >and was less~
than 10-percent of.this_. limit.
The total station' gaseous release for March has been compared with the' Technical Specifications maximum' annual; dose. commitment'and was lessLthan 10 percent of-this limit.
f A
DUKE POWER GOMPANY P.O. BOK 33180 CHARLOTrE, N.C. 28242 HALH. TUCKER Tzternoxe vens Pseemswr (704) 373-4531 May 15, 1985
= = * =
Director Office of Inspection and Enforcement U. S Nuclear Regulatory Commission Washington, D. C.
20555 Attention: Document Control Desk Re: McGuire Nuclear Station Docket No. 50-369, -370
Dear Sir:
Please find attached information concerning the performance and operating status of the McGuire Nuclear Station for the month of April, 1985.
Very truly yours, MTA /
Hal B. Tucker JAR:scs Attachments cc: Regional Administrator Mr. Darl Hood U. S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Region II U. S. Nuclear Regulatory. Commission 101 Marietta Street, Suite 2900 Washington, D. C.
20555 Atlanta, Georgia 30323 Mr. Phil Ross American Nuclear Insurers
'U. S. Nuclear Regulatory Commission c/o Dottie Sherman, ANI Library MNBB-5715 The Exchange, Suite 245 Washington, D. C.
20555 270 Farmington Avenue Farmington, Connecticut 06032 INFO Records Center Suite 1500 Ms. Judy Dovers 1100 Circle 75 Parkway Nuclear Assurance Corporation Atlanta, Georgia 30339 5700 Peachtree Parkway Narcross, Georgia 30092 Senior Resident Inspector i
McGuire Nuclear Station
%